6-6 Communications Settings
6-6-3
6-6-4
6-42
Setting High-speed 1:N NT Links (Standard, High-speed)
Setting Ethernet
Select the Comm. Tab from the System Menu, and select NT Link 1:N (1:N NT Link) as the
communications method for serial port A or B.
Press the Detail Button to display the setting items for high-speed 1:N NT Links on the right
side of the screen. Set the unit number and communications speed.
After setting, press the Write Button.
• Communications Conditions for 1:N NT Links
To use Ethernet, select the Comm Tab from the System Menu and press the Enable Button.
The setting items for Ethernet will be displayed on the right side of the screen. Display and
set the network address, node address, IP address, subnet mask, and default gateway. Dis-
play the MAC address and IP address table display.
After setting, press the Write Button.
Unit number
Communications Speed
Reference
Setting item
• The unit numbers that can be set depend on the type of host used, as follows:
• If the Detail Button is pressed for the NS15, the display will switch to the Protocol Set-
ting Dialog Box. Make the settings and press the Write Button. Press the Comm. But-
ton to return to the Comm Tab Page.
• C200HE(-Z):
• C200HG(-Z), C200HX(-Z), CS1G/H, CS1G/H-H, CQM1H, CJ1G, and CJ1G/H-H:
Unit numbers 0 to 3 (up to four PTs for each port of the host)
Unit numbers 0 to 7 (up to eight PTs for each port of the host)
Refer to 4-2 1:N Host Connection for the host settings.
Sets the unit number.
Sets the baud Communications speed.
Function
0 to 7
Standard, high-speed
Settings