6-8 Special Screens
6-56
FINS Communications Test
• Setting and Display Items in Communication Test Screen
• Display Items in Communication Test Screen
Note 1. SID is the source process ID.
1. Set each of the setting items, as follows:
2. Press the Start Button to start transmission.
3. If communications are normal, a response will be received from the transmission destination and
Send to
Send message
Number of
sends
Receive Time-
out
SID (See note 1.)
Received header
Received message
ms
Comment
The sending indicator will remain lit until the transmission is completed.
After transmission, the Receiving indicator will remain lit until reception is completed.
the following items will be displayed. Refer to the FINS Command Reference Manual (Cat. No.
W227) for details on FINS commands and information displayed in comments.
2. The FINS header is the header that precedes the FINS command. Refer to the FINS Com-
Item
Item
mand Reference Manual (Cat. No. W227) for details on FINS commands.
Sets the address of the transmission destination in the format (network ad-
dress).(node address).(unit number).
Sets the following addresses when performing a communications test for a node
connected to serial port A or B.
• Serial port A: 111.1.0
• Serial port B: 112.1.0
Sets the FINS command being to be sent.
Displays the number of times messages are transmitted. The number of times is
fixed to 1.
Sets the time before the message timeout occurs. Displays an error message
when the timeout time is exceeded after transmission.
The setting time is applicable for Ethernet only. For serial communications, the
timeout monitor time set from the Comm Tab is used.
The SID used for transmission is displayed as a hexadecimal.
The SID is incremented between 0 and 0xFF and returns to 0 after 0xFF is
exceeded.
Displays the FINS header that is received. (See note 2.)
Displays the received message.
Displays the time lapsed in ms from sending the FINS command until re-
ceiving the FINS response.
Displays the status, such as "normal completion," according to the comple-
tion code after reception.