NS5-MQ10B-V2 Omron, NS5-MQ10B-V2 Datasheet - Page 251

no-image

NS5-MQ10B-V2

Manufacturer Part Number
NS5-MQ10B-V2
Description
5 Mono Tchsrn,Serial+USB,Bk 60
Manufacturer
Omron
Datasheet

Specifications of NS5-MQ10B-V2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
• Inspection Items
Inspect the PT for the following items to check whether the PT is operating within the speci-
fied criteria. If the PT is outside the criteria, use measures such as improving the operating
environment to conform to the standards, or tightening screws.
Power
supply
Ambient
environment
Mounting
conditions
Parts with
limited
service life
Touch panel
input posi-
tion accu-
racy (NS15
only)
Inspection
Precautions
for Safe Use
items
Power terminal voltage
fluctuation
Ambient temperature
(temperature in control panel)
Ambient humidity
(temperature in control panel)
Presence of dust
Presence of oil
Looseness of fixed mounting
bracket
Connection status of
Connecting Cable
Connectors
Looseness of external wiring
screws
Status of external connecting
cables
Backlight brightness
Battery
Shifted input positions on the
touch panel
Inspection details
• Do not disassemble, repair, or modify the PT.
• Follow all local government regulations, where applicable, when disposing of
the Unit and used batteries.
Allowable voltage range
(24 VDC ±15%)
0 to 50°C
(Refer to Appendix 1.)
35% to 85%
(Refer to Appendix 1.)
No dust accumulated.
No oil between front panel sheet
and molding.
Specified torque.
Fully inserted, locked, and with
No looseness.
No looseness.
No breaks or other damage
Sufficient brightness.
Backlight life (at room tempera-
ture of 25°C) is 50,000 hours,
as a guideline.
5 years (at room temperature of
25°C).
Calibrate the touch panel if the
input positions have shifted.
Criteria
7-2 Inspection and Cleaning
Tester
Thermometer
Temperature meter
Visual inspection
Phillips screwdriver
tester
Visual inspection
Replace every 5
years
Touch panel opera-
tion
Visual inspection
Phillips screwdriver
Phillips screwdriver
Visual inspection,
Inspection means
7-5

Related parts for NS5-MQ10B-V2