CQM1H-CTB41 Omron, CQM1H-CTB41 Datasheet - Page 13

no-image

CQM1H-CTB41

Manufacturer Part Number
CQM1H-CTB41
Description
HS CTR INPUT,4 INPUT
Manufacturer
Omron
Datasheet

Specifications of CQM1H-CTB41

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Power Supply Units
Both AC and DC Power Supply Units are available. The AC
Power Supply Units require a power supply input from 100 to
240 VAC and two of the AC Power Supply Units are equipped
with an auxiliary 24 VDC power supply output.
The CQM1H’s left End Cover is part of the Power Supply Unit.
J SPECIFICATIONS
Note: The total power consumed at 5 VDC and 24 VDC must be less than 30 W.
Item
Supply voltage
Operating voltage
range
Operating frequency
range
Power consumption
Inrush current
Output capacity
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient operating
humidity
Operating environ-
ment
Ground
Construction
Weight
Internal current
consumption
Dimensions (without
cables)
Accessories
A--164
(5 × Current consumed at 5 VDC) + (24 × Current consumed at 24 VDC) ≤ 30 W
Programmable Controller
CQM1-PA203
100 to 240 VAC, 50/60 Hz
85 to 264 VAC
47 to 63 Hz
60 VA max.
30 A max.
5 VDC: 3.6 A (18 W)
20 MΩ min. at 500 VDC between AC external terminals and GR terminals
2,300 VAC 50/60 Hz for 1 min between AC external and GR
terminals, leakage current: 10 mA max.
1,000 VAC 50/60 Hz for 1 min between DC external and GR
terminals, leakage current: 20 mA max.
Conforms to IEC61000-4-4, 2 kV (power lines)
10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 9.8 m/s
Z directions for 80 minutes each (i.e., swept for 8 minutes, 10 times).
147 m/s
Operating: 0° to 55°C (32° to 131°F)
Storage: --20° to 75°C (--4° to 167°F), except battery
10% to 90% RH (no condensation)
No corrosive gas
Less than 100 Ω
Panel mounted
5 kg max.
CQM1H-CPU11:
CQM1H-CPU21/51/61:
CQM1H-CPU11/21: 187 to 571 ¢ 110 ¢ 107 mm (W¢H¢D)
CQM1H-CPU51/61: 187 to 603 ¢ 110 ¢ 107 mm (W¢H¢D)
RS-232C connector (one XM2A-0901 Plug and one XM2S-0911-E Hood) (except CQM1H-CPU11)
CPM2A-BAT01 Battery Set (installed in CPU Unit when shipped)
2
(118 m/s
2
for Contact Output Units) 3 times each in X, Y, and Z directions
CQM1H
CQM1-PA206
120 VA max.
5 VDC: 6 A
24 VDC: 0.5 A
(30 W total)
820 mA at 5 VDC
840 mA at 5 VDC
CQM1-PA206
CQM1-PA216
CQM1-PA216
100 or 230 VAC (select-
able), 50/60 Hz
85 to 132 VAC or 170 to
264 VAC
CQM1-PA203
CQM1-PD026
24 VDC
20 to 28 VDC
50 W max.
5 VDC: 6 A
(30 W)
CQM1-PD026
2
in the X, Y, and

Related parts for CQM1H-CTB41