SMART2200RM2U Tripp Lite, SMART2200RM2U Datasheet - Page 3

UPS, 120V, 2200VA

SMART2200RM2U

Manufacturer Part Number
SMART2200RM2U
Description
UPS, 120V, 2200VA
Manufacturer
Tripp Lite
Datasheet

Specifications of SMART2200RM2U

Capacity (va / W)
2200VA / 1920W
No. Of Outlets
6
Supply Voltage Typ
120VAC
Output Voltage
120V
Backup Time - Full Load
8min
Length
19"
Width
17.5"
Height
3.5"
Weight
65lb
Mounting Type
Rack
Power Rating
2200 VA
Tower / Rackmount
Rackmount
Frequency
60Hz
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Output AC waveform
(battery mode)
INPUT
Rated input current (at
maximum load)
Nominal Input Voltage(s)
Supported
UPS input connection type
Input circuit breaker
UPS Input cord length (ft.)
UPS Input cord length (m)
Recommended Electrical
Service
BATTERY
Full load runtime (minutes)
Half load runtime
(minutes)
DC system voltage (VDC)
Battery recharge rate
(included batteries)
Replacement battery
cartridge (internal UPS
battery replacement)
Battery Access
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
Pure Sine wave
16A (120V), 16.4A (110V), 16.7A (100V)
100V AC; 110V AC; 120V AC
5-20P
20A
10
3
20A 120V
5 min. (1920w)
13 min. (960w)
48
Less than 4.5 hours from 10% to 90%
RBC94-2U
Front panel battery access door
Hot-swappable, user replaceable batteries
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Voltage reduction of 12% applies when input is between 127 and 145 (120V), 116 and 133 (110V), 106 and
121 (100V)
Voltage boost of 12% applies when input voltage is between 96 and 108 (120V), 87 and 99 (110V), 83 and 90
(100V)
Voltage boost of 24% applies when input voltage is between 83 and 95 (120V only)
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches
support nominal voltage selection