PKM4610PI Ericsson Power Modules, PKM4610PI Datasheet - Page 3

no-image

PKM4610PI

Manufacturer Part Number
PKM4610PI
Description
DC/DC Power Supply Single-OUT 3.3V 20A 66W 8-Pin Quarter-Brick
Manufacturer
Ericsson Power Modules
Type
Step Downr
Series
PKMr
Datasheet

Specifications of PKM4610PI

Package
8Quarter-Brick
Output Current
20 A
Output Voltage
3.3 V
Input Voltage
36 to 75 V
Number Of Outputs
1
Output Power
66 W
Product
Isolated
Input Voltage Range
36 V to 75 V
Output Voltage (channel 1)
3.3 V
Output Current (channel 1)
20 A
Isolation Voltage
1.5 KV
Package / Case Size
Quarter Brick
Output Type
Isolated
Lead Free Status / Rohs Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
PKM4610PI
Manufacturer:
ERICSSON
Quantity:
38
Part Number:
PKM4610PI
Manufacturer:
SEMIKRON
Quantity:
530
Part Number:
PKM4610PI
Manufacturer:
ERICSSON/爱立信
Quantity:
20 000
Part Number:
PKM4610PI2
Manufacturer:
ERICSSON
Quantity:
292
Part Number:
PKM4610PILA
Manufacturer:
ERICSSON
Quantity:
492
Part Number:
PKM4610PILA
Manufacturer:
ERICSSON/爱立信
Quantity:
20 000
Part Number:
PKM4610PIP
Manufacturer:
ERICSSON
Quantity:
228
Prepared (also subject responsible if other)
SEC/D Kevin Chen
Approved
PKM 4000 PI series
DC/DC converters, Input 36-75 V, Output 35 A/126 W
Safety Specification
General information
Ericsson Power Modules DC/DC converters and DC/DC
regulators are designed in accordance with safety
standards IEC/EN/UL60950, Safety of Information
Technology Equipment.
IEC/EN/UL60950 contains requirements to prevent injury
or damage due to the following hazards:
On-board DC-DC converters are defined as component
power supplies. As components they cannot fully comply
with the provisions of any Safety requirements without
“Conditions of Acceptability”. It is the responsibility of the
installer to ensure that the final product housing these
components complies with the requirements of all
applicable Safety standards and Directives for the final
product.
Component power supplies for general use should comply
with the requirements in IEC60950, EN60950 and
UL60950 “Safety of information technology equipment”.
There are other more product related standards, e.g.
IEEE802.3af “Ethernet LAN/MAN Data terminal equipment
power”, and ETS300132-2 “Power supply interface at the
input to telecommunications equipment; part 2: DC”, but
all of these standards are based on IEC/EN/UL60950 with
regards to safety.
Ericsson Power Modules DC/DC converters and DC/DC
regulators are UL60950 recognized and certified in
accordance with EN60950.
The flammability rating for all construction parts of the
products meets requirements for V-0 class material
according to IEC 60695-11-10.
The products should be installed in the end-use
equipment, in accordance with the requirements of the
ultimate application. Normally the output of the DC/DC
converter is considered as SELV (Safety Extra Low
Voltage) and the input source must be isolated by
minimum Double or Reinforced Insulation from the primary
circuit (AC mains) in accordance with IEC/EN/UL60950.
Electrical shock
Energy hazards
Fire
Mechanical and heat hazards
Radiation hazards
Chemical hazards
Checked
PRODUCT SPECIFICATION
No.
1/1301-BMR631
Date
2006-11-3
Isolated DC/DC converters
It is recommended that a slow blow fuse with a rating
twice the maximum input current per selected product be
used at the input of each DC/DC converter. If an input filter
is used in the circuit the fuse should be placed in front of
the input filter.
In the rare event of a component problem in the input filter
or in the DC/DC converter that imposes a short circuit on
the input source, this fuse will provide the following
functions:
The galvanic isolation is verified in an electric strength test.
The test voltage (V
1500 Vdc or 2250 Vdc for 60 seconds (refer to product
specification).
Leakage current is less than 1 μA at nominal input voltage.
24 V DC systems
The input voltage to the DC/DC converter is SELV (Safety
Extra Low Voltage) and the output remains SELV under
normal and abnormal operating conditions.
48 and 60 V DC systems
If the input voltage to Ericsson Power Modules DC/DC
converter is 75 Vdc or less, then the output remains SELV
(Safety Extra Low Voltage) under normal and abnormal
operating conditions.
Single fault testing in the input power supply circuit should
be performed with the DC/DC converter connected to
demonstrate that the input voltage does not exceed
75 Vdc.
If the input power source circuit is a DC power system, the
source may be treated as a TNV2 circuit and testing has
demonstrated compliance with SELV limits and isolation
requirements equivalent to Basic Insulation in accordance
with IEC/EN/UL60950.
Non-isolated DC/DC regulators
The input voltage to the DC/DC regulator is SELV (Safety
Extra Low Voltage) and the output remains SELV under
normal and abnormal operating conditions.
Isolate the faulty DC/DC converter from the input
power source so as not to affect the operation of
other parts of the system.
Protect the distribution wiring from excessive
current and power loss thus preventing
hazardous overheating.
Technical Specifi cation
EN/LZT 146 310 R1B Nov 2006
© Ericsson Power Modules AB
Rev
PA1
iso
) between input and output is
Reference
3 (3)
3

Related parts for PKM4610PI