G2R1SNDC12S Omron, G2R1SNDC12S Datasheet

Electromechanical Relay SPDT 10A 12VDC 278Ohm Socket

G2R1SNDC12S

Manufacturer Part Number
G2R1SNDC12S
Description
Electromechanical Relay SPDT 10A 12VDC 278Ohm Socket
Manufacturer
Omron
Type
General Purpose Relayr
Datasheet

Specifications of G2R1SNDC12S

Contact Arrangement
SPDT
Dc Coil Voltage
12 V
Coil Current
43.2 mA
Mounting
Socket
Relay Construction
Non-Latching
Coil Voltage Dc
12V
Contact Form
1 Form C
Voltage Rating (vdc)
125V
Voltage Rating (vac)
440V
Dropout Volt (min)
1.8VDCV
Coil Resistance
278Ohm
Pick-up Voltage (max)
8.4VDC
Maximum Power Rating
300W/2.5KVA
Operate Time
15ms
Contact Current Rating
10A
Coil Suppression Diode
No
Push To Test Button
Yes
Led Indicator
Yes
Seal
Unsealed
Product Depth (mm)
13mm
Product Length (mm)
29mm
Operating Temp Range
-40C to 70C
Pin Count
5
Mounting Style
Socket
Termination Style
Quick Connect
Package / Case
Dust Cover
Lead Free Status / Rohs Status
Compliant
Slim and Space-saving Power Plug-in Relay
■ Lockable test button models now available.
■ Built-in mechanical operation indicator.
■ Provided with nameplate.
■ AC type is equipped with a coil-disconnection self-diagnostic
■ High switching power (1-pole: 10 A).
■ Environment-friendly (Cd, Pb free).
■ Wide range of Sockets also available.
Model Number Structure
Model Number Legend
1. Relay Function
2. Number of Poles
3. Contact Form
4. Contact Type
Ordering Information
List of Models
G2R
Note: When ordering, add the rated coil voltage and "(S)" to the model number. Rated coil voltages are given in the coil ratings table.
Plug-in terminal
General-purpose Relay
G2R-@-S
function (LED type).
Blank:
1:
2:
Blank:
Blank:
1
Example: G2R-1-S 12 VDC (S)
-
General-purpose
1 pole
2 poles
SPDT
Single
2
3
General-purpose
LED indicator
LED indicator with test button
Diode
LED indicator and diode
LED indicator and diode with test button
4
Classification
-
5
6
-
Rated coil voltage
7
New model
Unsealed
Enclosure
rating
5. Terminals
6. Classification
7. Rated Coil Voltage
S:
Blank:
N:
D:
ND:
NI:
NDI:
AC/DC
DC
Coil ratings
Plug-in
General-purpose
LED indicator
Diode
LED indicator and diode
LED indicator with test button
LED indicator and diode with test button
G2R-1-S
G2R-1-SN
G2R-1-SNI (S)
G2R-1-SD
G2R-1-SND
G2R-1-SNDI (S)
SPDT
Contact form
CSM_G2R-_-S_DS_E_3_1
G2R-2-S
G2R-2-SN
G2R-2-SNI (S)
G2R-2-SD
G2R-2-SND
G2R-2-SNDI (S)
DPDT
LR
1

Related parts for G2R1SNDC12S

G2R1SNDC12S Summary of contents

Page 1

General-purpose Relay G2R-@-S Slim and Space-saving Power Plug-in Relay ■ Lockable test button models now available. ■ Built-in mechanical operation indicator. ■ Provided with nameplate. ■ AC type is equipped with a coil-disconnection self-diagnostic function (LED type). ■ High switching ...

Page 2

Accessories (Order Separately) Connecting Sockets Track/surface-mounting Socket Applicable Relay model Screwless clamp terminal • P2RF-05S (See note.) 1 pole + G2R-1-S(N)(D)(ND)(NI)(NDI) (P2CM-S (option)) • P2RF-08S (See note.) 2 poles + G2R-2-S(N)(D)(ND)(NI)(NDI) (P2CM-S (option)) Note: Use of the P2CM Clip & ...

Page 3

Contact Ratings Number of poles 1 pole Resistive load Load (cosφ 250 VAC; Rated load VDC Rated carry current 10 A Max. switching voltage 440 VAC, 125 VDC Max. switching current ...

Page 4

... DC resistive load DC inductive load 1 (L ms) 0 100 1000 Switching voltage (V) Endurance Plug-in Relays G2R-1-S 5,000 250-VAC/30-VDC 1,000 resistive load 500 250-VAC inductive load (cosφ = 0.4) 100 30-VDC inductive load (L/R = 7ms) 50 Switching current (A) Ambient Temperature vs Maximum Coil Voltage ...

Page 5

... Dimensions Note: All units are in millimeters unless otherwise indicated. Relays with Plug-in Terminals SPDT Relays G2R-1-S, G2R-1-SN, G2R-1-SNI (S) G2R-1-SD, G2R-1-SND, G2R-1-SNDI (S) 29 max. 0.5 4.75 5.2 5.2 17.5 DPDT Relays G2R-2-S, G2R-2-SN, G2R-2-SNI (S) G2R-2-SD, G2R-2-SND, G2R-2-SNDI (S) 29 max. 0.5 2 19.4 Terminal Arrangement/Internal Connections ...

Page 6

Track/Surface Mounting Sockets P2RF-05-S Option (with ejector and Standard model label attached) P2RF-08-S Option (with ejector Standard model and label attached) Accessories for P2RF-@-S Socket Bridge Insulating coating 1.2 dia. conductor (See note 1.) 38.2 max. Terminal ...

Page 7

P2RF-05-E P2RF-05-E Five, M3.5×7 85.5 max. 3.5-dia. hole 16.0 max. P2RF-08-E P2RF-08-E 1.5 2 Eight, M3×8 85.5 max. 3.5-dia. hole 5 16.0 max. P2RF-05 P2RF-05 7 Five, M3 71.5 max. 4 19.5 max. P2RF-08 P2RF-08 7 Eight, M3.5 ...

Page 8

Mounting Height of Relay with Track/Surface Mounting Sockets P2RF-@ 62.0 66.5 P2RF-@-S 72.0 28.6 (5.30) Back-connecting Sockets P2R-05P (1-pole 4.5 15 1.2 4 3.5 1 P2R-08P (2-pole) 0 2.8 1.5 7.5 ...

Page 9

P2R-05A (1-pole) 7 0.3 6.7 3.8 5 16.7 Five 1.8-dia. holes 6 Terminal plate thickness: 0.3 P2R-08A (2-pole 0 2.6 2.8 1.5 Eight 1.2-dia. holes 7.5 Terminal plate thickness: 0.3 ...

Page 10

Mounting Tracks PFP-100N, PFP-50N 4 1,000 (500 recommended to use a panel 1.6 to 2.0 mm thick. End Plate PFP pan head screw Precautions Cation ...

Page 11

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...