15.904 Altech, 15.904 Datasheet

no-image

15.904

Manufacturer Part Number
15.904
Description
Circuit Breakers MA0.6 0.40-0.63A Motor Protector
Manufacturer
Altech
Series
MAr
Datasheet

Specifications of 15.904

Product Type
Circuit Breakers
Current Rating
0.63 Amp
Voltage Rating
277 VoltsAC
Mounting Style
DIN Rail
Termination Style
Screw
Circuit Function
ON/OFF
Features
Adjustable Trip Miniature Circuit Breakers/ Manual Motor Controllers
Height
89.5 mm
Illuminated
No
Length
68 mm
Product
Thermal Magnetic Circuit Breakers
Width
44 mm
Number Of Poles
3 Poles
Actuator Type
Handle
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
44
MA- Series
Three Phase Adjustable Trip
Miniature Circuit Breakers/
Manual Motor Controllers
The MA was designed to handle the high
inrush loads of 3 phase transformers,
power supplies, motors, etc. The MA
protects wiring and equipment from
damage caused by the three major
classes of over-current, yet greatly reduc-
es the number of nuisance trips in high
starting and inrush current circuits.
An IEC device with excellent ratings under
a UL listing at 480Y/277V (including group
ratings) and at 500V under international
standards, the Altech/ABL Sursum MA
provides short and long term cost effective
circuit protection for USA and/or export
applications. The short term advantages
include: (1) adjustable thermal trip allows
finalization of initial designs before
procurement of the load equipment is
complete; (2) snap-on mounting for readily
available, internationally standardized DIN
Rail saves panel layout design time as well
as installation and change labor; (3) large
cage-clamp terminals with screws suitable
to power screwdrivers, simplifies and
speeds wiring; (4) convenient switched
disconnect during factory testing and/or
initial start-up saves time and aggravation.
The key long term advantage is customer
satisfaction and proven over-current pro-
tection of wiring and equipment (and the
lack of rework/repair costs).
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as
NFPA-70 Tables 430-248, 430-249, 430-250; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc.
Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.
a The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher
MA016UM
MA025UM
MA040UM
MA063UM
MA1.0UM
MA1.6UM
MA2.5UM
MA4.0UM
MA6.3UM
MA10UM
MA16UM
MA20UM
MA25UM
MA32UM
MA40UM
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)
Cat. No.
Altech Corp.
®
Current
Rated
0.16A
0.25A
0.40A
0.63A
• 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
1.0A
1.6A
2.5A
4.0A
6.3A
10A
16A
20A
25A
32A
40A
0.16/0.19/0.22/0.25
0.25/0.30/0.35/0.40
0.40/0.48/0.56/0.63
0.1/ 0.12/0.14/0.16
0.63/0.75/0.87/1.0
1.0/1.2/1.4/1.6
1.6/1.9/2.2/2.5
2.5/3.0/3.5/4.0
4.0/4.8/5.6/6.3
6.3/7.5/8.7/10
16/17/18.5/20
20/21.5/23/25
Adjustment
10/12/14/16
25/27/30/32
32/34/37/40
Markings
FLA Dial
Voltage Rating
AIC (Interrupt Capacity)
Standard Short Circuit Withstand Rating
(UL/CSA Ratings)
Group Short Circuit Ratings
(UL/CSA Ratings)
Typical Life
Calibration Temperature
Standard Pack and Weight
Terminal Size Acceptability
Type Designation
____
(a) = MA - Manual Motor Controller
(b) = Rated Current
(c) = U - US Housing
(d) = M - Part No. Designation
MA
(a)
CIRCUIT RATING
GROUP SHORT
(and BCP size)
= R - US Housing + Ring Tongue
(max. 1200A
AT 480VAC a
symmetrical
symmetrical
symmetrical
(max. 350A
(max. 350A
42kA
14kA
10kA
or RK5)
(b)
or RK5)
or RK5)
16
__
MCCB
MCCB
MCCB
r ms
RMS
RMS
(c)
__
U
(d)
__
M
HP (HEA)
110-120V
1/2 (4.0)
3/4 (5.6)
1
2
3
3
5
5
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE
Through MA2.5U, ampere rated for motor circuits having a full-
load-amperage (FLA) not exceeding the MA’s general purpose
rated current (RC, equals maximum dial setting) and a locked
rotor current not exceeding 6 times the MA’s RC.
(13.6)
(19.2)
(19.2)
(30.4)
(30.4)
(7.2)
3/4 (3.2)
7
1
10 (32.0)
HP (HEA)
2
3 (11.0)
5 (17.5)
5 (17.5)
1/2
1/2
200V
(25.0)
(See Note for HEA Definition)
(6.0)
(7.8)
480Y/277VAC
0.16A-2.5A: 42kA; 4.0A-16A: 14kA; 20A-40A: 10kA
0.16A-2.5A: 42kA; 4.0A-16A: 14kA
see above
6000 on/off operations with 2xRC
25°C, +0°, -5° (77°F, +0° -9°)
1/450g (1.0 lb.)
Top/Bottom: 18-3 AWG
1
7
7
3/4
10
HP (HEA)
1/2
2
3
5
1/2
1/2
208V
(10.6)
(16.7)
(24.2)
(24.2)
(31.0)
(3.1)
(5.7)
(7.5)
CAN/CSA-C22.2 No.14 certified
UL508 listed
E137938
1
7
10
10
220-240V
HP (HEA)
1
1/2
3
5
5
1/2
(15.2)
(15.2)
(22.0)
(28.0)
(28.0)
(3.6)
(5.2)
(9.6)
10
10
15
20
25
460-480V
2
3
5
HP (HEA)
(3.42)
(14.0)
(14.0)
(21.0)
(27.0)
(34.0)
(4.8)
(7.6)

Related parts for 15.904

15.904 Summary of contents

Page 1

... The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.) Altech Corp. ® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 44 Type Designation MA ...

Page 2

... O OFF O OFF O OFF 52.5mm (2.07 in.) MA/USA Manual Motor Con trol ler Altech Corp. ® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 120 60 MA016UM-MA16UM Phase Controller Thermal Overload ( “Must Trip” Current = 115% of Dial Setting “ ...

Page 3

... Add-on Neutral Pole Standard Pack: Weight: Width: * Please consult Altech for other voltages and your 50Hz application needs. Altech Corp. ® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com 46 * Reset-Hold Voltage = 0. Trip/Coil Type/ Voltage Cat. No. ...

Page 4

... V-EA and MA can also be locked in the on and off position by simply using a common lead or meter seal, which gets fed through the hole in the handle and a corresponding hole in the housing. Altech Corp. ® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com Touch Protector Cat. No. BS.UL Ambient Temperature Adjustment for every 10° ...