E54-CT1 Omron, E54-CT1 Datasheet - Page 5

TRANSFORMER CURRNT 50A E5AK/E5CK

E54-CT1

Manufacturer Part Number
E54-CT1
Description
TRANSFORMER CURRNT 50A E5AK/E5CK
Manufacturer
Omron
Datasheets

Specifications of E54-CT1

Accessory Type
Current Transformer
Input Current
50A
Transformer Mounting
Chassis
Length/height, External
25mm
Output Current
50A
Transformer Type
Current
Current Rating
50A
Mounting Type
Chassis
Supply Voltage
1000 VoltsAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
E5AK/E5CK
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E54CT1
Z2416
■ Characteristics
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication
Indication accuracy (See note 1.)
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Set time (See note 2.)
Program capacity (See note 2.)
Programming method (See note 2.)
Time accuracy (See note 2.)
Sampling period (See note 3.)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Degree of protection
Memory protection
Weight
EMC
Approved standards
2. For Programmable Models.
3. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
Thermocouple:
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type or result of scaling)
0 to 99 hrs 59 min or 0 to 99 min 59 s
8 patterns, 16 steps
Time or ramp setting method
±0.2% (±500 ms) of the set value
Temperature input:
Current/voltage input:
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Malfunction: 10 to 55 Hz, 10 m/s
Destruction: 10 to 55 Hz, 20 m/s
Malfunction: 200 m/s
Destruction: 300 m/s
Operating:
Storage:
Operating:
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case:
Terminals:
Non-volatile memory (number of writings: 100,000 operations)
E5AK: approx. 450 g
E5EK: approx. 320 g
Mounting bracket: approx. 65 g
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
UL61010C-1, CSA 22.2 No. 61010-1
Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
(100 m/s
−10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C
−25°C to 65°C (with no icing)
35% to 85%
IEC standard IP20
IEC standard IP00
2
2
2
min. (approx. 20G), 3 times each in 6 directions
min. (approx. 30G), 3 times each in 6 directions
(approx. 10G) applied to the relay)
250 ms
100 ms
2
2
(approx. 1G) for 10 min each in X, Y, and Z directions
(approx. 2G) for 2 hrs each in X, Y, and Z directions
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
ENV50140:
EN61000-4-4: 2 kV power-line (level 3)
8 kV air discharge (level 3)
10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV I/O signal-line (level 4)
E5AK
5