WOUVT-3-208AC TE Connectivity, WOUVT-3-208AC Datasheet

VOLTAGE MONITORING RELAY 1NO/1NC, 208VAC

WOUVT-3-208AC

Manufacturer Part Number
WOUVT-3-208AC
Description
VOLTAGE MONITORING RELAY 1NO/1NC, 208VAC
Manufacturer
TE Connectivity
Datasheet

Specifications of WOUVT-3-208AC

Contact Configuration
SPST-NO / SPST-NC
Power Consumption
4VA
Supply Voltage Max
208VAC
Relay Mounting
Panel
Control Voltage Type
AC
Contact Voltage Ac Max
120V
Rohs Compliant
No
WOUVT Series, Over/Undervoltage
24
Part Number
Nominal Voltage ..............................
Phase ..............................................
Line Frequency ...............................
Type of Sensing ..............................
Undervoltage Trip ...........................
Overvoltage Trip ..............................
Drop-out Time Delay .......................
Pick-up to Drop-out Differential .....
Output Contacts ..............................
Contact Ratings ..............................
Operating Temperature Range ........
Power Consumption .......................
Notes:
1. Remove black screw for access to the voltage trip and time delay adjustment potentiometer.
2. Clockwise rotation of the voltage adjustment potentiometer will raise the voltage trip point.
3. Clockwise rotation of the time adjustment potentiometer will increase the drop-out time delay.
CII Technologies / P.O. Box 4422 / Santa Barbara, CA 93140 / ph 805.684.4560 / fax 805.684.9679 / e-mail info@kilovac.com / website www.ciitech.com
PRODUCT SPECIFICATIONS
WOUVT
120 VAC to 575 VAC
Single or Three
50-400 Hz
Average of all three phases
70-100% of nominal voltage, screwdriver adjustable
100-125% of nominal voltage, screwdriver adjustable
0.5 to 20 seconds, screwdriver adjustable
2% maximum
One set N.O., One set N.C.
5 amp resistive at 120 VAC or 28 VDC
-40°C to +70°C
4 VA maximum
TERMINAL STRIP
#6 - 32 SCREWS
Function:
Voltage sensitive relays are available for both AC
and DC applications for overvoltage and undervoltage
protection. Combination over/undervoltage relays
provide band-pass capabilities. AC relays are either
single or three-phase type. Three phase relays are
designed to sense the average of the three phases.
Voltage trip points are screwdriver adjustable, and
operation is time-delayed so that momentary volt-
age transients will not cause nuisance tripping.
Operation:
The relay will energize at normal voltage condition.
The normally closed contact (Form B) will open and
the normally open (Form A) will close. The relay will
de-energize after time delay when over or undervoltage
condition is reached.
Sample Part No.
Type:
No. Phases
Line Voltage VAC
Options:
Option "H"
125VDC.
Option "P"
complies with the requirements of ANSI/IEEE C37.90-
1978
See pages 30-38 for additional models.
WOUVT - Over/Undervoltage
1 = Single
3 = Three (line to line)
115
120
200
208
220
230
240
380
Blank - Standard
A = 2 Form A Contacts
B = 2 Form B Contacts
H = 125 VDC Contacts
P = Transient Protection
ANSI/IEEE C37.90-1978
Voltage Sensitive Relays
PART NUMBER SELECTION
provides additional transient protection which
provides for contacts rating of 3 amps @
400
416
440
460
480
525
575
27/59
WOUVT -1-120AC

Related parts for WOUVT-3-208AC