METSEPM1200 SQUARE D, METSEPM1200 Datasheet - Page 4

DIGITAL PANEL METER, 4-DIGIT, 80VAC TO 480VAC

METSEPM1200

Manufacturer Part Number
METSEPM1200
Description
DIGITAL PANEL METER, 4-DIGIT, 80VAC TO 480VAC
Manufacturer
SQUARE D
Datasheet

Specifications of METSEPM1200

No. Of Digits / Alpha
4
Meter Function
Power
Meter Range
50mA To 6A
Digit Height
15mm
Supply Voltage Range
80VAC To 480VAC
Functions and characteristics (cont.)
Type of measurement
Measurement
accuracy*
* Additional error of 0.05% of full scale, for meter input current below 100 mA
Data update rate
Input-voltage
characteristics
Input-current
characteristics
Power supply
Weight
IP degree of protection
Dimensions
Operating temperature
Storage temperature
Humidity rating
Altitude
Measurement CAT
Pollution degree
Protection class
Electrostatic discharge
Immunity to electromagnetic RF fields
Immunity to electrical fast transients
Immunity to surge waves
Conducted disturbance immunity
Damped oscillatory waves immunity
Impulse voltage withstand
Conducted and radiated emissions
Safety construction
CE certification IEC 61010
Complies with Regulation (EC) n° 1907/2006 of Dec 18 2006 named REACH (related to the Registration, Evaluation, Authorization and
restrictions applicable to Chemical substances)
RS-485 port
Integrated LED display
Analog load bar
Electrical characteristics
Mechanical characteristics
Environmental conditions
Electromagnetic compatibility
Safety and standards
Communication
Display characteristics
Current and voltage
Power
Frequency
Power factor
Energy
Inputs
Measured voltage
Permissible overload
Burden
Impedance
Frequency range
CT ratings
Measurement range
Permissible overload
Burden
Impedance
AC
DC
Ride-through time
Burden
Active
Reactive
Apparent
Active
Reactive
Apparent
Primary
Secondary
True RMS up to the 15th harmonic
20 samples per cycle at 50 Hz
1.0 % of reading
1.0 % of reading
2.0 % of reading
1.0 % of reading
0.1 % of reading
1.0 % of reading
IEC 62053-21 Class 1
IEC 62053-23 Class 2
1.0 % of reading
1 sec
V1, V2, V3, Vn
80 - 480 V AC L-L without PTs
Up to 999 kV with external PTs
1.10 Un (480 V L-L)
0.2 VA per phase max.
VLL - 4 Mohms, VLN - 2 Mohms
45 - 65 Hz
1 A - 99.0 kA
1 A - 5 A
50 mA - 6 A (5 mA is the starting)
10 A continuous
0.2 VA per phase max.
< 0.1 ohm
44 - 277 V AC at 50 Hz/60 Hz
44 - 277 V DC
100 ms at 50V
3 VA max.
18 oz (shipping), 1 oz (unpacked)
Front: IP 51; Back: IP 40
Bezel: 96 x 96 mm; Depth: 80 mm behind bezel; Panel cutout: 92 x 92 mm
14°F to 140°F
-13°F to 158°F
5 to 95 % RH non-condensing
6500 ft
III
2
2
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-12
6kV for 1.2/50 µS per IEC 60060-1
CISPR11 Class A
Self extinguishable V0 plastic; UL 508
Yes
2 terminals only; Baud rate up to 19,200 bps; Protocols: Modbus RTU
View 3 parameters together on 3-line, 4-digit-per-line display. Auto-scaling capability
for Kilo, Mega and Giga values. User-selectable default display page. Password
protection for setup parameters
Color-coded analog indicator provides an option to select the full scale of the load bar
based on the sanctioned power limit
PM1200
DM6200

Related parts for METSEPM1200