HPR1-00 Emerson Network Power, HPR1-00 Datasheet

no-image

HPR1-00

Manufacturer Part Number
HPR1-00
Description
350 - 1400 W 19" Rack 1U 4 Slots
Manufacturer
Emerson Network Power
Datasheet

Specifications of HPR1-00

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
HPS3000 Series
3000 Watts
• 3000 W output power
• 40 W/cu-in
• Optional customer provided air
• 1U x 3U form factor
• N+1 Redundant
• Hot-swap
• Internal OR-ing
• 5 V housekeeping
• High efficiency 89% @ 200 Vac,
• Variable speed “smart fans”
• Two year warranty
Distributed Power Bulk Front-End
Single Output
Special Features
Compliance
• POE Isolation
• EMI Class B - EN55022, Level “A”
@ 230 Vac
• EN61000 Immunity
Safety
• UL/cUL
• CSA
• China
• Nemko
• CB Report
• CSA 22.2
100% load
60950
60950
CCC
TUV
60950
Electrical Specifications
Input
Input ra n ge (operating):
Input range (nominal):
Frequency:
Input fusing:
Inrush current:
Power factor:
Harmonics:
Input current:
Holdup time:
Leakage current:
Power line transient:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
47 to 63 Hz
Internal 25 A fuses
≤40 A peak
0.97 typical
Meets IEC 1000-3-2
requirements
19 A max input current
10 ms minimum
1.4 mA
MOV directly after the fuse
Input through Card Edge Connection
on same end as DC output
Both lines fused
Either hot or cold start
Meets EN61000-3-2
@ 50% load
At full rated load
At 240 Vac
Embedded Power for
Business-Critical Continuity
Rev. 02.22.11_81
HPS3000 Series
1 of 8

Related parts for HPR1-00

HPR1-00 Summary of contents

Page 1

HPS3000 Series 3000 Watts Distributed Power Bulk Front-End Single Output Special Features • 3000 W output power • 40 W/cu-in • Optional customer provided air • form factor • N+1 Redundant • Hot-swap • Internal OR-ing • housekeeping • High efficiency 89% @ 200 Vac, 100% load • Variable speed “smart fans” • Two year warranty Compliance • POE Isolation • EMI Class B - EN55022, Level “A” @ 230 Vac • EN61000 Immunity Safety • UL/cUL 60950 • CSA 60950 • China CCC • Nemko TUV • CB Report ...

Page 2

Output Output rating 62 Vsb @ 3 29 Set point 48 V Total regulation range 48 V ± Vsb ± 4% Rated load 3000 W maximum @ 200 Vac Input 1500 W maximum @ 110 Vac Input Minimum load 0 Vsb @ 0.0 A Output noise 480 mV max P-P 100 mV max P-P Output voltage overshoot ± 5% maximum Transient response 5% maximum deviation Max units in parallel Short circuit protection ...

Page 3

Module Information (All units in mm) Embedded Power for Embedded Power for Business-Critical Continuity Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series ...

Page 4

Pin Assignments Bottom Top Pin Pin 1 AC LINE 64 AC LINE 2 AC LINE 63 AC LINE 3 n. NEUTRAL 61 AC NEUTRAL 5 AC NEUTRAL 60 AC NEUTRAL 6 n.c. 59 n.c. 7 n.c. 58 n.c. 8 n.c. 57 n.c. 9 +48 Vdc out 56 ...

Page 5

Input Main Vout T AC_On_Delay T PWOK_On PWOK T sb_On 3.3 V Vout T SB_Vout PS_ON AC_OK AC Input ON / OFF Cycle Timing Diagram T Vout_Holdup T PWOK_Off_ T PWOK_Off_ T PWOK_Off_ T T PWOK_Delay T ...

Page 6

Timing Signal Definitions Turn ON/OFF Timing Item Description Tvout_rise 48 V Output rise time Tsb_on_delay Delay from AC being applied to 5 Vsb being within regulation. Tac_on_delay Delay from AC being applied to all output voltages being within regulation. Tvout_holdup Time all output voltages, including 5 Vsb, stay within regulation after loss of AC. Tpwok_holdup Delay from loss de-assertion of PWOK Tpson_on_delay Delay from PSON# active to output voltages within regulation limits. Tpson_pwok Delay from PSON# de-active to PWOK being de-asserted. Tacok_delay Delay from loss of AC input to de-assertion of ACOK#. Tpwok_on Delay from output voltages within regulation limits to PWOK asserted at turn on. Tpwok_off Delay from PWOK de-asserted dropping out of regulation limits. Tpwok_low Duration of PWOK being in the de-asserted state during an off/on cycle using AC or the PSON# signal. Tsb_vout Delay from 5 Vsb being in regulation being in regulation at AC turn on. Signals and Controls - All Models PSON # ...

Page 7

PWOK# (Power Good) PWOK power good signal and will be pulled LOW by the power supply to indicate that both the outputs are above the regulation limits of the power supply. When any output voltage falls below regulation limits or when AC power has been removed for a time sufficiently long so that power supply operation is no longer guaranteed, PWOK will be de-asserted to a HIGH state. The start of the PWOK# delay time shall be inhibited as long as the 48 V output is in current limit or the 5 Vsb output is below the regulation limit. PSON# Signal Characteristic Signal Type PWOK = High PWOK = LOW Logic level low voltage, Isink=4mA Logic level high voltage, Isource=200µA Sink current, PWOK = low Source current, PWOK = high PWOK delay: T pwok on PWOK rise and fall time Power down delay: T Power Supply Present Indicator (PRESENT#) The PRESENT# signal is primarily used to provide a mechanism by which the host system can sense the number of power supplies physically present (operational or not). This pin is connected to ground in the power supply. AC INPUT Present Indicator (ACOK#) The AC OK# signal is used to indicate presence of AC input to the power supply. This signal shall be connected to 5 Vsb through a resistor on the host system side. A logic “Low” level on this signal shall indicate AC input to the power supply is present. A Logic “High” on this signal shall indicate a loss of AC input to the power supply. Signal Type PRESENT# = Low PRESENT# = High Logic level low voltage, Ising=4mA Logic level high voltage, Isink=50µA ...

Page 8

LED INDICATORS There will be a green POWER LED (PWR) to indicate that AC is applied to the PSU and standby voltage is available when blinking. This same LED should go solid when the 48 V output is enabled and operational. There will be an Amber Power Supply Fail LED (FAIL) to indicate that the power supply has failed and a replacement of the unit is necessary. Faults including UVP, OVP, OTP, or Fan Fail when PSON# is asserted “Logic Low” shall cause the amber LED to turn on. The LED can be turned off by recycling PSON# signal power interruption more than 1 second. The LED shall be off when PSON# is not asserted “Logic Low”. Refer to table 13 for conditions of the LED’s: Power Supply Condition No AC power to PSU AC present / Standby Output On Power supply 48 V output ON and OK Power supply failure (includes overvoltage, overtemperature) Current limit MTBF The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 °C and 40 °C, ambient, at full load. With the power supply installed in a system °C ambient environment and operating at full load, capacitor life shall be 10 years, minimum for ALL electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of > 500,000 hours. Quality Assurance Full QAV testing shall be conducted in accordance with Emerson Network Power Standards with reports available upon request. Warranty ...