2900059 Phoenix Contact, 2900059 Datasheet

no-image

2900059

Manufacturer Part Number
2900059
Description
Terminal Block Interface Modules PSI-GPRS/GSM-MODEM RS232-QB-USA
Manufacturer
Phoenix Contact
Type
Wire to Wirer
Datasheet

Specifications of 2900059

Product
Interface Modules
Mounting Type
DIN rail
Phoenix Part Number
PSI-GPRS/GSM-MODEM/RS232-QB-USA
Voltage, Supply
10-30 VDC
Extended Temperature Range
–25°C to +60°C
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
PSI-GPRS/GSM-MODEM/RS232-QB…
GPRS/GSM modems for the United States and
Canada
INTERFACE
Data Sheet
2534_en_B
1
The PSI-GPRS/GSM-MODEM/RS232-QB… rail-mount-
able modem is specifically designed to meet industrial re-
quirements for remote monitoring and alarm generation. It
provides global access to machines and systems via GSM
connections. A wide range of security functions, such as ad-
justable, selective call acceptance, connection establish-
ment with password protection, and call-back function, pro-
tect the system against unauthorized access. The
integrated TCP/IP stack even allows the implementation of
simple control systems into the GPRS network.
One particularly useful feature for remote system monitoring
is the configurable warning or alarm inputs. If these inputs
are activated, the modem calls user-defined numbers and
sends stored text messages by fax and/or SMS. Using the
switching output, additional functions can be controlled via
SMS messages. To ensure error-free operation in harsh
EMC conditions, the device has high-quality, 3-way isola-
tion and integrated surge protection.
The modem also features an integrated automatic “Sleep”
function to increase battery life, and a wide supply voltage
range of 10 to 30 V DC, making it suitable for universal use.
Modem startup is very easy using plug and play and user-
friendly configuration software.
Description
The PSI-GPRS/GSM-MODEM/RS232-QB is designed exclusively for SELV operation according to IEC 60950/EN
60950/VDE 0805.
The modem may only be connected to devices which meet the requirements of EN 60950 (“Safety of Information
Technology Devices”).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
© PHOENIX CONTACT - 10/2008
The modem is approved for use in both the North American
(850 and 1900 MHz) and European (900 and 1800 MHz)
frequency bands. Each modem is shipped with a country-
specific, pre-installed SIM card, and must be registered for
use through the registration portal before operation. The
registration portal can be accessed at
http://phoenix.diversenet.net
2
GSM (Global System for Mobile communication) and
GPRS (General Packet Radio Service)
Quad band (850 MHz/900 MHz/1800 MHz/1900 MHz)
Password-protected access/call-back function/
selective call acceptance
Integrated TCP/IP stack
Virtual permanent line via GPRS
2 digital inputs and 1 digital output
Alarm sent directly by SMS, e-mail or fax via the
integrated switching input (or via AT commands)
Sends, receives, and evaluates SMS messages
Wide supply voltage range from 10 to 30 V DC
Temperature range of -25 to 60°C
Features

Related parts for 2900059

2900059 Summary of contents

Page 1

... A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for all products listed on the following page: © PHOENIX CONTACT - 10/2008 The modem is approved for use in both the North American (850 and 1900 MHz) and European (900 and 1800 MHz) frequency bands. Each modem is shipped with a country- specific, pre-installed SIM card, and must be registered for use through the registration portal before operation ...

Page 2

... Serial asynchronous UART/NRZ 7/8 data, 1/2 stop, 1 parity, 10/11-bit character length Automatic transmission speed detection (default) or fixed setting at 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps (software adjustable) PSI-GPRS/GSM-MODEM/RS232-QB… Order No. Pcs./Pkt 2900059 1 2900060 1 Order No. Pcs./ Pkt 2707437 ...

Page 3

... Self-test, visualization via LEDs (controller, RAM, EPROM, GSM engine, antenna, EEPROM) The PIN code is saved in the modem. After a voltage interrupt, the modem automatically relogs into the network and logs automatically into the GPRS network. Network bar graph in the configuration software 3 PHOENIX CONTACT ...

Page 4

... According to EN 60068-2-27 15g, 11 ms, half-sine shock pulse 30g, 11 ms, half-sine shock pulse According to IEC 60068-2-32 from a height (without packaging) IP20 Power supply // V.24 (RS-232) 1.5 kV AC, 50 Hz, 1 min. between all ground levels according to DIN EN 61010-1/VDE 0411-1 and DIN EN 60950 4 PHOENIX CONTACT ...

Page 5

... CE Conformance PTCRB Certified AT&T Network Approved PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 2534_en_B PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 PSI-GPRS/GSM-MODEM/RS232-QB… EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 ...