CP2000AC54TEP Lineage Power, CP2000AC54TEP Datasheet - Page 3

Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE

CP2000AC54TEP

Manufacturer Part Number
CP2000AC54TEP
Description
Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE
Manufacturer
Lineage Power
Datasheet

Specifications of CP2000AC54TEP

Product
Linear
Output Power Rating
2000 W
Input Voltage
176 VAC to 275 VAC
Number Of Outputs
1
Output Voltage (channel 1)
54 VDC
Mounting Style
Plug In
Dimensions
13.85 in L x 4 in W x 1.63 in H
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
10/10 Compact Power Line Brochure
Output
Voltage Default
Voltage Adjust Range
- Hardware set via margin pin
- I
Output Current
- Low-Line
- High-Line
Output Power
- Low-Line
- High-Line
Psophometric Noise
Ripple (5Hz to 20MHz)
- RMS
- Peak-to-Peak
Overvoltage Protection
- Delayed
- Immediate
Over Temperature
- Warning
- Shutdown
- Auto-recoverable
Overload Current Limit
- Low Line
Overload Current Limit < 41.5Vo
- High Line
Overload Current Limit > 41.5Vo
- High Line
Overload System Power Up
Overall Regulation
Current Share
Proportional Current Share
External Bulk Load Capacitance
Turn-ON Delay
Turn-ON Rise Time
Turn-ON Overshoot
Load Step Response
Load Step Response ΔI
Load Step Response ΔV
Load Step Response Time
2
C or RS485 set
54 Vdc
44 – 58 Vdc
42 – 58 Vdc
22.2 Adc, 54V
50.5 Adc, 54V
52.4 Adc, 52V
37 Adc, 54V at 2000W
38.4 Adc, 52V at 2000W
1200 Watts
2725 Watts
2000 Watts at nominal 277Vac and Tamb > 45°C
4 mVrms max
250 mVrms
500 mVpk-pk
60 Vdc (200 ms delayed shutdown)
65 Vdc (Instantaneous shutdown above this point.)
5°C
20°C
Temperature hysteresis of approximately 10°C provided between shutdown and restart.
26 Adc Fold_down current limit
36 Adc Fold_down current limit
53-58 Adc Fold_down current limit (FL = 52.4A @ 52V) Hiccup mode with a 10% duty cycle enabled below 39Vdc.
Latched mode current limit optional. Above 275V input the voltage level at which current limit changes states is 45V.
There is a 30 second delay prior to shifting to the lower limit.
Units should be able to be plugged in one at a time and guarantee system start up. Units should stay in current limit for
approximately 20 seconds to guarantee restart.
-2% to +2% includes all variations due to specified load range, drift, and environmental conditions.
-5%FL to +5%FL compared to the average output current delivered by a set of rectifiers. Loads > 50% FL
<7%FL among rectifiers of different output capacities
5,000μF max External capacitance can be increased but the power supply will not meet its turn-ON rise time requirement
5 seconds
Monotonic Turn_ON from 30% to 100% of Vnom above -5°C operation.
Monotonic Turn_On from 60% to 100% of Vnom below -5°C operation.
100 ms standard (PMBus)
5 s telecom (RS-485)
2%
ΔI/Δt slew rate 1A/μs
50%FL Setting time to within regulation requirements
2.0Vdc Minimum load of 2.5A required
2 ms
© 2010 Lineage Power. All rights reserved.
T E C H N I C A L S P E C I FI C A T I ON S – R E C T I F I ER
Page 3

Related parts for CP2000AC54TEP