E5CN-R2MT-500AC100240 Omron Automation, E5CN-R2MT-500AC100240 Datasheet

no-image

E5CN-R2MT-500AC100240

Manufacturer Part Number
E5CN-R2MT-500AC100240
Description
Controller, Digital Temp, 48x48mm, Relay Out, Thermoc In, 100-240VAC, 2Aux Out
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5CN-R2MT-500AC100240

Brand/series
E5CN Series
Communication
USB
Contact Form
SPST-NO
Dimensions
48mmW×48mmH×78mmD
Enclosure Rating
IP00, IP20, IP66
Input Type
RTD/Thermocouple
Ip Rating
IP00, IP20, IP66
Mounting Type
DIN Rail
Number Of Outputs
3
Output Type
Relay
Primary Type
Controller
Special Features
USB Serial
Standards
UL, cULus, CSA
Termination
Terminal Block
Voltage, Supply
100 to 240 VAC
Supply Voltage
100-240 VAC or 24 VAC/VDC
Current Output
4-20 mA DC (E5CN-E5AN-E5EN)
Thermocouple Inputs
K, J, T, L, E, U, N, R, S, B
Platinum Rtd
Pt100 and JPt100
Infrared Sensor
10-70°C, 60-120°C, 115-165°C, 160-260°C
Voltage
0 to 50 mV
Lead Free Status / Rohs Status
RoHS Compliant part
New 48 x 48-mm Basic Temperature
Controller with Enhanced Functions and
Performance. Improved Indication
Accuracy and Preventive Maintenance
Function.
• Indication Accuracy
• New E5CN-U Models (Plug-in Models) with analog inputs and
• A PV/SV-status display function can be set to automatically
• Preventive maintenance for relays in the Temperature Controller
Main I/O Functions
Sensor Inputs
• Universal thermocouple/Pt inputs
• Analog current/voltage inputs
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period
• 250 ms
Basic-type Digital Temperature Controller
E5CN/E5CN-U
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
current outputs.
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.
using a Control Output ON/OFF Counter.
(Models with temperature inputs)
(Models with analog inputs)
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
Event Inputs
• None
• Two
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Long-life relay output (hybrid)
E5CN
Control Output 2
• None
• Voltage output
(for driving SSR)
2-level Display: PV and SV
Auxiliary Outputs
• None
• One
• Two
(48 x 48 mm)
48 × 48-mm
E5CN
4-digit Display
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485
communications
Refer to Safety Precautions on page 66.
48 × 48-mm
E5CN-U
3

Related parts for E5CN-R2MT-500AC100240

E5CN-R2MT-500AC100240 Summary of contents

Page 1

... This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) ( mm) 48 × ...

Page 2

... Temperature input Analog input 1 control output Option Units E53-CN@@@ Applicable Controller CN: E5CN or E5CN-H 2. Function 1 Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection ...

Page 3

... VAC/VDC (current/voltage) 100 to 240 VAC Thermocouple or Silver Resistance thermometer 24 VAC/VDC Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Communications 3-phase heater burnout/SSR failure/ RS-485 Heater overcurrent detection Heater burnout/SSR failure/Heater overcurrent detection Communications RS-485 ...

Page 4

... Voltage output (for driving SSR) E5CN-Q2TU Current output Relay output 1 Voltage output (for driving SSR) E5CN-Q1LU Current output Analog (current/voltage) Relay output 2 Voltage output (for driving SSR) E5CN-Q2LU Current output Relay output None Voltage output (for driving SSR) E5CN-QTDU Current output Relay output Thermocouple or resistance 1 ...

Page 5

... E58-CIFQ1 Terminal Cover Connectable models Terminal block models Model E53-COV17 Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Model Y92S-29 Note: The Waterproof Packing is included with the Controller only for models with terminal blocks. Current Transformers (CTs) ...

Page 6

... model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) E5CN Power 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) consump- 100 to 240 VAC (max ...

Page 7

... JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Voltage E5CN/E5CN-U Infrared temperature Analog sensor input 115 140 120 70°C 165 260 °C °C ° ...

Page 8

... E5CN/E5CN-U Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent ...

Page 9

... Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An Setup Tool port E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN. ✽6 Approved UL 61010-1, CSA C22 ...

Page 10

... ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 E5CN 250 VAC, 30 VDC 3 (resistive load) cosφ ...

Page 11

... USE B Input power supply B • 100 to 240 VAC TC/Pt universal input • 24 VAC/VDC (no polarity) E5CN/E5CN-U A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. E53-CNP03N2 Communications (RS-485) and External Power Supply ...

Page 12

... E5CN/E5CN-U Nomenclature E5CN E5CN-U The front panel is the same for the E5CN and E5CN-U. Operation indicators Dimensions E5CN Terminal Models 48 × Waterproof Packing (Accessory) E5CN-U Plug-in Models 48 × Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 14 Temperature unit Level Key Mode Key ...

Page 13

... E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Two, M3 (depth: 4) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for the Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω Armature Lead E5CN/E5CN-U 100 ∞ 10 Distortion 1 kΩ factor 10 100 mV 100 Ω ...

Page 14

... Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets Protective Cover for finger protection (Y92A-48G) is also available. 16 4.7 69.6 to 77.6 72 × 72 Panel ( mm) 72 × × 48 2.2 4.7 77.3 (to back of E5CN) Terminal Layout/Internal Connections 3 4.5 7.8 (Top View 35.4 Two ...