E5CK-AA1-500 Omron Automation, E5CK-AA1-500 Datasheet

no-image

E5CK-AA1-500

Manufacturer Part Number
E5CK-AA1-500
Description
Controller; 100 to 240 VAC; 4 to 20, 0 to 20 mA mA; 15 VA; Analog; SPST
Manufacturer
Omron Automation
Type
Processr
Datasheet

Specifications of E5CK-AA1-500

Brand/series
E5CK Series
Contact Form
SPST-NO
Current, Input
4 to 20, 0 to 20 mA mA
Dimensions
58mmW×58mmH×113mmD
Enclosure Rating
IP00, IP20, IP66
Height
1.89 in.
Input Type
Analog
Ip Rating
IP00, IP20, IP66
Length
2.28 in.
Mounting Type
Panel
Number Of Outputs
1
Output Type
Relay
Power Consumption
15 VA
Primary Type
Controller
Standards
UL, CSA, CE
Time, Response
200 ms (Typ.)
Voltage, Input
1 to 5, 0 to 5, 1 to 10
Voltage, Supply
100 to 240 VAC
Width
4.45 in.
Auxiliary Output
Relay — SPST-NO 3 A @ 250 VAC (Standard)
Supply Voltage
100-240 VAC/24 VAC/VDC
Thermocouple Inputs
K, J, T, E, L, U, N, R, S, B, W
Platinum Rtd Input
Pt100 and JPt100
Current Input
4 to 20 mA DC, 0 to 20 mA DC
Voltage Input
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
Control Output
SPST-NO 3 A @ 250 VAC/SSR 1 A @ 75 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
1
Ordering Information
Advanced Process Digital
Controllers with Fuzzy Logic
D
D
D
D
D
D
D
D
D
D
D
D
Note: Order Control Output Boards and Option Boards separately below.
Note: 1. When using the heater burnout alarm function with a standard model, the Linear Output Module cannot be used for the control
Standard model
Position-proportional model (See Note 3)
Standard model
Position-proportional model (See Note 3)
Standard model
Non-standard model with built-in quick auto-tune button
(See Nomenclature section for details)
Field configurable outputs, options.
100 ms sampling (for analog input).
Advanced PID, or fuzzy self-tuning.
Conforms to UL, CSA and CE standards.
Water-resistant front panel meets IP66/NEMA 4X.
Remote set point with optional event input board.
Set point ramp.
Serial communications available.
Front panel programming.
Heat only or heat/cool control.
Auxiliary outputs (SPST) standard; two for E5AK/E5EK,
one for E5CK.
3-year warranty.
E5 K
Digital Process Controller Series
2. E5EK-PRR2/E5AK-PRR2 controllers are supplied with dedicated relay output.
3. Position-proportional models are intended for motorized valves (not 4-20 mA modulating valves). These use two relays (“open”
4. Part numbers ending in --500 include a Finger Safe cover.
Digital Process Controller
outputs (heat). The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at
4 to 20 mA for the current outputs.
and “close”) which will turn a motor clockwise or counter-clockwise, thus opening or closing the valve.
Description
E5 K
1/4 DIN
(96
(96 x 96 mm)
1/8 DIN
(48
(48 x 96 mm)
1/16 DIN
(48
(48 x 48 mm)
/
/
/
DIN size
96
96
48
)
)
)
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
Supply voltage
E5AK-AA2-500
E5AK-PRR2-500
E5EK-AA2-500
E5EK-PRR2-500
E5CK-AA1-500
E5CK-AA1-302
Model

Related parts for E5CK-AA1-500

E5CK-AA1-500 Summary of contents

Page 1

... Part numbers ending in --500 include a Finger Safe cover. 1 Digital Process Controller DIN size Supply voltage 1/4 DIN / 100 to 240 VAC ( mm) ( 100 to 240 VAC 1/8 DIN / 100 to 240 VAC ( mm) ( 100 to 240 VAC 1/16 DIN / 100 to 240 VAC ( 100 to 240 VAC E5 K Model E5AK-AA2-500 E5AK-PRR2-500 E5EK-AA2-500 E5EK-PRR2-500 E5CK-AA1-500 E5CK-AA1-302 ...

Page 2

... A at 250 VAC (resistive load 250 VAC (resistive load) ON/OFF, Advanced PID Control (with auto-tuning) or Self-tuning Digital setting using front panel keys or communications features E5EK mm 9.5 mm E5CK mm 100 Ω to 2.5 kΩ 1 kΩ max. 100 kΩ min. residual voltage: 1.5 V max. leakage current: 0.1 mA max. ...

Page 3

... Memory protection Weight g E5AK E5EK Mounting bracket E5CK Adapter EMC Standards - - Approvals Note: Indication Accuracy -- Of the K1, T, and N thermocouples at a temperature of -100°C or less: ±2°C ±1 digit maximum. Of the U, L1, and L2 thermocouples at any temperature: ±2°C ±1 digit maximum. Of the B thermocouple at a temperature of 400°C or less: unrestricted. ...

Page 4

... Dimensions Unit: mm (inch) J E5AK 96 (3.78 (3.78) Note: 1. Recommended panel thickness mm. J E5EK 48 (1.89) J E5CK Panel Cutouts 65 min. 60 min 13.5 (0.53) 100 (3.94) 2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be closely mounted vertically or horizontally. ...