MSO-0008P-012 NCC, MSO-0008P-012 Datasheet - Page 51

no-image

MSO-0008P-012

Manufacturer Part Number
MSO-0008P-012
Description
Socket, Relay; 8 Pin Octal
Manufacturer
NCC
Type
Octalr
Datasheet

Specifications of MSO-0008P-012

Number Of Contacts
8
Time Range
0.05 Sec. to 999 Min.
Output Rating
10 A @ 240 VAC Max.; 100 mA @ 5 VDC Min.
Operating Temperature
–23°C to +55°C
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
Resistance Sensors
Models NS210 and NS211
FEATURES
Operating Logic: Assuming an empty tank,
upon application of voltage to the system,
the fill output is turned on and the heat-
er output is off. As the liquid fills the tank,
and when it reaches the low probe (above
heater), the heater output is turned on. The
level will rise until it reaches the high probe
causing the fill output to turn off. As liquid
is removed from the tank, 2 to 4 seconds
after it breaks contact with the high probe,
the fill output is turned on and stays on until
the liquid reaches the high probe. This time
delay eliminates fill output chatter if the liq-
uid is splashing.
(common) probe must be installed at a level
where it will always be submerged.
ORDERING INFORMATION
Probe Holder with Ground
Probe, 6” Long, 1/4” Dia., S.S.
Probe, 12” Long, 1/4” Dia., S.S.
Probe, 24” Long, 1/4” Dia., S.S.
Probe Assembly, Plastic Body
Pump Up
Pump Up
Pump Up
Pump Up
If the tank is non-conductive, a third
100% functionally tested
Solid state sensing circuitry
Isolated UL Class ll sensing voltage
1/4” male fast-ons for circuit connection
Conformal coating to protect circuit
from harsh environments
ACCESSORY
LOGIC TYPE
File #E61377
INPUT VOLTAGE
PART NUMBER
LLP-06.00-OSS
LLP-12.00-OSS
LLP-24.00-OSS
LLH-11383-010
LLP-001/2-011
120 VAC
240 VAC
120 VAC
24 VAC
(Pump Up Logic with Heater Burn Out Protection)
SPECIFICATIONS
CONTROL TYPE
On/Off Resistance Sensing:
On low probe: probe resistance below set
point activates heater output
On high probe: probe resistance above set
point activates fill output after a 2 to 4 sec.
delay
Sensing Voltage: 15 VAC, max. RMS
Sensing Current: 2 mA, max. RMS
Sensitivity Adjustment: Factory set at
50 K ohms ±10%
INPUT
Operating Voltage: 24, 120, 240 VAC, ±10%
Power Consumption: 3.0 VA max.
Frequency: 50/60 Hz
OUTPUT
Type: Relay contacts, switch loads to L1
Rating: 5 A resistive at 240 VAC
Life:
Mechanical: 5,000,000 cycles
Electrical: 100,000 min. at full load
PROTECTION
Isolation: 1500 VAC between probe and other
terminals
MECHANICAL
Terminations: 1/4” x .032” male fast-ons
Mounting: 4 - .141” dia. mounting holes
ENVIRONMENTAL
Operating Temperature: 0°C to 55°C
LNC-NS210-024
LNC-NS210-120
LNC-NS210-240
LNC-NS211-120
PART NUMBER
LIQUID LEVEL CONTROL SERIES
Voltage
Input
Voltage
Input
Mounting Holes
(5) .14 Dia
Light
Low
Heat
Fill
NS211
HEAT
FILL
1.25
(3672-2)
Heating
Element
3.50
4.00
(3672-1)
Typical Probe Connection
NS210
4.00
3.50
L
To Probes
and Tank
PROBES
To Level Contro l
L H
H C
C
Mounting Holes
To conductive
tank
High Probe
Low Probe
(4) .14 Dia
2-5
.25

Related parts for MSO-0008P-012