H3DE-S2 AC/DC24-230 Omron Automation, H3DE-S2 AC/DC24-230 Datasheet

no-image

H3DE-S2 AC/DC24-230

Manufacturer Part Number
H3DE-S2 AC/DC24-230
Description
Timer, Standard Type, DPDT, Analog, 0.1 Second to 120 Hours, 24-230 VAC/VDC
Manufacturer
Omron Automation
Datasheet

Specifications of H3DE-S2 AC/DC24-230

Brand/series
H3DE
Contact Form
DPDT
Current, Rating
5 A
Function
Timing
Mounting Type
DIN Rail
Relay Type
Electro Mechanical
Timer Type
Multi-Function
Voltage, Control
230 VAC/VDC
Voltage, Rating
250/30 VAC/VDC
Supply Voltage
24-230 VAC/VDC
Control Output
SPDT Time Limit (M1/S1), DPDT Time Limit SPDT and Instantaneous SPDT (M2/S2)
Lead Free Status / Rohs Status
RoHS Compliant part
Analog Set Multifunction Timers
In Slim 22.5 mm Design
For Track Mounting
H
H
H
H
H
H
Ordering Information
J TIMER
J MODEL NUMBER LEGEND
H3DE-j-j-j
J ACCESSORIES (ORDER SEPARATELY)
Description
Contact output
DPDT (time-limit output SPDT);
and switchable SPDT
(time-limit ←→ instantaneous)
(time-limit ←→ instantaneous)
SPDT (time-limit output SPDT)
Item
Mounting track
End plate
Spacer
Multifunction Timer
Wide AC/DC power supply range
(24 to 230 VAC/DC) minimizes inventory
12 VDC available in H3DE-M model
Programmable contacts (available in
-M2 and -S2 models) can enable and
disable a self-holding relay circuit
Eight operating modes in the H3DE-M
(four in the H3DE-S) offer wide
application flexibility
Time setting range 0.10 sec to 120 hrs
Finger protection terminal block
1
2 3
1. M: Multifunction type
S: Standard type
Supply voltage
12 VDC
24 to 230
VAC/DC
Part number
Multifunctional
H3DE-M2 DC12
H3DE-M2 AC/DC24-230
H3DE-M1 AC/DC24-230
Description
50 cm (l) x 7.3 mm (t)
1 m (l) x 7.3 mm (t)
1 m (l) x 16 mm (t)
2. 1: SPDT
2: DPDT
3. Supply voltage
Standard
H3DE-S2 AC/DC24-230
H3DE-S1 AC/DC24-230
Part number
PFP-50N
PFP-100N
PFP-100N2
PFP-M
PFP-S
H3DE
1

Related parts for H3DE-S2 AC/DC24-230

H3DE-S2 AC/DC24-230 Summary of contents

Page 1

... J ACCESSORIES (ORDER SEPARATELY) Item Mounting track End plate Spacer Part number Multifunctional Standard H3DE-M2 DC12 — H3DE-M2 AC/DC24-230 H3DE-S2 AC/DC24-230 H3DE-M1 AC/DC24-230 H3DE-S1 AC/DC24-230 2. 1: SPDT 3. Supply voltage 2: DPDT Description Part number 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) ...

Page 2

... Timer with a solid-state output such as a sensor. 3. The power consumption is for mode A (ON-delay) after the Timer counts the time-up time and for the AC input at 50 Hz. The power consumption of the H3DE-Mj includes the input circuit with the B1 and A1 terminals short-circuited. 2 ...

Page 3

... IP30 (Terminal block: IP20) Weight 120 g Note: 1. With the H3DE-Mj, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes: Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range Setting error: ±10% +100/- -50 ms max. Signal input time: 100 ms min. ...

Page 4

... Output indicator (orange) (Lit while Timer gives output.) Operating mode selector (select a mode from B2 and G for the H3DE-M1/-M2, from and B2 for the H3DE-S1/S2) Power-on indicator (green) (Lit while the power is on.) Bottom View Output type selector switch for H3DE-M2/-S2 (default setting ...

Page 5

... Time range/ Operating unit selectors mode selector Counting Output circuit circuit Indicator Input circuit circuit Power-ON Output indicator indicator Time range/ Operating unit selectors mode selector Counting Output circuit circuit Indicator circuit Power-ON Output indicator indicator H3DE-S1/-S2 No input is available. 5 ...

Page 6

... The H3DE-M/-S can be set to any one of the operating modes Turn the operating mode selector with a screwdriver until the desired operating mode ( for the H3DE-M and A, B2 for the H3DE-S) appears in the operating mode display window located below the selector. J TIMING CHART Note: 1. The minimum power reset time is 0.1 s and the minimum signal input time is 0. The letter “ ...

Page 7

... Note.) Output relay and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Power indicator Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement ...

Page 8

... Approx. Output relay: NO 1±0.6 s (output indicator) (fixed) 15 and 18 (25 and 28) Power indicator Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement ...

Page 9

... H3DE-S Installation J TERMINAL ARRANGEMENT Note: 1. The contact symbol for the H3DE is indicated with the delayed contact for conventional timers supply voltage does not require the designation of polarity. 3. The relay R2 can be set to either instantaneous or time-limit contact using the switch located on the bottom of the Timer. ...

Page 10

... J INPUT CONNECTIONS The inputs of the H3DE-M1/-M2 are voltage (voltage imposition or open) inputs. No-Contact Input Connection to PNP output sensor. Sensor Timer (+) 1 Start 24 VDC (- -) A 2 Operates with PNP transistor ON Voltage Input Signal Levels 1. Transistor ON No-contact input Residual voltage max.; voltage between terminals B “H-level” voltage (20.4 VDC min.) 2. Transistor OFF Leakage current: 0.01 mA max. ...

Page 11

... When removing the H3DE, pull out portion (C) with a flat-blade screwdriver and remove the Timer from the mounting track. (A) The H3DE can be mounted or removed easily if a distance (1.18 in) or more is kept between the H3DE and the top surface of other equipment located below the H3DE. (B) H3DE 16 35± ...

Page 12

... Timer. Both AC and DC power supplies can be connected to the power input terminals without regarding polarity. With the H3DE only power supply must be connected to the power input terminals as designated according to the polarity of the terminals power supply can be connected if its ripple factor is 20% or less and the mean voltage is within the rated operating voltage range of the Timer ...

Page 13

... J VDE CONFORMANCE The H3DE as a built-in timer conforms to VDE 0435/P2021 provided that the following conditions are satisfied: The output section of the H3DE is provided only with basic isolation. To ensure reinforced isolation required by the VDE standards, provide supplementary basic isolation on the load side connected to the output ...

Page 14

... One East Commerce Drive Schaumburg, IL 60173 1-800-55-OMRON Cat. No. GC TMCN1 3/02 J RELAY LIFE EXPECTANCY Built-in relay for the H3DE: G6RN; 50,000 operations min 250 VAC, resistive load at 360 operations/h.) OMRON ON- -LINE Global - - http://www.omron.com USA - - http://www.omron.com/oei Canada - - http://www.omron.com/oci Specifications subject to change without notice. ...