DescriptionPhase Monitor, Universal Voltage, DIN Rail Mount, 10A, SPDT Relay Output
ManufacturerATC Diversified Electronics
SLU100ASD datasheet
 

Specifications of SLU100ASD

Phase Unbalance2% to 10%, AdjustableFault Delay0.1 to 25 Sec, Adjustable
Restart0.5 to 300 Sec, Adjustable (Auto Restart)Relay Rating10 A @ 240 VAC
Page 1/1

Download datasheet (129Kb)Embed
SLU-100 Series
SLU-100-ASA
SLU-100-ASD
\\\
ORDERING INFORMATION
MODEL NUMBER
SLU-100-ASA
Universal Phase Monitor
SLU-100-ASD
Din Rail Mount Universal Phase Monitor
\\\
TOP LABELS
\\\
DIMENSIONS
(INCHES)
DIN Rail
208
Diversified Electronics
Phase Monitor Relays (3-Phase Monitors) provide cost-effective protection
against premature equipment failure caused by voltage faults on 3-Phase
systems (Wye or Delta). The SLU Series multi-mode phase monitoring
relay, was designed for the convenience of electrician's, maintenance
managers and engineers. A single SLU Phase Monitoring Relay can be eas-
ily adjusted for the voltage, imbalance percentage and time delay require-
ments to protect against unbalanced voltages or single phasing regardless
of any regenerative voltages.
Both Delta and Wye systems may be monitored. In Wye systems,
connections to neutral are NOT required.
NOTE: Not recommended for generator or variable frequency drive applications. Call technical sup-
port for application assistance.
\\\
SPECIFICATIONS
AUTO
RANGING
SCALES
VOLTAGE
BAND
DESCRIPTION
MAXIMUM
VOLTAGE
PHASE
SEQUENCE
POWER
REQUIRED
Plug-In
PHASE
UNBALANCE
PHASE SHIFT 13° Drop-out, 12° Pick-up (Ø-Loss)
FREQUENCY
SHIFT
RESET
RELAY
DIN Rail
OUTPUT
INDICATORS
RESPONSE
TIMES
TEMPERATURE
RATINGS
REPEAT
ACCURACY
TERMINALS
(DIN)
ENCLOSURE
WEIGHT
800.727.5646
atcdiversified.com
Nominal Line-to-
Adjustable
Frequency
Line Voltages
Range
208, 220, 240
200-250
60Hz
380, 415, 440,
360-500
460, 480
208, 220, 240
200-250
50Hz
346, 380, 415
330-430
±10% of Range Setting
Drop-out
(Under/Over)
±7% of Range Setting
Pick-up
(Under/Over)
550 VAC (Line-to-Line)
ABC (Will Not Operate On CBA Sequence)
90VA Max.
2% to 10%, Adjustable Drop-out
Hysteresis
10% of Setting
50/60 Hz
Drop-out
± 4%
Pick up
± 3%
Automatic or Manual Mode
SPDT, 10A @ 240VAC
Resistive, 1/2 HP @240VAC
Flashing
Continuous
Normal
Fault Delay
Relay
(Green LED)
Active
Energized
Fault
Restart Delay
Relay
(Red LED)
Active
De-energized
Power Up
2.5 S Minimum
Fault Delay
0.1 to 25 S, Adjustable
100mS (Phase-Loss, Unbalance
Severe Fault
or Phase Reversal)
0.5 to 300 S, Adjustable
Restart
(Auto Reset)
Operate
32° to 131°F (0° to +55°C)
Storage
-49° to 185°F (-45° to +85°C)
1% @ Fixed Condition
Slotted Screw Terminal Clamps, 12AWG Max.
Style “A”
LEXAN
®
Dust Cover
35mm DIN Rail, 14 Term
DIN
Polycarbonate Housing
0.35 to 0.5 lbs.