SLU600ASTDS ATC Diversified Electronics, SLU600ASTDS Datasheet

no-image

SLU600ASTDS

Manufacturer Part Number
SLU600ASTDS
Description
Phase Monitor, Universal Voltage, Din Rail/Surface Mount, 10 A DPDT Relay Output
Manufacturer
ATC Diversified Electronics
Datasheet

Specifications of SLU600ASTDS

Phase Unbalance
2% to 10%, Adjustable
Fault Delay
0.1 to 25 Sec, Adjustable
Restart
0.5 to 300 Sec, Adjustable (Auto Restart)
Relay Rating
10 A @ 240 VAC
FEATURES: ALL SLU'S
• DIN Rail Mount & Surface Mount
• Adjustable Restart Delay
• Adjustable Fault Delay
• Manual or Automatic Reset
• Adjustable Operating Range SLU-600:
PROTECTS AGAINST
• Rapid Cycling
• Phase Reversal
• Phase Unbalance
• Over/Under Frequency
SPECIFICATIONS
AUTO RANGING
3 Ø VOLTAGE BAND
CONTROL VOLTAGE: 120 VAC ±10%, 50/60Hz
MAXIMUM VOLTAGE: 700 VAC (Line-to-Line)
PHASE SEQUENCE:
POWER REQUIRED:
PHASE UNBALANCE 2% to 10%, Adjustable Drop-out
PHASE SHIFT:
FREQUENCY SHIFT
RESET:
RAPID CYCLING:
SLU
SCALES:
Drop-out:
Pick-up:
Hysteresis:
Drop-out:
Pick up:
200-630 VAC 3-Phase Nominal
Universal Phase Monitor/Relay
SLU-600-ASTDS
SERIES
See Table Previous Page
ABC (Will Not Operate On CBA Sequence)
90 VA Maximum
10% of Setting
13° Drop-out, 12° Pick-up (Ø-Loss)
50/60 Hz
± 4%
± 3%
Automatic or Manual Mode
Clears Rapid Cycle Count
5 Cycle Lockout,
30-Min. Cycle Count Reset
• Phase Loss
• Over/Under Voltage
• Phase Shift
±10% of Range Setting (Under/Over)
±7% of Range Setting (Under/Over)
www.automatictiming.com
LED STATUS CHART
Status
Powering Up/First 3 Sec
Powered Up/Normal Voltages
Relay ON/Under Voltage
Detected/FAULT DELAY active
Relay ON/Over Voltage Detected/
FAULT DELAY active
Relay ON/Unbal or Ø Loss
Detected/FAULT DELAY active
Relay OFF/Under Voltage Failure
Relay OFF/Over Voltage Failure
Relay OFF/Unbal or Ø Loss Failure
Relay OFF/Under Voltage Corrected/
RESTART DELAY active
Relay OFF/Over Voltage Corrected/
RESTART DELAY active
Relay OFF/Unbal or Ø Loss
Corrected/RESTART DELAY active
TOP LABEL
278
RELAY OUTPUT:
INDICATORS
RESPONSE TIMES
TEMPERATURES
REPEAT ACCURACY: 1% @ Fixed Condition
TERMINALS:
ENCLOSURE:
Normal (Green LED):
Under (Red LED):
Over (Red LED)
Unbal / Ø Loss (Red LED) :
Power Up:
Fault Delay:
Severe Fault:
Restart:
Operate:
Storage:
DIMENSIONS
MILLIMETERS
INCHES
Normal
Green
DPDT, 10A @ 240 VAC Resistive
Flashing
Fault Delay Active
Restart Delay Active
Restart Delay Active
Restart Delay Active
2.5 S Minimum
0.1 to 25 S, Adjustable
100mS (Ø-Loss, Unbalance or Ø Reversal)
0.5 to 300 S, Adjustable (Auto Reset)
32°F to +131°F (0°C to +55°C)
-49°F to +185°F (-45°C to +85°C)
Plug and Socket Term Block with Spring
Pressure Wire Retention, 12 AWG Max.
35mm DIN Rail or Surface Mount,
Polycarbonate Housing
LED
Under
= OFF
Red
LED
= ON
Over
Red
LED
Continuous
Relay Energized
Relay De-energized
Relay De-energized
Relay De-energized
Ø Loss Red
Unbal &
= FLASHING
LED