CXONELT01CV4 Omron Automation, CXONELT01CV4 Datasheet - Page 15

no-image

CXONELT01CV4

Manufacturer Part Number
CXONELT01CV4
Description
Support Software Development Tool
Manufacturer
Omron Automation
Type
Configuration Softwarer
Datasheet

Specifications of CXONELT01CV4

Application
Logic Control
Brand/series
CP1
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
CP1L
28
CPU Unit Specifications
■ I/O Bits and I/O Allocations
With CP1H and CP1L CPU Units, the beginning input and output words (CIO 0 and CIO 100) are allocated by the CPU Unit one or two words at
a time. I/O bits are allocated in word units in order of connection to Expansion Units and Expansion I/O Units connected to a CPU Unit.
Note: For details on the number of words allocated to Expansion Units and Expansion I/O Units, refer to Words Allocated to CP1W Expansion Units and Expansion I/O
● Example: I/O Bit Allocations When Expansion Units Are Connected
CPU Unit with 40 I/O Points + Temperature Sensor Unit + Analog Output Unit + Expansion I/O Unit with 40 I/O Points
■ General Specifications
Note: The above values are for a cold start at room temperature for an AC power supply, and for a cold start for a DC power supply.
Inputs
Outputs
Item
Power supply
Operating voltage range
Power consumption
Inrush current (See note.)
External power supply
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient operating tempera-
ture
Ambient humidity
Ambient operating environ-
ment
Ambient storage temperature
Power holding time
CP1H CPU Unit with 40 I/O points
CP1L CPU Unit with 10, 14, or 20 I/O points
CP1L CPU Unit with 30 or 40 I/O points
CP1L CPU Unit with 60 I/O points
Units on page 26.
• A thermistor (with low-temperature current suppression characteristics) is used in the inrush current control circuitry for the AC power supply. The thermistor
• A capacitor charge-type delay circuit is used in the inrush current control circuitry for the DC power supply. The capacitor will not be charged if a hot start is
will not be sufficiently cooled if the ambient temperature is high or if a hot start is performed when the power supply has been OFF for only a short time. In
those cases the inrush current values may be higher (as much as two times higher) than those shown above. Always allow for this when selecting fuses and
breakers for external circuits.
performed when the power supply has been OFF for only a short time, so in those cases the inrush current values may be higher (as much as two times
higher) than those shown above.
CPU Unit with 40 I/O Points
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
CP1H-X@40D
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.07
24 inputs
16 outputs
CPU Unit
Model
Type
100 to 240 VAC 50/60 Hz
85 264 VAC
100 VA max. (CP1H-@@@-A)
50 VA max. (CP1L-M60/-M40/-M30@@-A) (See next page.)
30 VA max. (CP1L-L20/-L14/-L10@@-A)
100 to 120 VAC inputs:
200 to 240 VAC inputs:
300 mA at 24 VDC (CP1H, CP1L-M60/-M40/-M30@@-A)
200 mA at 24 VDC (CP1L-L20/-L14/-L10@@-A)
20 MΩ min. (at 500 VDC) between the external AC terminals
and GR terminals
2,300 VAC at 50/60 Hz for 1 min between the external AC and
GR terminals, leakage current: 5 mA max.
Conforms to IEC 61000-4-4. 2 kV (power supply line)
Conforms to JIS C0040. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
minutes each. Sweep time: 8 minutes × 10 sweeps = total time of 80 minutes)
Conforms to JIS C0041. 147 m/s
0 to 55°C
10% to 90% (with no condensation)
No corrosive gas
−20 to 75°C (Excluding battery.)
10 ms min.
Temperature Sensor Unit
20 A max. (for cold start at room temperature)
8 ms max.
40 A max. (for cold start at room temperature), 8 ms max.
CP1W-TS002
CIO 2 to 5
1st Unit
None
AC power supply models
CIO 0, CIO 1, and CIO 2
Analog Output Unit
CIO 0 and CIO 1
CIO 0 and CIO 1
CP1W-DA041
CP1H-@@@-A
to CIO 105
CP1L-@@@-A
CIO 102
2nd Unit
None
Inputs
CIO 0
2
three times each in X, Y, and Z directions
Expansion I/O Unit with 40 I/O Points
Allocated words
CIO 106.00 to CIO 106.07
CIO 107.00 to CIO 107.07
CIO 6.00 to CIO 6.11
CIO 7.00 to CIO 7.11
16 outputs
CP1W-40ED
CIO 100, CIO 101, and CIO102
24 inputs
3rd Unit
CIO 100 and CIO 101
CIO 100 and CIO 101
Outputs
CIO 100
24 VDC
20.4 to 26.4 VDC
50 W max. (CP1H-@@@-D)
20 W max. (CP1L-M60/-M40/-M30@@-D) (See next page.)
13 W max. (CP1L-L20/-L14/-L10@@-D)
30 A max. (for cold start at room temperature)
20 ms max.
None
No insulation between primary and secondary for DC power
supply
No insulation between primary and secondary for DC power
supply
2 ms min.
DC power supply models
CP1H-@@@-D
CP1L-@@@-D
2
in X, Y, and Z directions for 80

Related parts for CXONELT01CV4