44
Expansion I/O Unit Specifications
■ CP1W-40EDR/40EDT/40EDT1/32ER/32ET/32ET1/20EDR1/20EDT/20EDT1/16ER/16ET/16ET1/8ED/8ER/8ET/8ET1 Expansion I/O Units
Expansion I/O Units can be connected to the CPU Unit to configure the required number of I/O points.
● DC Inputs (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)
● Relay Outputs (CP1W-40EDR/32ER/20EDR1/16ER/8ER)
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON delay
OFF delay
Circuit configuration
Max. switching capacity
Min. switching capacity
Service
life of
relay
ON delay
OFF delay
Circuit configuration
Item
Elec-
trical
Mechanical
Item
Resistive
load
Inductive
load
24 VDC +10%/−15%
4.7 kΩ
5 mA typical
14.4 VDC min.
5.0 VDC max.
0 to 32 ms max. (Default: 8 ms) (See note 1.)
0 to 32 ms max. (Default: 8 ms) (See note 1.)
2 A, 250 VAC (cosφ = 1), 24 VDC 4 A/common
5 VDC, 10 mA
150,000 operations (24 VDC)
100,000 operations (24 VAC cos = 0.4)
20,000,000 operations
15 ms max.
15 ms max.
COM
IN
IN
Internal
circuits
4.7 kΩ
Output LED
Specifications
Specifications
Input LED
OUT
OUT
COM
L
L
Internal
circuits
Maximum
250 VAC: 2 A,
24 VDC: 2 A
Note: 1. Do not apply a voltage exceeding the rated voltage to an input terminal.
Note: Under the worst conditions, the service life of output contacts is as shown on
500
300
200
100
50
30
20
10
5
3
2
0.1
2. Can be set in the PLC Setup to 0, 0.5, 1, 2, 4, 8, 16 or 32 ms. The CP1W-
Switching frequency: 1,800 operations/h
the left. The service life of relays is as shown in the following diagram as a
guideline.
40EDR/EDT/EDT1 are fixed at 16 ms.
0.2 0.3
0.5 0.7 1
120 VAC resistive load
24 VDC τ = 7 mA
120 VAC cos φ = 0.4
240 VAC cos φ = 0.4
24 VDC/240- VAC
resistive load
Contact current (A)
2
3
5
10
Relationship between
Output Load Current and
Ambient Temperature
(CP1W-16ER/32ER)
When using the CP1W-32ER, do not
allow more than 24 outputs to be ON
simultaneously regardless of the
ambient temperature.
100
50
0
Ambient temperature (˚C)
43
55