EVT1-420-24L Eaton / Control Automation, EVT1-420-24L Datasheet

no-image

EVT1-420-24L

Manufacturer Part Number
EVT1-420-24L
Description
AC VOLTAGE TRANSDUCER, 120 MAX INPUT, 4-20MA OUT, LOOP POWERED
Manufacturer
Eaton / Control Automation
Datasheet
MODELS COVERED IN THIS MANUAL
INTRODUCTION
Eaton’s VoltageWatch™ sensors are designed to
monitor AC voltages to allow a monitoring system to
detect conditions where supply voltage is above or
below normal. Detecting such conditions helps
users avoid problems commonly associated with
voltage irregularities, such as motor overheating,
damange to drives due to regeneration, and loss of
phase.
VoltageWatch sensors are available with a 4-20mA “True RMS”
output as standard, making them suitable for use in applications where
the waveform of the monitored voltage is distorted (such as noisy
environments, variable speed applications or SCR controlled loads).
MOUNTING
VoltageWatch sensors feature a 35mm wide DIN rail compatible
enclosure and are typically located in the same environment as motors,
contactors, heaters, pull-boxes, and other electrical devices.
Mounting on DIN Rail: Orient the sensor so that line voltage terminals
L1 and L2 are upright (on top) of the unit and snap securely onto DIN
rail. To remove, insert small screwdriver into depression on top of unit
and pry orange mounting tab up until unit dislodges from DIN rail.
Screw Mounting: Insert small screwdriver into depression on top of
unit and pry orange mounting tab up to reveal mounting hole. Continue
to pry tab up until it extends and snaps into place, about 0.25 inches.
Insert screws and mount to back plane or other suitably fl at surface.
Effective: 15 October 2009
Catalog Number
EVT1-420-24L
EVT3-420-24L
EVT4-420-24L
IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:
• TO AVOID ANY POTENTIAL FOR SHOCK OR SAFETY HAZARD,
• DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS.
• DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G.
• ENSURE THE PRODUCT IS PROPERLY WIRED TO THE CORRECT
ENSURE LINE VOLTAGE IS DISCONNECTED AT SOURCE BEFORE
WIRING TO UNIT.
IT WAS NOT DESIGNED, TESTED OR RECOMMENDED FOR THIS
USE.
EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED OR
RECOMMENDED FOR THIS USE.
POWER SUPPLY FOR THE APPLICATION. REFER TO THE
SPECIFICATIONS AND WIRING DIAGRAMS IN THIS MANUAL.
Description
AC Voltage Sensor, 120V Max Input, 4-20mA Output, Loop Powered
AC Voltage Sensor, 240V Max Input, 4-20mA Output, Loop Powered
AC Voltage Sensor, 480V Max Input, 4-20mA Output, Loop Powered
WARNING
VoltageWatch™ Voltage Sensors
Installation Instructions
LINE VOLTAGE CONNECTION WARNING
CAUTION: TO AVOID ANY POTENTIAL FOR SHOCK OR SAFETY
HAZARD, ENSURE LINE VOLTAGE IS DISCONNECTED AT SOURCE
BEFORE WIRING TO UNIT.
INSTALLATION
The below steps can be followed to quickly install a VoltageWatch
sensor:
OUTPUT WIRING
Connect control or monitoring wires to the sensor using up to 14 AWG
copper wires. Tighten terminals to 7 inch-pounds torque. Be sure the
output load or loop power requirements are met (see diagram below).
OUTPUT GRAPH
(120, 240, 480V)
1. For your safety, ensure line voltage is disconnected at source
2. Ensure correct sensor model was chosen for input voltage of
3. Mount the sensor to a DIN rail or fl at surface using integrated
4. Connect input voltage L1 and L2 and output wiring (24V + and -)
Line Voltage
-
25
20
15
10
5
0
Output
24V DC Power
before wiring this sensor
application
mounting clip on back side of sensor (see “Mounting” section for
more information)
using up to 14 AWG copper wires. Refer to “Output Wiring” section
for loop voltage and impedance recommendations.
0
(-) (+)
Transducer Output vs. Nominal Input Voltage
+
Page 1
Input Voltage (% FS)
50
(+)
(-)
Loop Voltage Requirements:
L
Where:
L
L
Note:
1M
Add 1.3% error for 100K .
Load
V
V
R
Controller,
Meter...
= 12 + (L
= Minimum Loop Voltage
= Loop Resistance
recommended for output load.
R
x .02)
100
P52215 Rev 02
292181021

Related parts for EVT1-420-24L

EVT1-420-24L Summary of contents

Page 1

... POWER SUPPLY FOR THE APPLICATION. REFER TO THE SPECIFICATIONS AND WIRING DIAGRAMS IN THIS MANUAL. MODELS COVERED IN THIS MANUAL Catalog Number Description EVT1-420-24L AC Voltage Sensor, 120V Max Input, 4-20mA Output, Loop Powered EVT3-420-24L AC Voltage Sensor, 240V Max Input, 4-20mA Output, Loop Powered EVT4-420-24L ...

Page 2

P52215 Rev 02 292181021 TROUBLESHOOTING Problem Solution Sensor has no output Power supply is not properly sized. Check power supply voltage and current rating. Polarity is not properly matched. Check and correct wiring polarity. Output signal is Sensor model may ...