3400-IG2-P10-10A E-T-A Circuit Protection and Control, 3400-IG2-P10-10A Datasheet

no-image

3400-IG2-P10-10A

Manufacturer Part Number
3400-IG2-P10-10A
Description
Circuit Breaker; Therm/Mag; Press-to-Reset; Cur-Rtg 10A; Panel; 1 Pole; Blade Snap
Manufacturer
E-T-A Circuit Protection and Control
Type
Thermal/Magneticr
Datasheet

Specifications of 3400-IG2-P10-10A

Actuator Type
Press-to-Reset
Brand/series
3400 Series
Current, Rating
10 A
Dimensions
1.65"Lx0.551"Wx1.98"H
Mounting Hole Size
0.453x0.48 "
Mounting Type
Panel
Number Of Poles
1
Standards
UL Listed, CSA Certified, VDE Approved, Demko Approved
Termination
Blade
Voltage, Rating
240/65 VAC/VDC
Lead Free Status / Rohs Status
RoHS Compliant part
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Control systems, instrumentation, medical equipment, machine tools,
robotics.
Type No.
3300
3400
3400 - iG2 - P10 - .. - .. - Si - .. - 10 A
3400 - ... - P10 - .. - H - Si - .. - 10 A
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Current
ratings (A) 3300
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
fast acting
standard delay
Mounting
iG2
...
moulded threadneck M12x1 (bulk-shipped), not with -H;
leave blank for metal threadneck, required for -H
Terminal design
P10
K20
Internal resistance (Ω)
447
131
41
19.6
10.4
7.2
4.8
2.5
1.93
0.81
0.44
0.27
blade terminals 6.3-0.8 (QC .250)
screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
A3
Thermal-Magnetic Circuit Breakers 3300/3400
same as main terminals, up to I
Manual release (optional)
H
3400
211
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si
with silver-plated solder terminals
(N/O and N/C)
Push button marking (optional)
1
without
Current ratings
0.05...16 A
Current
ratings (A) 3300
3
4
5
6
7
8
10
12
13
14
15
16
ordering example, without manual
release and with moulded
threadneck
ordering example, with manual
release and metal threadneck
Internal resistance (Ω)
0.18
0.109
0.066
0.046
0.032
0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
N
=7 A max. load 5 A
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
3400
For further details please see chapter: Technical Information
Voltage rating
Current ratings
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Dielectric strength
(IEC 60664 and 60664A)
Insulation resistance
Interrupting capacity I
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Authority
VDE (EN 60934)
CSA, UL
UL: only type 3400
Technical data
Approvals
with -H:
without -H: 0.05...8 A 5,000 operations at 2 x I
operating area
operating area
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7
> 8 A
cn
fast acting
3300
Voltage ratings
AC 240 V; DC 65 V
AC 250 V; DC 80 V
DC 65 V
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
0.05...16 A
1 A, AC 240 V / DC 65 V
5,000 operations at 1 x I
5,000 operations at 2 x I
1,500 operations at 2 x I
-30...+60 °C (-22...+140 °F)
rated impulse
2.5 kV
reinforced insulation in operating area
test voltage
AC 3,000 V double insulation
AC 840 V
> 100 MΩ (DC 500 V)
0.05...0.8 A
1...2 A
2.5...16 A
I
0.05...16 A
0.05...16 A
operating area IP40
terminal area IP00
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms) to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
3300: approx. 55 g
3400: approx. 50 g
withstand voltage
N
3400
standard delay
self-limiting
200 A
400 A
U
AC 250 V
DC 80 V
N
Current ratings
0.05...16 A
0.05...16 A
0.05...25 A
pollution
degree
2
N
N
N
N
, inductive
, resistive
, inductive
, inductive
1,000 A
1,000 A
2 - 47
2

Related parts for 3400-IG2-P10-10A

3400-IG2-P10-10A Summary of contents

Page 1

... N/C) Push button marking (optional) 1 without Current ratings 0.05...16 A 3400 - iG2 - P10 - .. - .. - ordering example, without manual release and with moulded threadneck 3400 - ... - P10 - .. - ordering example, with manual release and metal threadneck The exact part number required can be built up from the table of choices shown above ...

Page 2

... Thermal-Magnetic Circuit Breakers 3300/3400 Dimensions -iG2-P10 ø6.4 .252 M12x1 tightening torque max. 1 blade terminals DIN 46244-A6.3-0.8 (QC .250) 42 1.65 29 1.14 5 current rating ø6.4 .252 M12x1 mounting holes +0.2 ø3 +.008 .118 Installation drawing operating area (reinforced insulation .118 .039 mounting area Internal connection diagrams Terminal design 14 ...