5b45-05 Analog Devices, Inc., 5b45-05 Datasheet

no-image

5b45-05

Manufacturer Part Number
5b45-05
Description
Isolated, Frequency Input
Manufacturer
Analog Devices, Inc.
Datasheet
FEATURES
Isolated Frequency Input.
Amplifies, Protects, Filters, and Isolates Analog Input.
Generates an output of 0 to +5V proportional to input
frequency.
Model 5B45 accepts full-scale inputs from 500 Hz to 20 kHz.
Model 5B46 accepts full-scale input from20 Khz to 275 kHz.
Module circuitry can withstand 240v rms at the input screw-
terminals.
All 5B45 & 5B46 series modules are mix-and-match and Hot
Swappable.
APPLICATIONS
Industrial signal conditioning
Industrial signal isolation
Industrial signal filtering
PRODUCT OVERVIEW
The 5B Series represents an innovative generation of low cost,
high performance plug-in signal conditioners. Designed for
industrial applications, these modules incorporate highly
reliable transformer-based isolation and automated surface-
mount manufacturing technology. They are compact,
economical components whose performance exceeds that
available from more expensive devices. Combining 1500 V rms
continuous isolation, +0.05% calibrated accuracy, small size and
low cost, the 5B Series is an attractive alternative to expensive
signal conditioners and in-house designs
All modules are potted and identical in pin-out and size (2.27” x
2.32” x 0.595”). They can be mixed and matched, permitting
users to address their exact needs, and may be “hot swapped
without disturbing field wiring or power. The isolated input
modules provide 0 to +5V or +5V outputs and accept J, K, T, E,
R, S, N, or B type thermocouples.
These modules feature complete signal conditioning functions
including 240 V rms input protection, filtering, chopper
stabilized low drift +1 uV/oC amplification, 1500 V rms
isolation, and sensor excitation when required.
All modules feature excellent common mode rejection and
meet industrial transient surge withstand specifications.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective companies.
There are also a number of backplanes and mounting sockets
which provide a complete signal conditioning solution for end
users. Each backplane incorporates screw terminals for field
wiring inputs and outputs and cold junction sensors for
thermocouple applications.
These signal conditioners are designed to provide an easy and
convenient solution to signal conditioning problems of both
designers and end users in measurement and control
applications. Typical uses include microcomputer-based
measurement systems, standard data acquisition systems,
programmable controllers, analog recorders and dedicated
control systems. The 5 B series modules are ideally suited to
applications where monitoring and control of temperature,
pressure, flow, rotation and other analog signals are required.
The 5B Series modules and backplanes are approved by Factory
Mutual (FM) and the 5B Series modules are approved by the
Canadian Standards Association (CSA) for use in Class 1,
Division 2, Groups A, B, C, and D locations. These approvals
certify that the 5B Series is suitable for use in locations where a
hazardous concentration of flammable gas may exist only under
fault conditions of operation. Equipment of this category is
called “nonincendive” and they need no special enclosures or
other physical safeguards.
The 5B series modules and backplanes have been tested and
passed the stringent heavy industrial requirements of the
European Union’s electromagnetic compatibility (ENC)
directive – EN50082-1 and EN50081-2. When used according
to installation directions (refer to 5B series User Manual), any
errors caused by EMI/RFI interference will be less than 0.1% of
the full scale 5B measurement range for field strengths up to 10
V/M and frequencies up to 1 GHz.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
Fax: 781.326.8703
Isolated, Frequency Input
Figure 1. 5B45 & 5B46 Functional Block Diagram
FUNCTIONAL BLOCK DIAGRAM
© 2004 Analog Devices, Inc. All rights reserved.
5B45 / 5B46
www.analog.com

Related parts for 5b45-05

5b45-05 Summary of contents

Page 1

... Amplifies, Protects, Filters, and Isolates Analog Input. Generates an output +5V proportional to input frequency. Model 5B45 accepts full-scale inputs from 500 kHz. Model 5B46 accepts full-scale input from20 Khz to 275 kHz. Module circuitry can withstand 240v rms at the input screw- terminals. All 5B45 & ...

Page 2

... All models withstand 240 V rms at their input terminals without damage, thereby shielding computer- side circuitry from field-side over-voltage conditions. In addition, all 5B45 and 5B46 models are mix-and match and hot- swappable, so can be inserted or removed from any socket in the same backplane without disrupting system power. ...

Page 3

... Models Available Model Input Range 5B45- 500 Hz 5B45- kHz 5B45- 2.5 kHz 5B45- kHz 5B45- kHz 5B45-Custom * Model Input Range 5B46- kHz 5B46- kHz 5B46- 100 kHz ...

Page 4

... Mechanical Dimensions Rated Performance Operating Performance Storage Relative Humidity RFI Susceptibility * Specifications same as model 5B45. 1 Jumper selectable. Refer to Field Connection diagram. 2 Includes the combined effects of repeatability, hysteresis, and nonlinearity. Loads heavier than The Output Common must be kept within ± Power Common. ...

Page 5

... PIN CONFIGURATIONS AND FUNCTIONAL DESCRIPTIONS Figure 3 5B45 & 5B46 Input Field Connections Table 1. Pin Function Descriptions— Pin No. Description 1 HYSTERESIS 2 -1. RETURN ESD CAUTION ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the human body and test equipment and can discharge without detection. Although this product features proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges ...

Page 6

... OUTLINE DIMENSIONS Figure 5. Outline Dimensions Rev Page 5B45 / 5B46 ...

Page 7

... NOTES Rev Page 5B45 / 5B46 ...

Page 8

... NOTES © 2004 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective companies. D00259-0-9/04(0) Rev Page 5B45 / 5B46 ...

Related keywords