e5cn-hc2md-w-500 Omron Corporation, e5cn-hc2md-w-500 Datasheet

no-image

e5cn-hc2md-w-500

Manufacturer Part Number
e5cn-hc2md-w-500
Description
Advanced Digital Temperature Controller
Manufacturer
Omron Corporation
Datasheet
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive
Maintenance Function.
Main I/O Functions
• High-resolution display with 5 digits/0.01°C display in a compact
• High-speed sampling cycle of 60 ms.
• High Accuracy
• Universal inputs on all models (thermocouple, PT, or analog input)
• A PV/SV-status display function can be set to automatically alternate
• Flexible contact outputs with logic operations (AND, OR, and
• Preventive maintenance for relays in the Temperature Controller
Advanced Digital Temperature Controller
E5CN-H
Controller (48 x 48 mm).
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
to handle various sensors with one Controller.
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
delays) set from the Support Software (CX-Thermo Ver. 4.0)
using a Control Output ON/OFF Counter.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
Indication Accuracy
• Thermocouple/Pt input: ±0.1% of PV
• Analog input: ±0.1% FS
Universal Sensor Inputs
• Universal thermocouple/Pt/analog
Sampling Period
• 60 ms
(current/voltage) inputs.
Event Inputs
• None
• Two
(48 x 48 mm)
E5CN-H
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 2
• None
• Voltage output
(for driving SSR)
2-level Display: PV and SV
Auxiliary Outputs
• Two
Refer to Operation for E5
operating procedures.
Refer to Safety Precautions for E5
5-digit Display with high resolution of 0.01°C
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Logic operations
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485 or
RS-232C communications
@
48 × 48 mm
E5CN-H
N/ E5
CSM_E5CN-H_DS_E_3_1
@
N-H for
@
N/E5
@
N-H.
1

Related parts for e5cn-hc2md-w-500

e5cn-hc2md-w-500 Summary of contents

Page 1

... This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159) ...

Page 2

... Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). 1 control output Fully universal input 2 control outputs Option Units E53-@@@@ Applicable Controller CN: E5CN-H or E5CN 2. Function 1 Blank: None Q: Control output 2 (voltage output for driving SSR) P: Power supply for sensor C: Current output 3. Function 2 Blank: None ...

Page 3

... E5CN-H Control output 1 Model E5CN-HR2M-500 E5CN-HQ2M-500 E5CN-HC2M-500 E5CN-HV2M-500 E5CN-HR2MD-500 E5CN-HQ2MD-500 E5CN-HC2MD-500 E5CN-HV2MD-500 E5CN-HR2M-W-500 E5CN-HQ2M-W-500 E5CN-HC2M-W-500 E5CN-HR2MD-W-500 E5CN-HQ2MD-W-500 E5CN-HC2MD-W-500 Model E53-CNHH03N2 E53-CNHBN2 E53-CNQ03N2 E53-CNH03N2 E53-CN03N2 E53-CNBN2 E53-CNQHN2 E53-CNQHHN2 E53-CNQBN2 Transfer Output E53-CNQFN2 Transfer Output E53-CNBFN2 E53-CNQ01N2 ...

Page 4

... VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) Power consumption 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) Any of the following can be selected (i.e., fully universal input). Thermocouple Sensor input ...

Page 5

... JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) E5CN-H Analog input 2300.0 1800 ...

Page 6

... Always OFF when the upper-limit and lower-limit hysteresis X ON overlaps. OFF OFF OFF 0 E5CN-H Case 2 Case 3 (Always ON) H < < < > > < 0 H ≥ L H > L ...

Page 7

... Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H. Setup Tool port An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. *4 Approved UL 61010-1, CSA C22.2 No. 1010-1 ...

Page 8

... ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 E5CN-H 250 VAC, 30 VDC 3 (resistive load) cosφ Switching current (A) E5CN ...

Page 9

... B (+) 11 RS-485 12 A (−) DO NOT 13 USE CT2 14 CT1 15 E5CN-H Auxiliary outputs Auxiliary outputs (relay outputs) (relay outputs) 250 VAC (resistive load) Auxiliary output 2 A heater burnout alarm, SSR failure, heater overcurrent alarm, Auxiliary output 1 or input alarm is sent to the ? output to which the alarm 1 function is assigned ...

Page 10

... Mounting Adapter Terminal Cover (Accessory) (E53-COV17) (Accessory) Note: The terminal block cannot be removed. (2,100) LED indicator 250 (SD) E5CN-H No. 1 display No. 2 display Up Key (Unit: mm) Panel Cutout Group Mounted +1.0 (48 × number of units − 2.5) Group mounting does not allow waterproofing. • Recommended panel thickness ...

Page 11

... Two, 3.5 dia. 2.36 dia. 12 dia. 9 Two, M3 (depth: 4) Armature Lead E5CN-H E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω 100 ∞ 10 Distortion 1 kΩ factor 10% ...

Page 12

... Adapter Y92F-45 Note: 1. Use this Adapter when the panel has already been prepared for the E5B@. 2. The Adapter is available only in black. Mounted to E5CN-H 4.7 76 69.6 to 77.6 72 × 72 Panel ( mm) 72 × × 48 2.2 4.7 77.3 (to back of E5CN-H) E5CN-H Fixture (Accessory) 67 × ...

Page 13

... OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ Read and Understand This Catalog Warranty and Limitations of Liability Application Considerations Disclaimers In the interest of product improvement, specifications are subject to change without notice. (c)Copyright OMRON Corporation 2009 All Right Reserved. 2009.4 ...

Related keywords