2811271 Phoenix Contact, 2811271 Datasheet
2811271
Specifications of 2811271
Related parts for 2811271
2811271 Summary of contents
Page 1
... Depending on the ambient temperature and load, the housing can become very hot. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/download. This data sheet is valid for all products listed under "Ordering data" on page 3. © PHOENIX CONTACT - 2009-09-01 Features – Space-saving ...
Page 2
... Rechargeable battery module.................................................................................................... 9 Method of operation................................................................................................................... 9.1 Output voltage .............................................................................................................................................. 13 9.2 Remote shutdown ........................................................................................................................................ 13 9.3 Buffer time setting ........................................................................................................................................ 13 9.4 PC mode ...................................................................................................................................................... 13 9.5 PC idle time .................................................................................................................................................. 14 9.6 Battery management .................................................................................................................................... 15 10 Interfaces................................................................................................................................... 10.1 Config.-Port .................................................................................................................................................. 15 10.2 IFS-USB-PROG-ADAPTER ......................................................................................................................... 15 10.3 IFS-CONFSTICK.......................................................................................................................................... 15 11 UPS-CONF configuration and management software ............................................................... 104103_en_00 TRIO-UPS/1AC/24DC PHOENIX CONTACT ...
Page 3
... Type Order No. MINI-BAT/24DC/1.3AH 2866417 QUINT-BAT/24DC/3.4AH 2866349 QUINT-BAT/24DC/7.2AH 2866352 QUINT-BAT/24DC/12AH 2866365 UPS-CONF 2320403 IFS-USB-PROG-ADAPTER 2811271 IFS-CONFSTICK 2986122 100 ... 240 ... 264 V AC (< derating: 2.5%/V) 100 ... 350 V DC (UL508: 100 ... 250 V) 45 ... 65 Hz 0.95 A/1.1 A 1.7 A/1.8 A typical < < 1.3 A²s 150 ms 200 ms Varistor T 6 ...
Page 4
... Can be adjusted via UPS-CONF software 104103_en_00 22.5 ... 29 2.5%/ approximately Yes, unlimited < 1% (static load change 10 ... 90%) 88% 86 27.9 ... 19 0 2.5%/ approximately Yes, 3300 µF > 10; 15; 20; PC mode Yes Yes I/U 1.0 A/0.2 A/1 mV/K / 200 mV h/4 h/200 h 19 (preset/minimum/maximum) 20 TRIO-UPS/1AC/24DC/5 4 PHOENIX CONTACT ...
Page 5
... Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat -25°C ... +70°C -40°C ... +80°C 95% 2 3K3 < 15 Hz, amplitude ±2.5 mm according to IEC 60068-2 ... 150 Hz, 2.3g, 90 min. 30g in each direction 500 60715 IP20 I > 500,000 h Aluminum (AlMg3)/zinc-plated sheet steel 130 mm x 118 mm 1.1 kg TRIO-UPS/1AC/24DC/5 5 PHOENIX CONTACT ...
Page 6
... Cable to cable) Output 2 kV (Level 3 - asymmetrical (Level 3 - symmetrical) Signal 2 kV (Level 3 - asymmetrical) Remark Criterion B Input/output/signal Level 3 Frequency range 10 kHz ... 80 MHz Voltage 10 kV Remark Criterion A Radio interference voltage according EN 55011 (EN 55022) Class B, industrial and residential to EN 55011 applications TRIO-UPS/1AC/24DC PHOENIX CONTACT 6 ...
Page 7
... Connection notes NOTE: Electrostatic discharge The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. 104103_en_00 TRIO-UPS/1AC/24DC/5 7 PHOENIX CONTACT ...
Page 8
... The following cable cross-sections can be connected: Terminal block No TRIO-UPS/1AC/24DC/5 Connection terminal blocks Rigid Stranded AWG [mm²] [mm²] 0.2 - 2.5 0 0.5 - 0.6 3.5 - 4.5 In order to comply with UL approval, use copper cables that are designed for operating temperatures >75°C. PHOENIX CONTACT Tightening torque [Nm] [lb in] 8 ...
Page 9
... networks according to VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC. TN Figure 3 TRIO-UPS/1AC/24DC/5 For operation using two phase conductors of a three-phase system, an all-pole disconnecting device must be provided. TN Single-phase network systems PHOENIX CONTACT L PEN + - ...
Page 10
... The UPS has been overloaded in 9 mains mode, the battery is OK and charged The UPS has been overloaded in 10 mains mode, the battery is faulty Key LED OFF LED ON LED flashing TRIO-UPS/1AC/24DC/5 BAT is < 20.4 V) BAT = 19.2 V) and BAT 10 PHOENIX CONTACT ...
Page 11
... DIN rail at a 90° angle. Mount the DIN rail adapter (UTA 107) as shown in the figure. The screws that were previously used to secure the UTA must be used: Torx T10 (0.8 Nm ... 0.9 Nm tightening torque). Figure 8 Modification for flat mounting position B TRIO-UPS/1AC/24DC/5 11 PHOENIX CONTACT ...
Page 12
... They have a service life of six to nine years at an ambient temperature of 20°C. In order to ensure immediate availability, all batteries are supplied fully charged. Startup should be carried out at the latest after nine months at 20°C ... 30°C, or after six months at 30°C ... 40°C. PHOENIX CONTACT 12 ...
Page 13
... In "PC mode", the UPS function follows a chronological sequence that can be parameterized via the software and individually optimized for the relevant IPC solution. Requirements: IFS-USB-PROG-ADAPTER data cable (Order No. 2811271) and UPS-CONF software (Order No. 2320403). 104103_en_00 To set the parameters, an Interface interface (IFS) is used for data exchange between the TRIO-UPS and a suitable user interface on the IPC ...
Page 14
... Active switching output (can be parameterized LED green ON POWER IN OK OFF 9 9 LED yellow ON Bat. mode OFF PC response ON OFF Figure 10 Time diagrams 104103_en_00 Delay time Power comes back on during set time PC shutdown PC shutdown Delay time TRIO-UPS/1AC/24DC/5 PC shutdown PC idle time PHOENIX CONTACT 14 ...
Page 15
... The TRIO-UPS is connected to the USB connection on the service PC via the "Config.-Port" using the IFS-USB-PROG- ADAPTER data cable. 10.2 IFS-USB-PROG-ADAPTER The programming adapter (Order No. 2811271) represents the interface between the service PC and the TRIO-UPS and is required in order to parameterize the TRIO-UPS. Figure 11 Programming adapter 104103_en_00 10 ...
Page 16
... IPC and TRIO-UPS is interrupted, the UPS-CONF dialog box is automatically displayed on screen. The status is queried cyclically. PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: + 104103_en_00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com ...