SMART5000RT3U Tripp Lite, SMART5000RT3U Datasheet - Page 3

UPS 5KVA 4000W 14OUT W/BATTERY

SMART5000RT3U

Manufacturer Part Number
SMART5000RT3U
Description
UPS 5KVA 4000W 14OUT W/BATTERY
Manufacturer
Tripp Lite
Series
Smart Pro®r
Type
Power Supply Regulatorr
Datasheet

Specifications of SMART5000RT3U

Rohs Status
Not applicable
Power - Rated
5kVA / 4000W
Ac Outlets
14 (UPS)
Features
DB9 and USB Communications, Rack Mount
Backup Time - Max Load
16 minutes
Voltage - Output Per Connector
208, 120V
Voltage - Input
208V / 30A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA L6-30P
Connector - Ac Output
10 NEMA 5-15R, 2 NEMA 5-20R, 1 NEMA L6-30R, 1 NEMA L14-30R
Size
22.50" L x 17.50" W x 5.25" H (571.5mm x 444.5mm x 133.4mm)
Weight
135 lbs (61.2kg)
Ac Output Connector
10 NEMA 5-15R, 2 NEMA 5-20R, 1 NEMA L6-30R, 1 NEMA L14-30R
Media Lines Protected
-
Other names
SMART5000RT3U
TL317
Output AC waveform
(battery mode)
INPUT
Nominal Input
Voltage(s) Supported
UPS input connection
type
Input circuit breaker
UPS Input cord length
(ft.)
UPS Input cord length
(m)
Recommended
Electrical Service
Input cord length (ft.)
Input cord length (m)
BATTERY
Full load runtime
(minutes)
Half load runtime
(minutes)
Expandable battery
runtime
External battery pack
compatibility
DC system voltage
(VDC)
Battery recharge rate
(included batteries)
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage correction
Undervoltage
correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
Pure Sine wave
208V AC
L6-30P
30A double-pole
10
3
30A 208V
10
3
16 min. (4000w)
38 min. (2000w)
Extended runtime supported via optional external battery packs
BP48V60RT3U (multi-pack compatible)
48
Less than 4 hours from 10% to 90%
Hot-swappable, user replaceable batteries
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 282
Input voltages between 240V and 282 are reduced by 12%
Input voltages between 180V and 199 are boosted by 12%
Input voltages between 151V and 179 are boosted by 24%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation