BXA40-48S05-S Emerson Network Power, BXA40-48S05-S Datasheet

no-image

BXA40-48S05-S

Manufacturer Part Number
BXA40-48S05-S
Description
CONV DC/DC SNGL 5VOUT 40W REMOTE
Manufacturer
Emerson Network Power
Series
BXA40r
Type
Isolatedr
Datasheet

Specifications of BXA40-48S05-S

Rohs Status
RoHS non-compliant
Output
5V
Number Of Outputs
1
Power (watts)
40W
Mounting Type
Through Hole
Voltage - Input
36 ~ 75V
Package / Case
9-DIP Module
1st Output
5 VDC @ 8A
Size / Dimension
2.20" L x 2.20" W x 0.50" H (55.9mm x 55.9mm x 12.7mm)
Power (watts) - Rated
40W
Operating Temperature
-40°C ~ 105°C
Efficiency
82%
Approvals
CSA, EN, UL, VDE
3rd Output
-
2nd Output
-
4th Output
-
BXA40 Series
The BXA40 Series providing up to 40 Watts, has been conceived as an applications specific
range of DC/DC converters, specifically addressing telecommunications, industrial electronics,
test equipment, mobile telecommunications and distributed power applications. The series offers
two wide input voltage ranges, 18-36VDC and 36-75VDC, and is available with single outputs
from 2.9V to 12V. The BXA40 series is designed to meet ETSI telecoms interface standards
ETS300-132-2. Together with internal filtering, safety approval to IEC950 and basic insulation, the
48VDC models are ideal for telecommunications applications. The 24V models are particularly
suited to industrial and test equipment applications, featuring EN61000-4-2, -3, -4, -5 and -6
immunity compliance. Other features include low output ripple, overvoltage protection, indefinite
short circuit protection, remote enable and remote sense.
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
DC/DC CONVERTERS
OUTPUT SPECIFICATIONS
Voltage adjustability
Line regulation
Load regulation
Ripple and noise
(20MHz bandwidth)
Temperature coefficient
Overvoltage protection
Short circuit protection
Transient response
Voltage accuracy
Remote sense
(See Note 8)
INPUT SPECIFICATIONS
Input voltage range
Reverse voltage
protection
Max. input rise and
fall time
Start-up time
Remote ON/OFF
Logic compatibility
ON
OFF
Pin-compatible with NFC40 Series
Meets telecom power supply interface standard
ETS300-132-2
EN60950, CSA C22.2 No. 950 and UL1950 safety approvals
EN61000-4-2, -3, -4, -5, -6 immunity compliant
Fixed frequency operation at 350kHz typ.
MTBF in excess of 500,000 hours
Basic insulation system with 1500V isolation
Remote sense on low voltage logic outputs
Output voltage trim
Low line to high line
Full load to no load
2.9V and 3.3V
5V
12V
All models
(See Note 9)
(See Note 10)
25% to 100% load
(See Note 11)
24Vin nominal
48Vin nominal
48V
S i n g l e o u t p u t
40W Wide Input DC/DC Converters
300mV on 2.9V and 3.3V models
Compensated line drop up to
up to 0.5V on 5V models
±1.0% 5V, ±2.0% 12V
Compensated line drops
100mV pk-pk
18 to 36VDC
36 to 75VDC
(See Note 5)
ETS300-132
Open-circuit
30mV pk-pk
50mV pk-pk
Continuous
±0.02%/°C
135% Vout
CMOS/TTL
20mV rms
30ms typ.
<1VDC
±0.3%
±1.0%
5V/ms
±10%
4.0%
EMC CHARACTERISTICS
Conducted emissions
Radiated emissions
ESD air
ESD contact
Surge
Fast transients
Radiated immunity
Conducted immunity
GENERAL SPECIFICATIONS
Efficiency
Isolation voltage
Switching frequency
Approvals and
standards (pending)
Case material
Material flammability
Weight
MTBF
Size
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
Thermal impedance
(See Note 6)
EN55022, FCC part 15,
(See Notes 4 and 13)
EN55022, FCC part 15
EN61000-4-2, level 3
EN61000-4-2, level 4
EN61000-4-5, level 3
EN61000-4-4, level 3
EN61000-4-3, level 3
EN61000-4-6, level 3
Input/output
Input/case
Fixed
MIL-HDBK-217F
Baseplate operating
temperature
Non-operating
No air flow, no heatsink
No air flow, with heatsink
File Name: BXA40S.PDF Rev: 02 Oct 2002
SPECIFICATIONS
55.9 x 55.9 x 12.7 mm
2.2 x 2.2 x 0.5 inches
2 YEAR WARRANTY
Aluminum substrate
CSA C22.2 No. 950
EN60950, UL1950
-40°C to +105°C
-55°C to +105°C
with plastic case
500,000 hours
Perf. criteria 1
Perf. criteria 1
Perf. criteria 1
Perf. criteria 1
Perf. criteria 1
Perf. criteria 1
350kHz typ.
85g (3.0oz)
See table
1500VDC
1500VDC
UL94V-0
8.5°C/W
7.2°C/W
Level B
Level A
1

Related parts for BXA40-48S05-S

BXA40-48S05-S Summary of contents

Page 1

... The series offers two wide input voltage ranges, 18-36VDC and 36-75VDC, and is available with single outputs from 2.9V to 12V. The BXA40 series is designed to meet ETSI telecoms interface standards ETS300-132-2. Together with internal filtering, safety approval to IEC950 and basic insulation, the 48VDC models are ideal for telecommunications applications ...

Page 2

... BXA40-24S05 and BXA40-48S05 come with remote sense as an option. Remote sense design is designated by the suffix ‘-S’ e.g. BXA40-48S05- SM (for units with metric inserts), BXA40-48S05-S (for units with imperial inserts). For models without remote sense option, pin 5 and pin 6 are absent. ...

Page 3

... BOTTOM VIEW ALL DIMENSIONS IN INCHES (mm) TOLERANCE : 0.004 (0.1) (Unless otherwise specified) Design Note 1.90 (48.26) 1.80 2.20 0.02 (45.72) (55.90 0.50) 4 0.2 (5.08) 0.05 0.15 (1.27) (3.82) www.artesyn.com File Name: BXA40S.PDF Rev: 02 Oct 2002 3 ...

Related keywords