Specifications of GPC200EG

Voltage - Output
5V, ±15V, 24V
Number Of Outputs
4
Power (watts)
200W
Applications
Commercial
Power Supply Type
Switching (Open Frame)
Voltage - Input
85 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
5 VDC @ 18A
2nd Output
24 VDC @ 3A
3rd Output
-15 VDC @ 1A
4th Output
15 VDC @ 3A
Size / Dimension
9" L x 5" W x 2.5" H (228.6mm x 127mm x 63.5mm)
Power (watts) - Rated
200W
Operating Temperature
0°C ~ 50°C
Efficiency
65%
Approvals
CE, CSA, IEC, UL
Line Regulation
2%, 3%
Load Regulation
2%, 3%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
64
GPC200
200 Watt Global Performance Switchers
SPECIFICATIONS:
Ac Input
85-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated output
load: 5.5 A
Hold-Up Time
20 ms minimum from loss of ac input at full load, nominal line
(115 Vac).
Output Power
150 W convection; 200 with 26 cfm air; 220 W peak. Peak ratings
are for 60 s maximum duration, 10% duty cycle. During peak
load condition, output regulation may exceed total regulation
limits.
Overload Protection
Fully protected against short circuit and output overload. Short
circuit protection is cycling type power limit on outputs 1 & 2;
foldback type on outputs 3 & 4. Recovery after fault is automatic.
See output ratings chart for additional notes or conditions.
Overvoltage Protection
Main outputs: 124% ± 12% typical.
Efficiency
Minimum 65% at full rated load, nominal input voltage, depending
on model and load distribution.
Input Protection
Internal ac fuse provided. Designed to blow only if a catastrophic
failure occurs in the unit.
Inrush Current
Inrush is limited by internal thermistors. Inrush at 240 Vac under
cold start conditions will not exceed 60 A.
Temperature Coefficient
0.03%/
Thermal Shutdown
Provided as a standard feature. Designed to protect unit from
prolonged overtemperature.
Environmental
Designed for 0 to 50°C operation at full rated output power;
derate output current and total output power by 2.5% per °C
above 50°C. See Environmental and Packaging Specifications
on next page.
°
C typical on all outputs.
Commercial/GPM200 Medical
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com
FEATURES:
• Wide-range ac input 85-264 Vac
• 2-year warranty
• Conducted EMI exceeds FCC Class B and CISPR 22
• Commercial Approved to UL1950, IEC950 and
• Medical Approved to UL2601-1, IEC601-1 and
• Multiple outputs
Power Fail
TTL- or CMOS-compatible output goes low (< 0.5 V) 5 ms
before output voltage drops more than 4% below nominal
voltage upon loss of ac power. The signal is factory set to trip on
84 to 94 Vac brown-out depending upon incoming line impedance
and distortion. Other settings are available to the user through
adjustment of built-in potentiometer.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode.
Measured with noise probe directly across output terminals of
the power supply.
Transient Response
Main output—500 µs typical response time for return to within
0.5% of final value for a 50% load step change. i/ t<0.2 A/µs.
Maximum voltage deviation is 3.5%. Startup/shutdown overshoot
less than 3%.
Remote Sense
Provided as a standard feature on main 5 V output.
Voltage Adjustment
Built-in potentiometer adjusts voltage ±5% on output 1 & 2.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the following
emissions requirements:
EMI SPECIFICATIONS
Conducted Emissions GPC200 EN55022 Class B; FCC Class B
Conducted Emissions GPM200 EN55011 Class B; FCC Class B
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
Commercial Leakage Current
0.95 mA 254 Vac @ 60 Hz input (with no deviations).
Commercial Safety
Approved to UL1950, CSA22.2 No. 234 Level 3, IEC950 and
EN60950. UL file #E135803 commercial; CSA #LR46516 all
models. The output(s) are intended for safety earthed Signal
Output and Intermediate Circuits only. All dc outputs are SELV
under normal and single fault conditions.
Medical Leakage Current
60 µA 254 Vac @ 60 Hz input.
Medical Safety
Approved to UL2601-1, CSA-C22.2 No. 601 Level 3 and IEC601.
UL file E116994; CSA #LR46516. The output(s) are intended for
safety earthed Signal Output and Intermediate Circuits only. The
output(s) are not acceptable for patient connection without
additional isolation. All dc outputs are SELV under normal and
single fault conditions.
Class B (Commercial models) and CISPR 11 Class B
(Medical models)
CSA22.2-234 L3
CSA22.2 No. 601
marked to LVD
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-5, 1 kV diff., 2 kV com.
COMPLIANCE LEVEL
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz

Related parts for GPC200EG