HPS3000-9 Emerson Network Power, HPS3000-9 Datasheet

POWER SUPPLY AC/DC 48V 650W

HPS3000-9

Manufacturer Part Number
HPS3000-9
Description
POWER SUPPLY AC/DC 48V 650W
Manufacturer
Emerson Network Power
Series
HPS3000r
Datasheet

Specifications of HPS3000-9

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
3000W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
180 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 62A
Size / Dimension
12.9" L x 4.2" W x 1.57" H (327.7mm x 106.7mm x 39.9mm)
Power (watts) - Rated
3000W
Operating Temperature
-10°C ~ 40°C
Efficiency
90%
Approvals
CB, CSA, cUL, NEMKO, TUV, UL
Output Voltage
48V
Output Power (max)
3000W
Screening Level
Commercial
Product Height (mm)
40mm
Product Depth (mm)
106.7mm
Operating Temperature Min Deg. C
-10C
Operating Temperature Max Deg. C
40C
Mounting Style
Desktop
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
454-1275
HPS3000 Series
3000 Watts
• 3000 W output power
• 40 W/cu-in
• Optional customer provided air
• 1U x 3U form factor
• N+1 Redundant
• Hot-swap
• Internal OR-ing
• 5 V housekeeping
• High efficiency 89% @ 200 Vac,
• Variable speed “smart fans”
• Two year warranty
Distributed Power Bulk Front-End
Single Output
Special Features
Compliance
• POE Isolation
• EMI Class B - EN55022, Level “A”
@ 230 Vac
• EN61000 Immunity
Safety
• UL/cUL
• CSA
• China
• Nemko
• CB Report
• CSA 22.2
100% load
60950
60950
CCC
TUV
60950
Electrical Specifications
Input
Input ra n ge (operating):
Input range (nominal):
Frequency:
Input fusing:
Inrush current:
Power factor:
Harmonics:
Input current:
Holdup time:
Leakage current:
Power line transient:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
47 to 63 Hz
Internal 25 A fuses
≤40 A peak
0.97 typical
Meets IEC 1000-3-2
requirements
19 A max input current
10 ms minimum
1.4 mA
MOV directly after the fuse
Input through Card Edge Connection
on same end as DC output
Both lines fused
Either hot or cold start
Meets EN61000-3-2
@ 50% load
At full rated load
At 240 Vac
Embedded Power for
Business-Critical Continuity
Rev. 02.22.11_81
HPS3000 Series
1 of 8

Related parts for HPS3000-9

HPS3000-9 Summary of contents

Page 1

... Frequency Input fusing: Internal 25 A fuses Inrush current: ≤40 A peak Power factor: 0.97 typical Harmonics: Meets IEC 1000-3-2 requirements Input current max input current Holdup time minimum Leakage current: 1.4 mA Power line transient: MOV directly after the fuse Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series Input through Card Edge Connection on same end as DC output Both lines fused Either hot or cold start Meets EN61000-3-2 @ 50% load At full rated load At 240 Vac ...

Page 2

... Measured with a 0.1µF Ceramic and 10 µF Tantalum capacitor on any input Nominal Voltage Setting 50% load step @ 1 A/us Step load valid between 10% to 100% of output rating. Total power in 1U 19” rack Output to return >2000 Vac Digital sharing control 48 V output 5 Vsb output 48 V output 5 Vsb output Both PFC and output converter monitored 5 Vsb will operate under overtemperature condition. Built in hysteresis Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series 80 90 100 C serial bus ...

Page 3

... Module Information (All units in mm) Embedded Power for Embedded Power for Business-Critical Continuity Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series ...

Page 4

... V_STBY 41 SYS_GND 25 Reserved 40 Reserved 26 PRESENT# 39 ACOK# 27 DCOK/PWOK# 38 SMBUS_ALERT_OUT 28 SDA 37 SCL 29 HVCC PSON# 35 PSKILL 31 #ALERT ISHARE 33 A0 Embedded Power for Embedded Power for Business-Critical Continuity Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series ...

Page 5

... Main Vout T AC_On_Delay T PWOK_On PWOK T sb_On 3.3 V Vout T SB_Vout PS_ON AC_OK AC Input ON / OFF Cycle Timing Diagram T Vout_Holdup T PWOK_Off_ T PWOK_Off_ T PWOK_Off_ T T PWOK_Delay T PWOK_On T ACOK_Delay Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series PWOK_Off_ T PWOK_Off PWOK_On T PSON_PWOK T PSON_On_Delay PSON ON / OFF Cycle ...

Page 6

... Accepts an open collector/drain input from the system. Pulled-up to the 5 Vsb located in power supply. ON OFF MIN MAX 0 V 0.4 V 2. msec 400 msec Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series Units msec msec msec msec msec msec msec msec msec msec msec msec ...

Page 7

... MIN 0 V 2.0 V 100 msec 1 msec pwok off Table 12 ACOK# Signal Characteristics Pull- Vsb through a resistor in the host Not present MIN 0 V 2.0 V Embedded Power for Business-Critical Continuity supply. ON OFF MAX 0 1000 msec 100 µsec 1000 msec system. Present MAX 0 µA Rev. 02.22.11_81 HPS3000 Series ...

Page 8

... Quality Assurance Full QAV testing shall be conducted in accordance with Emerson Network Power Standards with reports available upon request. Warranty Emerson Network Power shall warrant the power supply to be free of defects in materials and workmanship for a minimum period of two years from the date of shipment, when operated within specifications. The warranty shall be fully transferable to the end owner of the equipment powered by the supply. Ordering Information Model Number Main Output HPS3000-9 48 Vdc Table 13 LED Indicators Power LED (GREEN) (AMBER) OFF Blinking ON OFF ON ...

Related keywords