Specifications of MY3N-DC24

Relay Type
General Purpose
Contact Form
3PDT (3 Form C)
Contact Rating (current)
5A
Switching Voltage
250VAC, 125VDC - Max
Coil Type
Standard
Coil Current
36.9mA
Coil Voltage
24VDC
Turn On Voltage (max)
19.2 VDC
Turn Off Voltage (min)
2.4 VDC
Mounting Type
Socket
Termination Style
Socketable
Circuit
3PDT (3 Form C)
Contact Rating @ Voltage
5A @ 220VAC
Control On Voltage (max)
19.2 VDC
Control Off Voltage (min)
2.4 VDC
Power Consumption
0.9 W
Contact Carry Current
3 A
Maximum Switching Current
5 A
Contact Rating
5 A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
MY3NDC24
■ Contact Ratings
Note: Don’t exceed the carry current of a Socket in use. Please see page 9.
■ Characteristics
Note: The values given above are initial values.
■ Endurance Characteristics
Rated load
Carry current
Max. switching
voltage
Max. switching
current
Max. switching
power
Failure rate
(reference value)
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Endurance
Ambient temperature
Ambient humidity
Weight
2-pole
4-pole
4-pole (bifurcated)
Item
Pole
5A, 250 VAC
5A, 30 VDC
10 A (see note)
250 VAC
125 VDC
10 A
2,500 VA
300 W
5 VDC, 1 mA
Item
Resistive load
(cos φ = 1)
AC:50,000,000 operations min.
DC:100,000,000 operations min.
20,000,000 operations min.
Mechanical life (at 18,000 operations/hr)
2-pole
2A, 250 VAC
2 A, 30 VDC
1,250 VA
300 W
(cos φ = 0.4, L/R = 7 ms)
Inductive load
100 m Ω max.
20 ms max.
20 ms max.
Mechanical: 18,000 operations/hr
Electrical:
1,000 M Ω min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Destruction: 1,000 m/s
Malfunction: 200 m/s
See the following table.
Operating: –55 ° C to 70 ° C (with no icing)
Operating: 5% to 85%
Approx. 35 g
1,800 operations/hr (under rated load)
3 A, 250 VAC
3 A, 30 VDC
5 A (see note)
250 VAC
125 VDC
5 A
1,250 VA
150 W
1 VDC, 1 mA
Resistive load
(cos φ = 1)
2
2
General-purpose Relay
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
4-pole
(cos φ = 0.4, L/R = 7 ms)
Inductive load
500,000 operations min.
200,000 operations min.
100,000 operations min.
All Relays
(at 1,800 operations/hr under rated load)
MY New model
3 A, 250 VAC
3 A, 30 VDC
1,250 VA
150 W
1 VDC, 100 µ A
Resistive load
(cos φ = 1)
Electrical life
4-pole (bifurcated)
0.8 A, 250 VAC
1.5 A, 30 VDC
500 VA
150 W
(cos φ = 0.4, L/R = 7 ms)
Inductive load
3