MKS1XTIN-10 DC24 Omron, MKS1XTIN-10 DC24 Datasheet

RELAY PWR DC SPST-NO 10A 24VDC

MKS1XTIN-10 DC24

Manufacturer Part Number
MKS1XTIN-10 DC24
Description
RELAY PWR DC SPST-NO 10A 24VDC
Manufacturer
Omron
Series
MK-S(X)r
Datasheet

Specifications of MKS1XTIN-10 DC24

Relay Type
General Purpose
Coil Resistance
380 Ohms
Coil Type
Standard
Contact Form
SPST-NO (1 Form A)
Contact Rating (current)
10A
Switching Voltage
220VDC - Max
Coil Current
63.2mA
Coil Voltage
24VDC
Turn On Voltage (max)
19.2 VDC
Turn Off Voltage (min)
3.6 VDC
Mounting Type
Socket
Termination Style
Socketable
Circuit
SPST-NO (1 Form A)
Contact Rating @ Voltage
10A @ 220VDC
Control On Voltage (max)
19.2 VDC
Control Off Voltage (min)
3.6 VDC
Contact Rating
10 A
Contact Termination
Solder Lug
Mounting Style
PCB or DIN Rail
Power Consumption
1.5 W
Contact Material
Silver Tin Indium
Coil Voltage Vdc Nom
24V
Contact Current Max
10A
Contact Voltage Dc Nom
220V
Contact Configuration
SPST-NO
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
MKS1XTIN10DC24
Z2965
MK-S-series Relays with AC and DC Load
switching Models
• Models for DC Loads can switch 220 VDC, 10 A (resistive).
• Models for AC Loads can switch 250 VAC, 15 A (resistive).
• Lineup includes models with 1FormA and 1FormA+1FormB
• Models available with operation indicators and built-in test buttons.
• Standards: UL/CSA, IEC (TÜV certification)
• RoHS compliant.
Ordering Information
■ List of Models
■ Accessory (Order Separately)
Connecting Socket and Hold-down Clips
Note: 1. The P7M-06P, P7MF-06, and P7MF-06-D can be used with models for DC loads with an SPST-NO or SPST-NO/SPST-NC contact form
Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in the specifications.
Type
Standard
Built-in Operation Indicators
Test Button
Test Button and Built-in Operation Indicators MKS1XTIN-10
Back-connecting Socket
Front-connecting Socket
contact arrangements.
General Purpose Power Relays
MKS-X
2. The P7MF-06-D has a built-in diode and can thus be used only with Relays with DC operating coils. Do not use it with a Relay with an
3. Refer to Gang Mounting in the Safety Precautions section for the conditions required to gang mounti multiple relays side-by-side.
4. Use the Clips to securely mount the Relay and prevent it from falling due to vibration or shock.
2. Refer to Terminal Arrangement and Internal Connections for all wiring diagrams.
or with models for AC loads with an SPST-NO or SPST-NO/SPST-NC contact form.
AC operating coil.
Example: MKS2XTIN-11 AC240
Classifications
Contact form
DIN Track or Panel Mount
PCB Mount
MKS1XT-10
MKS1XTN-10
MKS1XTI-10
SPST-NO
Model
Models for DC Loads
Built-in diode
Rated voltage
Yes
No
No
MKS2XT-11
MKS2XTN-11
MKS2XTI-11
MKS2XTIN-11
SPST-NO/SPST-NC
General Purpose Power Relays
Model
P7MF-06-D
P7M-06P
P7MF-06
Socket
MKS1T-10
MKS1TN-10
MKS1TI-10
MKS1TIN-10
SPST-NO
Model
Models for AC Loads
Hold-down Clip
MKS-X
PYC-A2
MKS2T-11
MKS2TN-11
MKS2TI-11
MKS2TIN-11
SPST-NO/SPST-NC
Model
1

Related parts for MKS1XTIN-10 DC24

MKS1XTIN-10 DC24 Summary of contents

Page 1

... Standard Built-in Operation Indicators Test Button Test Button and Built-in Operation Indicators MKS1XTIN-10 Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in the specifications. Example: MKS2XTIN-11 AC240 2. Refer to Terminal Arrangement and Internal Connections for all wiring diagrams. ...

Page 2

... NO NC Max. switching current NO NC Max. switching capacity NO (reference value) NC Note: These values apply to a switching frequency of 20 times per minute. 2 General Purpose Power Relays SPST-NO MKS1XT(I)(N)-10 Inductive load L DC13 class Double-break --- AgSnIn 5 A, 220 VDC 0.4 A, 220 VDC --- ...

Page 3

... VDC −40°C to 60°C (with no icing or condensation) Note: The range is −25°C to 60°C for models with built-in operation indicators 85% SPST-NO: Approx SPST-NO/SPST-NC: Approx General Purpose Power Relays Power consumption Max. voltage (V) (VA, W) 110% of rated Approx. 2.3 VA ...

Page 4

... Model Coil ratings 12, 24, 48, 110, 220 VDC MKS1XT@-@ 24, 100, 110, 120, 200, 220, 230, 240 VAC MKS2XT@-@ MKS1T@-@ MKS2T@-@ 4 General Purpose Power Relays Contact ratings 10 A, 220 VDC (Resistive 220 VDC L contacts 0.632 0.4 A, 220 VDC L 300 ms 0. 220 VDC (Resistive) ...

Page 5

... AC resistive load resistive load 1 NC 0.1 0. 100 1.000 Switching voltage (V) MKS2XT-11 DC Specification 100 Must operate Number of Relays: 5 voltage Must release voltage - Ambient temperature (°C) MKS2XT@-11 10 220 VDC NO 1 0 100 Load time constant (ms) MKS-X General Purpose Power Relays 5 ...

Page 6

... Operation Indicators MKS1XTIN-10 MKS2XTIN-11 Models for AC Loads Models with Test Button MKS1TI-10 MKS2TI-11 Models with Test Button and Built-in Operation Indicators MKS1TIN-10 MKS2TIN-11 Terminal Arrangement and Internal Connection (Bottom View) MKS1XT-10 MKS1XTN-10 MKS1XTI-10 MKS1XTIN-10 DC specification 4 6 (+) 4 6 (+) (+) B (− MKS1T-10 MKS1TN-10 MKS1TI-10 ...

Page 7

... Terminal Arrangement/Internal Connections (TOP View) P7MF-06 35.5 Note: 1. The internal connections diagram is for the MKS2(X)T@@-11 The P7MF-06-D has polarity. Be careful to wire with the correct polarity. General Purpose Power Relays PCB Mounting Holes (Bottom View 11.05 11.05 Mounting Holes (TOP View) ...

Page 8

... Hold-down Clip PYC-A2 One Set (Two Clips) 5 max. 42.8 4.5 4.5 1.2 Note: The minimum order for the PYC-A2 is ten clips. Socket Mounting Height P7M-06P P7MF-06 P7MF-06-D 8 General Purpose Power Relays 64 MK-S(X) 61 MK-S( MKS ...

Page 9

... Safety Precautions Be sure to read the precautions and information common to all electromechanical relays, contained in the Technical User’s Guide, “Electromechanical Relays, Technical Information” for correct use. Precautions for Correct Use Installation • Models for DC loads (i.e., models with “X” in the model number) have permanent magnets built into the insulating block ...

Page 10

... MEMO 10 General Purpose Power Relays MKS-X ...

Page 11

... Seller within 30 days of receipt of shipment. III. PRECAUTIONS 1. Suitability THE BUYER’S SOLE RESPOINSIBILITY TO ENSURE THAT ANY OMRON PRODUCT IS FIT AND SUFFICIENT FOR USE IN A MOTORIZED VEHICLE APPLICATION. BUYER SHALL BE SOLELY RESPONSIBLE FOR DETERMINING APPROPRIATENESS OF THE PARTICULAR PRODUCT WITH RESPECT TO THE BUYER’ ...

Page 12

... THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Complete “Terms and Conditions of Sale” for product purchase and use are on Omron’s website at http://www.components.omron.com – under the “About Us” tab, in the Legal Matters section. ...

Related keywords