PJRS110A Crouzet USA, PJRS110A Datasheet

RELAY ALTERNATING 110VAC 8OCTAL

PJRS110A

Manufacturer Part Number
PJRS110A
Description
RELAY ALTERNATING 110VAC 8OCTAL
Manufacturer
Crouzet USA
Series
JRSr
Datasheets

Specifications of PJRS110A

Contact Current Max
10A
Contact Voltage Ac Nom
250V
Contact Voltage Dc Nom
250V
Contact Configuration
SPDT
Relay Mounting
Plug In
Average Power Consumption
5VA
External Height
74.5mm
Relay Type
Impulse
Contact Form
SPDT (1 Form C)
Contact Rating (current)
10A
Switching Voltage
250VAC, 250VDC - Max
Coil Type
Latching, Single Coil
Coil Voltage
110VAC
Mounting Type
Socket
Termination Style
8 Pin Socketable
Circuit
SPDT (1 Form C)
Contact Rating @ Voltage
10A @ 250VAC
Brand/series
JRS Series
Current, Rating
10 A
Function
Alternating
Material, Contact
AgCdO
Number Of Pins
8
Power, Rating
2200⁄80 VA⁄W
Resistance, Insulation
1000 Megohms
Standards
UL
Temperature, Operating
-10 to +60 °C
Termination
Plug-In
Voltage, Control
110 VAC
Voltage, Rating
250 VAC/VDC
Contact Rating
10 A
Mounting Style
PCB
Power Consumption
80 W
Contact Material
Silver Cadmium Oxide
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coil Current
-
Control On Voltage (max)
-
Control Off Voltage (min)
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
646-1161
CONTROLS
5-12
JRS SERIES
ALTERNATING RELAY WITH
SELECTOR SWITCH
UL listed
• Duplex Alternating Control
• SPDT or DPDT Control Relay
• 10 Amp Rated
• Externally Controlled
• Selection of Lead or Lag Load
The electronic alternating relay is designed to replace mechanical
style devices used in control applications requiring a duplexing
or alternating action of the control circuits to operate pumps,
compressors, etc. This is achieved by activating a control switch
which is common to one side of the input control voltage. The
output contact of the relay(s) change state when this switch is
opened (on de-energization of the control circuit). When the control
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC/DC, 110, 220 VAC
Maximum power consumption . . . 24 VAC: 1.5 VA
Output . . . . . . . . . . . . . . . . . . . . . . SPDT 10 A resistive
Minimum pulse
Contact material
Maximum loading
Maximum switching voltage . . . . . 250 VAC
Relay maximum power rating . . . . 2200 VA
Mechanical life of relay . . . . . . . . . 3 x 10
Electrical life of relay . . . . . . . . . . . 2 x 10
Operating temperature . . . . . . . . . 14°F to 140°F
Weight . . . . . . . . . . . . . . . . . . . . . . 2.8 oz. (100g)
ORDERING INFORMATION:
L = 11 pin plug-in
P = 8 pin plug-in
NOTE: DPDT relay available only with 11 pin plug-in (L)
MOUNTING
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
. . . . . . . . . . . . . . . 30 ms
. . . . . . . . . . . . . . AgCdO
. . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
±15%, 50/60 Hz
110 VAC: 5 VA
220 VAC: 11VA
DPDT 10 A resistive
DPDT 10 A crosswired
6
5
Products and specifications subject to change without notice.
operations
at 2200 VA resistive load
MOUNTING
Consult factory for application assistance.
L
250 VDC
80 W
-10°C to +60°C
.
LJRS 2 = DPDT
PJRS = SPDT
PJRXS = DPDT (crosswired)
SERIES
JRS 2
initiate switch is actuated and released or opened, the relay will
change state. The next time the initiate switch is actuated, it will
change back to its original state. Two red LED’s located on the top
of the dust resistant enclosure provide the status of the relay. A 3
Position Selector switch is installed for selection of normal opera-
tion (alternating) or selection of lead or lag load.
WIRING DIAGRAM:
SERIES
3
2
PJRS
1
4
5
8
INITIATE
SWITCH
6
7
INPUT POWER
110A
INITIATE SWITCH
3
2
PJRXS
1
4
5
8
6
7
CONTROLS
24A = 24
VAC/DC
110A = 110 VAC
220A = 220 VAC
INPUT POWER
3
4
2
LJRS2
5
1
INITIATE
6
1 1
SWITCH
7
10
8
9

Related parts for PJRS110A

PJRS110A Summary of contents

Page 1

CONTROLS JRS SERIES ALTERNATING RELAY WITH SELECTOR SWITCH UL listed • Duplex Alternating Control • SPDT or DPDT Control Relay • 10 Amp Rated • Externally Controlled • Selection of Lead or Lag Load The electronic alternating relay is designed ...

Page 2

...

Related keywords