CHD-38-30013 Tyco Electronics, CHD-38-30013 Datasheet

RELAY TIME DELAY DPDT 24 VDC 11

CHD-38-30013

Manufacturer Part Number
CHD-38-30013
Description
RELAY TIME DELAY DPDT 24 VDC 11
Manufacturer
Tyco Electronics
Series
CHr
Datasheet

Specifications of CHD-38-30013

Relay Type
Integrated
Function
Off-Delay
Circuit
DPDT (2 Form C)
Delay Time
1 Sec ~ 180 Sec
Output Type
Mechanical Relay
Contact Rating @ Voltage
10A @ 277VAC
Voltage - Supply
24VDC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage, Trigger Signal
Contact Configuration
DPDT
Nom Input Voltage
24VDC
Delay Time Range
1s To 180s
Timing Adjustment
Knob
Relay Mounting
Plug In
Peak Reflow Compatible (260 C)
No
Supply Voltage
24VDC
Timing Range
1 s to 180 s
Contact Form
2 Form C (DPDT) 2 C/O
Contact Rating
10 A at 30 VDC, 277 VAC
Mode Of Operation
Delay on Release
Lead Free Status / RoHS Status
Lead free / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant, Lead free / RoHS non-compliant
Other names
2-1393137-3
1226
Timing Modes
Delay on operate – Delay period begins when input voltage is applied. At
the end of the delay period, the relay will operate and will not release until
input voltage is removed. Reset occurs when input voltage is reapplied.
Delay on release – Input voltage must be applied continuously to operate
the internal relay. When the control switch is closed, the relay energizes.
When the control switch is opened, timing begins. When timing is
complete, the relay will de-energize. Time may be reset to zero during
timing by closing the control switch.
Interval on – The relay energizes and timing begins when input voltage is
applied. At the end of the time delay period the relay will de-energize.
Reset is accomplished by removing, then reapplying, the input voltage.
Timing Specifications
Timing Ranges: From 1 to 180 sec.
Timing Adjustment: Fixed and knob adjustable.
Tolerance (for AC units add 1/2 cycle 60 Hz.):
Delta Time (for AC units add 1 cycle 60 Hz.):
Repeatability (for AC units add 1 cycle 60 Hz.):
Release Time: 125 ms, typ.; 200 ms, max.
Recycle Time: 125 ms, typ.; 200 ms, max.
INPUT
VOLTAGE
N.O. RELAY
CONTACTS
CONTROL
SWITCH
N.O. RELAY
CONTACTS
INPUT
VOLTAGE
N.O. RELAY
CONTACTS
Dimensions are shown for
reference purposes only.
Knob Adj. Types:–0, +20% of max. specified at high end of timing range;
Fixed Types:
Res. Adj. Types:
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
min. specified, or less, at low end.
at low end.
5%.
5% at high end of timing range; min. specified, or less,
TIME
TIME
Dimensions are in inches over
(millimeters) unless otherwise
specified.
10%.
2%.
TIME
Catalog 1308242
Issued 3-03
CH
Mid- To Low-Priced
CMOS IC Time Delay Relay
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Contact Data @ 25 C
Arrangements: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
Initial Dielectric Strength
Between Open Contacts: 500V rms, 60 Hz.
Between All Other Conductors: 500V rms, 60 Hz.
Input Data @ 25 C
Voltage: 24 through 240VAC and 24VDC.
Power Requirement: AC Types: Typically less than 3 VA.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
Mechanical Data
Termination: 8- or 11-pin octal style plug.
Enclosure: White plastic case. Knob adjustable types have dial scale for
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
Weight: 6 oz. (170g) approximately.
Input Voltages & Limits @ 25 C
Environmental Data
Temperature Range: Storage: -55 C to +85 C.
Choice of timing modes
Fixed or knob adjustable types
10A output relay with DPDT contacts
Various models time from 1 to 180 sec.
File E22575
File LR15734
– Delay on operate
– Delay on release
– Interval on
AC models will operate on 50 or 60 Hz.
Voltage
Specifications and availability
subject to change.
Type
120VAC.
series
AC
DC
screw terminal sockets. 11-pin types fit either 27E123 or
27E892 (snap-on) screw terminal sockets.
reference only.
DC Types: Typically less than 3 W.
Operating: -10 C to +55 C.
Nominal
Voltage
120
240
24
24
Minimum
Voltage
105
210
20
20
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Maximum
Voltage
130
260
28
32
P&B

Related parts for CHD-38-30013

CHD-38-30013 Summary of contents

Page 1

... SWITCH OFF N.O. RELAY ON CONTACTS OFF Interval on – The relay energizes and timing begins when input voltage is applied. At the end of the time delay period the relay will de-energize. Reset is accomplished by removing, then reapplying, the input voltage. INPUT ON VOLTAGE OFF N.O. RELAY ...

Page 2

... Fig Pin Specifications and availability subject to change. P&B Adjustment Wiring Dia. Part Number Knob 3 CHB-38-30011 CHB-38-70011 Knob 3 CHB-38-70012 CHB-38-70013 Knob 3 CHD-38-30011 CHD-38-30013 Adjustment Wiring Dia. Part Number CHB-38-70021 Knob 1 CHB-38-70022 CHB-38-70023 Knob 1 CHD-38-30021 www.tycoelectronics.com Technical support: 1227 Refer to inside back cover. ...