QOU110 SQUARE D, QOU110 Datasheet

CIRCUIT BREAKER, THERMAL MAG, 1P, 10A

QOU110

Manufacturer Part Number
QOU110
Description
CIRCUIT BREAKER, THERMAL MAG, 1P, 10A
Manufacturer
SQUARE D
Series
QOUr
Type
Thermal/Magneticr
Datasheet

Specifications of QOU110

Actuator Style
Toggle
No. Of Poles
1
Current Rating
10A
Voltage Rating Vac
240V
Mounting Type
DIN Rail
Voltage Rating Vdc
48V
Actuator Type
Handle
Brand/series
QOU Miniature — Low Ampere
Number Of Poles
1
Special Features
Visi-Trip® Trip Indicator
Voltage Rating
120 V
Leaded Process Compatible
No
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Catalog
September
2005
QOU Miniature Circuit
Breakers and Switches
Unit Mount (Cable-in/Cable-out)
Class 720
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
UL Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17
Circuit Breaker Tripping Characteristics (Trip Curves) . . . . . . . . . . . page 19
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 28
QYU One-Pole 277 Vac Supplementary Protectors. . . . . . . . . . . . . page 30

Related parts for QOU110

QOU110 Summary of contents

Page 1

Catalog September 2005 QOU Miniature Circuit Breakers and Switches Unit Mount (Cable-in/Cable-out) Class 720 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . ...

Page 2

QOU Miniature Circuit Breakers and Switches Application Information APPLICATION INFORMATION QOU Miniature Circuit Breaker Types Miniature molded case circuit breakers are intended for use in residential and commercial applications. They are tested and listed according to UL Standard 489 and ...

Page 3

... QOU160* QOU160VH QOU260* QOU170* — QOU270* ‡ ‡ QOU180 — QOU280 ‡ ‡ QOU190 — QOU290 ‡ QOU1100 — QOU2100 — — QOU2125 Application Information Two-Pole Three-Pole 240 Vac 120/240 Vac 240 Vac 22K AIR 10K AIR — QOU310 QOU215H* QOU215VH QOU315* — ...

Page 4

... Square D calibrates the thermal elements and they are not field-adjustable. The thermal trip elements are calibrated for 40° C (104° F) ambient temperature, per UL Standard 489 and CSA Standard C22.2 No ...

Page 5

... These miniature circuit breakers are designed for use with a standard 35 mm DIN mounting rail (DIN/EU 50 022, 0.30 x 1.38 in. [7 mm]). Standards Square D brand QOU miniature circuit breakers are manufactured and tested according to the following standards: • UL Standard 489 (File E84967) • ...

Page 6

... QOU Miniature Circuit Breakers and Switches Application Information Catalog Numbers Square D brand circuit breakers are ordered by a catalog number that includes the circuit breaker family, description, number of poles, amperage rating and suffix. Table 2: QO Miniature Circuit Breaker Family Description U – Unit Mounted (Lugs on Both Ends) No. of Poles 1 – ...

Page 7

Interrupting Rating The interrupting rating of a circuit breaker is the highest current at rated voltage that the circuit breaker is intended to interrupt under standard test conditions. Circuit breakers must be chosen with interrupting ratings equal to or greater ...

Page 8

QOU Miniature Circuit Breakers and Switches Application Information UL HACR Type HACR is an acronym that designates circuit breakers certified to be used on heating, air conditioning, and refrigeration loads. The 9th edition of UL489 eliminated special testing requirements for ...

Page 9

... C. Rerating of Thermal-magnetic Circuit Breakers for Ambient Conditions Square D thermal-magnetic circuit breakers are to be applied in ambient temperatures within the range of 14° 140° F (-10° 60° C). Use the following rerating guidelines: • ...

Page 10

... A noncontinuous load.” Frequency Rating 40 A The standard-rated frequency for circuit breakers is 60 Hz, but Square circuit breakers can be applied systems without thermal magnetic rerating. Other frequencies can affect the thermal, magnetic and 15 A short-circuit tripping characteristics of circuit breakers. ...

Page 11

... At frequencies above 60 Hz, the interrupting rating of thermal-magnetic circuit breakers is less than the 60 Hz interrupting rating. Unless specifically marked for use of 400 Hz systems, the interrupting rating of Square D circuit breakers is reduced to 1/10th of the 60 Hz interrupting rating. Magnetic Tripping Performance At frequencies above 60 Hz more current is necessary to magnetically trip a circuit breaker than ...

Page 12

QOU Miniature Circuit Breakers and Switches Accessories ACCESSORIES Factory-installed Accessories QOU circuit breakers and QYU supplementary protectors can be supplied with electrical accessories factory-installed. Available factory-installed accessories are shown in Table 5 below. Each QOU circuit breaker or QYU supplementary ...

Page 13

Figure 7: Auxiliary Switch Accessory Circuit Breaker ON "A" Contact "B" Contact Circuit Breaker OFF or Tripped "A" Contact "B" Contact Figure 8: Alarm Switch Accessory Normally-open Alarm Switch Circuit Breaker (Tripped) Circuit Breaker (OFF or ON) 09/2005 QOU Miniature ...

Page 14

QOU Miniature Circuit Breakers and Switches Accessories Field-installed Accessories Table 6: Field-installed Accessories Accessory Ties two 1-pole circuit breakers together. Handle Tie Ties three 1-pole circuit breakers together; includes lock-off for California Title 24. Clamp for holding QOU single-pole handle ...

Page 15

QO1HT QO1LO Handle Lock-off Handle Tie Handle Lock-off QOU1PA QO1HPL Padlock Attachment Padlock Attachment QOU1PL Padlock Attachment QOU2DTILA Mechanical Interlock Attachment QOUMF1 suffix -3100 or QOUMFSI Mounting Foot Tapped Mounting Foot Jumper Bar Base Cover Plate ...

Page 16

QOU Miniature Circuit Breakers and Switches Accessories Ring-tongue Rainproof Covers Terminal Adapter End Quick Forward or Reverse Connector Quick Connector Table 7: Optional Terminations Type Field-installed Quick Connectors Field-installed Quick Connectors Factory-installed Quick Connectors Available only on 10–60 ampere circuit ...

Page 17

UL REQUIREMENTS A UL label on the QOU miniature circuit breaker indicates that the circuit breaker meets the requirements of UL Standard 489 for molded case circuit breakers. Underwriters Laboratories Inc. (UL), the Canadian Standards Association (CSA), the National Electrical ...

Page 18

QOU Miniature Circuit Breakers and Switches UL Requirements Calibration Retest Both the 200% and 135% thermal calibration tests are repeated. Short Circuit For circuit breakers rated 240 V, two short-circuit tests per pole and one test with all poles connected ...

Page 19

CIRCUIT BREAKER TRIPPING CHARACTERISTICS (TRIP CURVES) The tripping characteristics of thermal-magnetic circuit breakers are represented by a characteristic tripping curve that plots tripping time versus current level. See page 20. The curve shows the amount of time required for a ...

Page 20

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 Copyright © Square D Company 1987 20 © 2005 Schneider Electric All Rights Reserved MULTIPLES OF RATED CURRENT MAXIMUM SINGLE POLE TRIP TIMES AT 25¡C BASED ON NEMA AB-2, 1980 (60 HZ) CYCLE 2 (60 HZ) MULTIPLES OF RATED CURRENT ...

Page 21

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 Copyright © Square D Company 1987 09/2005 QOU Miniature Circuit Breakers and Switches MULTIPLES OF RATED CURRENT MAXIMUM SINGLE POLE TRIP TIMES AT 25¡C BASED ON NEMA AB-2, 1980 (60 HZ) CYCLE 2 (60 HZ) MULTIPLES OF RATED CURRENT ...

Page 22

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 © 1995 Square D 22 © 2005 Schneider Electric All Rights Reserved MULTIPLES OF RATED CURRENT MAXIMUM SINGLE POLE TRIP TIMES AT 25¡C BASED ON NEMA AB-2, 1980 (60 HZ) CYCLE 2 (60 HZ) MULTIPLES OF RATED CURRENT 10000 ...

Page 23

Curve 730-4 10000 9000 8000 7000 6000 5000 4000 3000 2000 1500 1000 900 800 700 600 500 400 300 200 150 100 ...

Page 24

QOU Miniature Circuit Breakers and Switches Tripping Curves Curve 730-5 10000 9000 8000 7000 6000 5000 4000 3000 2000 1500 1000 900 800 700 600 500 400 300 200 150 100 ...

Page 25

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 © 1995 Square D 09/2005 QOU Miniature Circuit Breakers and Switches MULTIPLES OF RATED CURRENT MAXIMUM SINGLE POLE TRIP TIMES AT 25¡C BASED ON NEMA AB-2, 1980 70A. 60A. 50A. (60 HZ) CYCLE 2 (60 HZ) ...

Page 26

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 Copyright © Square D Company 1987 26 © 2005 Schneider Electric All Rights Reserved MULTIPLES OF RATED CURRENT MAXIMUM SINGLE POLE TRIP TIMES AT 25¡C BASED ON NEMA AB-2, 1980 100A. 90A. 80A. (60 HZ) CYCLE 2 (60 HZ) ...

Page 27

... CYCLE .015 .01 .009 1 .008 .007 .006 .005 Copyright © Square D Company 1987 09/2005 QOU Miniature Circuit Breakers and Switches MULTIPLES OF RATED CURRENT (60 HZ) CYCLE 2 (60 HZ) MULTIPLES OF RATED CURRENT Tripping Curves 10000 QO MOLDED CASE CIRCUIT BREAKERS 9000 8000 CHARACTERISTIC TRIP CURVE NO 730-9 ...

Page 28

QOU Miniature Circuit Breakers and Switches Dimensions DIMENSIONS 1 & 2 pole 10A - 70A and 3 pole 10A -60A QOU Circuit Breakers 0.68 (17) 0.63 (16) 0.36 (9) 1.37 4.05 (35) (103) 0.26 (7) 0.61 (16) 0.75 (19) 0.76 ...

Page 29

Circuit Breakers 0.45 (11) 0.17 (4) Auxiliary Device 26˚ Reset 22˚ On 21˚ Off 3˚ 2.25 Tripped (57) 1.89 (48) 1.20 (30) 0.82 (21) 0.39 (10) 4.45 (113) 6.78 (172) 09/2005 QOU Miniature Circuit Breakers and Switches ...

Page 30

... These devices are designed to provide supplemental overcurrent protection in accordance with Article 240-10 of the 2005 NEC, which states that thermal-magnetic supplementary protectors cannot be used to replace the primary branch-circuit protection in an application. When used in combination with branch-circuit protection, as required in Article 210 of the 2005 NEC, these supplementary protectors can be used to protect lighting fixtures, appliances and other equipment or internal circuits and components of equipment ...

Page 31

DIMENSIONS QYU One-pole 277 Vac Supplementary Protectors 0.68 (17) 0.63 (16) 0.36 (9) 1.37 4.05 (35) (103) 0.26 (7) 0.61 (16) 0.75 0.75 (19) (19) 0.76 0.76 1.18 1.18 (19) (19) (30) (30) Typical Typical Both Ends Both Ends ON ...

Page 32

... Schneider Electric USA 3700 Sixth St. SW Cedar Rapids, IA 52404 USA 1-888-Square D 1-888-778-2733 0720CT9401R1/05 © 2005 Schneider Electric All Rights Reserved Replaces 0720CT9401 dated 08/1994 09/2005 ...