8910DPA33V02 SQUARE D, 8910DPA33V02 Datasheet - Page 4

CONTACTOR, 3PST-NO, 120VAC, 30A, PANEL

8910DPA33V02

Manufacturer Part Number
8910DPA33V02
Description
CONTACTOR, 3PST-NO, 120VAC, 30A, PANEL
Manufacturer
SQUARE D
Type
DPr
Datasheets

Specifications of 8910DPA33V02

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
Panel
Coil Voltage Vac Nom
120V
Relay Terminals
Screw
Contact Voltage Ac Nom
600V
Contact Current Max
30A
Mounting Type
Panel
Contact Form
3PST-NO
Current, Rating
30 A
Function
Contactor
Horsepower, Max, 1 Phase, At 115 V
2 @ 115 VAC, 5 @ 230 VAC
Horsepower, Max, 3 Phase, At 230 V
10 @ 230VAC, 15 @ 460VAC
Number Of Poles
3
Relay Type
Electro Mechanical
Voltage, Coil
120 VAC
Enclosure Type
Open
Maximum Voltage Rating
600 VAC
Phase
1-Phase
Operating Voltage
600VAC
Switching Power Ac1
5hp
Switching Power Ac3
15hp
Switching Current Ac1
40A
Switching Current Ac3
30A
Load Current Inductive
30A
Load Current Resistive
40A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Operating Tab
Auxiliary Contact Installation
Class 8910 — Types DP, DPA and SYD Application Data
4
Top Hooks
Bottom Tabs
Contactor
© 1998 Square D All Rights Reserved
2 Normally Open and 2 Normally Closed
4-Pole Contactors – 600 Vac Maximum
Auxiliary Contacts
NEMA Type 1 General Purpose Enclosures
for Type DP and DPA Contactors
Application Data
Mechanical Life:
Electrical Life:
Duty Cycle:
Approvals:
UL Listed
CSA Certified
t Voltage code must be specified to order this product. Refer to standard voltage codes listed in Coil Voltage
c Above 240 volts, all lines must be switched.
a N.C. poles on outside. N.C. poles “open” before N.O. poles “close.”
Code Table.
Amperes
Class 8910 Type
Type DP
Type DPA, SYD
Load
Full
20
25
30
40
Class 8910 Type
For Use with
DPA
DPA
DPA
DPA
DP
DPA
DPA122
DPA123
SYD
Resistive
Amperes
Load
25
35
40
50
Full Load Amperes
90-120
20-40
20-40
20-40
60-75
50
Poles
N.O.
2
2
2
2
Arrangement
1 N.O.
1 N.C.
1 N.O. & 1 N.C.
2 N.O.
1 N.O.
1 N.C.
1 N.O. & 1 N.C.
Contact
500,000 operations
100,000 operations
200,000 operations
Continuous
File E42240, CCN NLDX
File LR25490, Class 3211 04
Poles
N.C.
2
2
2
2
Poles
1 & 2
2 & 3
2 & 3
2 & 3
2 & 3
4
DPA14t
DPA24t
DPA34t
DPA44t
Type
Class 9999
Class 8910
Class 9991 Type
Type
D10
D01
D11
D20
SX6
SX7
SX8
DPG1
DPG1
DPG2
DPG3
DPG4
5/98
Form
Y392
Y392
Y392
Y392

Related parts for 8910DPA33V02