ELC-EX06NNNI-2 EATON CUTLER HAMMER, ELC-EX06NNNI-2 Datasheet - Page 23

Digital Output PLC

ELC-EX06NNNI-2

Manufacturer Part Number
ELC-EX06NNNI-2
Description
Digital Output PLC
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of ELC-EX06NNNI-2

Supply Voltage
24VDC
No. Of Analog Outputs
6
February 2009
Product Description
The Cutler-Hammer Intelligent
Technologies (IT.) DeviceNet Adapter
(D77D-DNA) from Eaton’s electrical
business has greatly increased the
functionality of IT. communicating
products, allowing monitoring and
control for IT. motor control devices.
The adapter concentrates all data
from these devices into a single
DeviceNet node.
To simplify the configuration of the
D77D-DNA, a simple auto-configure
button press sets the system up for
default operation. This automatically
configures the DeviceNet I/O assem-
blies to the system devices. The data
from these devices is assembled into
a single input and output message.
Application Description
In a typical DeviceNet Adapter applica-
tion, the D77D-DNA connects directly
to DeviceNet, and resides in a system
with communicating motor controls.
The data from these IT. devices is
assembled into a single input and out-
put message before being presented
to DeviceNet.
CA08102001E
Cat. No. D77D-DNA
Features, Functions and Benefits
Standards and Certifications
Approvals
Table 50-30. Approvals/Certifications
Electrical/EMC
Other Approvals
Description
ESD Immunity (IEC 61000-4-2)
Radiated Immunity (IEC 61000-4-3)
Fast Transient (IEC 61000-4-4)
Surge (IEC 61000-4-5)
RF Conducted (IEC 61000-4-6)
Magnetic Field (IEC 61000-4-8)
Ingress Protection Code
Radiated and Conducted Emissions EN 5011 Class A
Agency Certifications
For more information visit: www.eaton.com
Communication to DeviceNet
consuming one DeviceNet MAC ID.
Provides for control of all IT.
communicating devices connected
to the gateway.
Manually set to MAC ID and baud
rate; configuration using a software
application is not required for
normal operation.
Single button press auto configures
the gateway, setting up the system
for default operation.
Advanced configuration using
CH Studio.
PLC, I/O & Communications Products
IT. Connect
Communication Adapters (D77D Series) — DeviceNet Adapter
Specification
ODVA Conformance Tested
± 8 kV air, ± 4 kV contact
10V/m 80 – 1,000 MHz, 80% amplitude modulation @ 1 kHz
± 2 kV supply and control, ± 1 kV communications
± 1 kV line-to-ground, ± 2 kV line-to-line
10V, .15 – 80 MHz
30A/m, 50 Hz
IP20
UL 508, CUL (CSA C22.2 No. 14), CE (Low Voltage Directive),
Provides for backplane and inter-
connect cable connections to motor
control products.
Provides one I/O DeviceNet message
representing all connected devices.
Two independent ports.
Powered from backplane.
Isolated from DeviceNet.
Status LEDs for DeviceNet and
module health.
Provides for configuration of I/O
devices over DeviceNet.
Small package size.
DIN-rail mountable.
50-23
50

Related parts for ELC-EX06NNNI-2