PAXT0000 Red Lion Controls, PAXT0000 Datasheet - Page 11

Temperature Meter

PAXT0000

Manufacturer Part Number
PAXT0000
Description
Temperature Meter
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheet

Specifications of PAXT0000

No. Of Digits / Alpha
5
Meter Function
Temperature
Meter Range
-19999 To 99999
Digit Height
14.2mm
Power Consumption
15VA
Operating Temperature Range
0°C To +50°C
Supply Voltage Ac, Min
85V
Brand/series
PAX
Connection Type
Cage-Clamp
Cut Out, Panel
1⁄8 DIN
Dimensions
4.2" L × 3.8" W × 1.95" H
Display Digit Height
0.56 "
Display Resolution
0.1, 0.2, 0.5/1, 2/5 °
Display Type
LED
Function
Temperature
Number Of Digits
5
Primary Type
Electronic
Range, Measurement
-19999 to 99999
Special Features
Programmable Function Keys
Termination
Cage Clamp
Voltage, Supply
85 to 250 VAC
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
3.2 INPUT SIGNAL WIRING
Resistance Signal
(3 wire requiring
excitation)
Terminal 3: Resistance
Terminal 5: Resistance
Terminal 6: Jumper to
Excitation Jumper:
PAXD INPUT SIGNAL WIRING
PAXP INPUT SIGNAL WIRING
Voltage Signal
Terminal 3: +VDC
Terminal 5: -VDC
Voltage Signal
Terminal 3: +VDC
Terminal 5: -VDC
Before connecting signal wires, the Input Range Jumper and Excitation Jumper should be verified for proper position.
(self powered)
1.75 mA REF.
(self powered)
terminal 3
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
Current Signal
(self powered)
Terminal 4: +ADC
Terminal 5: -ADC
Current Signal
(self powered)
Terminal 4: +ADC
Terminal 5: -ADC
Current Signal (2 wire
requiring excitation)
Terminal 4: -ADC
Terminal 6: +ADC
Excitation Jumper: 24 V
Current Signal (2 wire
requiring excitation)
Terminal 4: -ADC
Terminal 6: +ADC
11
Potentiometer Signal
(3 wire requiring excitation)
Terminal 3: Wiper
Terminal 5: Low end of pot.
Terminal 6: High end of pot.
Excitation Jumper: 2 V REF.
Input Range Jumper: 2 Volt
Module 1 Input Range: 2 Volt
Note: The Apply signal scaling style
should be used because the signal will
be in volts.
Current Signal (3 wire
requiring excitation)
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
Voltage Signal (3 wire
requiring excitation)
Terminal 3: +VDC (signal)
Terminal 5: -VDC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
Current Signal (3 wire
requiring excitation)
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: +Volt supply
Voltage Signal (3 wire
requiring excitation)
Terminal 3: +VDC (signal)
Terminal 5: -VDC (common)
Terminal 6: +Volt supply

Related parts for PAXT0000