3RS17051FW00 SIEMENS, 3RS17051FW00 Datasheet - Page 42

INTERFACE CONVERTER

3RS17051FW00

Manufacturer Part Number
3RS17051FW00
Description
INTERFACE CONVERTER
Manufacturer
SIEMENS
Datasheet

Specifications of 3RS17051FW00

Input Type
Selectable Current
Output Type
Selectable Current
Supply Voltage
240V
No. Of Input Channels
1
Mounting Type
DIN Rail
Isolation Input
Isolated
External Width
17.5mm
Input Current Max
20mA
No. Of Channels
1
3RS10, 3RS11 Temperature Monitoring Relays
Relays, digitally adjustable to DIN 3440
Overview
The 3RS10/3RS11 temperature monitoring relays can be used
for measuring temperatures in solid, liquid and gas media. The
temperature is sensed by the sensor in the medium, evaluated
by the device and monitored for overshoot or undershoot or for
staying within an operating range (window function). The 3RS10
40, 3RS20 40, 3RS11 40 and 3RS21 40 relays comply with the
requirements of DIN 3440 as temperature monitors; the 3RS10
42 and 3RS11 42 relays comply with the requirements of DIN
3440 as temperature limiters. The relays are also an excellent
alternative to temperature controls in the
low-end performance range (2 or 3-point closed-loop control).
Benefits
• Very simple operation without complicated menu selections
• Certification to DIN 3440
• All devices are available alternatively with spring-loaded
• 2 or 3-point closed-loop control can be configured quickly
Application
The 3RS10 40, 3RS10 42, 3RS11 40, 3RS11 42, 3RS20 40 and
3RS21 40 temperature monitoring relays can be used in almost
any application in which temperature overshoot or undershoot is
not permitted, e.g. in the monitoring of set temperature limits and
the output of alarm messages for:
• Plant and environment protection
• Temperature limits for process variables e.g. in the packaging
• Temperature limits for district heating plants
• Exhaust temperature monitoring
• Controlling equipment and machines such as heating, climate
• Motor, bearing and gear oil monitoring
• Monitoring of coolants
7/58
terminals
industry or electroplating
and ventilation systems, solar collectors, heat pumps or warm
water supplies
Monitoring Relays
Siemens LV 1 · 2006
The short-circuit and open-circuit detection as well as the
measuring range is limited, depending on the sensor type.
Measuring range in °C for thermocouples
Measuring range in °C for resistance sensors
1) Not for NTC B57227-K333-A1 (100 °C: 1.8 k W ; 25 °C: 32.762 k W ).
Sensor
type
J
K
T
E
N
S
R
B
Sensor
type
PT100
PT1000
KTY 83-110 x
KTY 84
NTC
1
)
Short-circuit Wire
--
--
--
--
--
--
--
--
Short-circuit Wire
x
x
x
x
break
x
x
x
x
x
x
x
x
break
x
x
x
x
--
3RS11 40
Measuring range
in °C
-99 ... +999
-99 ... +999
-99 ... +400
-99 ... +999
-99 ... +999
--
--
--
3RS10 40/41
Measuring range
in °C
–50 ... +500
–50 ... +500
–50 ... +175
–40 ... +300
80 ... 160
400 ... 1800
3RS11 42
Measuring range
in °C
-99 ... +1200
-99 ... +1350
-99 ... +400
-99 ... +999
-99 ... +999
3RS10 42
Measuring range
in °C
–50 ... +750
–50 ... +500
–50 ... +175
–40 ... +300
80 ... 160
0 ... 1750
0 ... 1750

Related parts for 3RS17051FW00