18TB-2-25 PAYNE ENGINEERING, 18TB-2-25 Datasheet

Variable Transformer

18TB-2-25

Manufacturer Part Number
18TB-2-25
Description
Variable Transformer
Manufacturer
PAYNE ENGINEERING
Datasheet

Specifications of 18TB-2-25

Power Supply Output Type
Variable
No. Of Outputs
1
Output Voltage
235VAC
Output Current
25A
Power Rating
6kVA
Length
70mm
Width
102mm
Height
152mm
Transformer Mounting
Chassis
Secondary Current Nom
25A
Current Rating
25A
Input Voltage
240VAC
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Rt. 29 Scott Depot WV 25560-0070
Model 18TBP/TB controls provide infi-
nitely variable control of single-phase
a.c. voltage to resistive heating ele-
ments. These controls are solid-state
replacements for variable transformers,
mercury relays, saturable core reac-
tors, and electromechanical contactors.
Power Triacs replace contacts and
brushes to control electric power with-
out moving parts, and, when operated
within their stated ratings for current,
voltage, and temperature, have no
known MTBF or life expectancy rating.
Description:Variable-Voltage
Power Control
Product Range:120-240 VAC,
5-25 amps.
Application: R esistance Loads
All Solid-State Construction
Short Circuit Protection
Integral Heatsink Chassis
No Thermal Derating
Replace Variable Transformers
Electric Heater Control
Light Dimming
Hot-Wire Cutting
Heat Sealing and Packaging
Plastic Molding and Extruding
Food Preparation Equipment
TYPICAL APPLICATIONS
Model 18TBP/TB
FEATURES
Model 18TBP controls are compact,
lightweight packages that employ
single hole mounting to panels and
enclosure doors. Model 18TB con-
trols are designed for rear or rack
mounting. Both utilize an electrically
isolated heatsink chassis.
Model 18TBP/TB controls incorpo-
rate exclusive design features to
protect power semiconductor com-
ponents against damage. “2 milli-
second” fuses protect against
short-circuit damage; an R-C snub-
ber network protects against dv/dt
failure; an integral heatsink chassis
allows continuous operation in
ambients to 50
Power Circuit: p ower Triac with par-
allel R-C circuit for dv/dt protection
and current-clamping 2 millisecond
fuse for short-circuit protection.
Control Circuit:R-C network with
variable-resistance potentiometer
adjusts firing capacitor into bilateral
diode connected to power Triac gate
for stable, full-range control.
Mains Frequency: 5 0/60 Hz.
Output Voltage:0-95% of input.
Overall Efficiency: 99%.
Power Loss: approximately 1.5
watts/amp.
Voltage Drop Across Power Circuit
at 100% Output: 1-2 volts maxi-
mum/phase.
Control Input:manual control via
variable potentiometer.
Control Power: 1 watt.
Fuse Protection:2 millisecond I
fuses are factory tested and coordi-
nated with all power semiconduc-
tors, considering:
PANEL- OR CHASSIS-MOUNT
Three Pillars Of Protection
EXCLUSIVE ADVANCED
SPECIFICATIONS
TECHNOLOGY:
o
C with no derating.
2
t
APPLICATION ASSISTANCE - 304/757-7354
Ambient Temperature Range: -10 to
+50
Terminal Connections: B akelite or
thermoplastic blocks.
Model 18TBP/TB controls are rated
for use with constant resistance
loads. Size units by actual load cur-
rent, not kW.
1> Always use maximum possible
load current for sizing purposes.
2> The amp rating is determined by
the fuse. Current draw must not ex-
ceed the fuse rating at any time.
3> Rated voltage of connected load
should match control input voltage.
Application: s ingle-phase, 800 watt
nichrome heating element; input
voltage 120 VAC, 60 Hz.
Model Number Selection:
a. Triac-based variable-voltage: SC
b. Panel-mount: E
c. 120 VAC input: 12
d. Amp rating, calculated as follows:
800 = 6.66 amps
120
Since 6.66<10, amp rating: -10
Model Number:SCE12-10.
PERFORMANCE NOTE: Triac
power circuits may “slave” when
multiple units are used on 240 VAC
lines derived from three phase
mains. For optimum performance,
use on single phase, 240 VAC de-
rived from 3-wire, 120/240 VAC
mains.
WHEN ORDERING, SPECIFY:
SIZING CONSIDERATIONS
a. fuse element melt time t
b. peak melt current I
c. arc quench time t
d. peak arc current I
Model Number
Input Voltage
Load Specifications
o
C.
SCR Power Controls
SIZING EXAMPLE
24 HOUR FAX - 304/757-7305
Model 18TBP/TB
arc
arc
melt
;
.
;
melt
;

Related parts for 18TB-2-25

18TB-2-25 Summary of contents

Page 1

... C. Terminal Connections: B akelite or thermoplastic blocks. SIZING CONSIDERATIONS Model 18TBP/TB controls are rated for use with constant resistance loads. Size units by actual load cur- rent, not kW. 1> Always use maximum possible load current for sizing purposes. 2> The amp rating is determined by the fuse ...

Page 2

... MODEL 18TBP F1 TRIAC POWER CIRCUIT SCHEMATIC All dimensions are approximate, and are not to be used for construction purposes. Payne Engineering Company Inc. reserves the right to make changes to product design, construction, and component parts in the interest of technical advancement without prior notification ...