FD3125 EATON CUTLER HAMMER, FD3125 Datasheet - Page 66

CIRCUIT BREAKER, THERMAL MAG, 3P, 125A

FD3125

Manufacturer Part Number
FD3125
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 125A
Manufacturer
EATON CUTLER HAMMER
Series
Cr
Datasheet

Specifications of FD3125

Actuator Style
Toggle
No. Of Poles
3
Current Rating
125A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Screw
12
12-66
Plug-in Blocks
Plug-in adapters simplify installation
and front removal of circuit breakers.
Plug-ins are available for rear connec-
tion applications on 3- and 4-pole
circuit breakers. Trip on drawout
interlock kits are included. Stabs for
EG, JG and LG plug-ins rotate 90° for
flexible installation. Use terminal
shields for IP30 protection.
Product Selection
Table 12-119. Plug-in Blocks
EG-, JG- and LG-Frame Plug-in Blocks
Trip-on Drawout Interlock Kit
Terminal Shields IP30
Position Switch
Breaker
Frame
EG
EG
JG
JG
LG
LG
EG
JG
LG
EG
EG
JG
JG
LG
LG
EG
JG
LG
Included with plug-in block. Trips the breaker
when breaker is removed from plug-in block.
Series G Molded Case Circuit Breakers
15 – 2500 Amperes for UL, CSA & IEC Applications
Plug-in Blocks and Drawout Cassettes
LG Breaker with Plug-in Block
Poles
3
4
3
4
3
4
3, 4
3, 4
3, 4
3
4
3
4
3
4
3, 4
3, 4
3, 4
Catalog
Number
PAD3E
PAD4E
PAD3J
PAD4J
PAD3L
PAD4L
PIILEG
PIILJG
PIILLG
EFTS3K
EFTS4K
FJTS3K
FJTS4K
LTS3K
LTS4K
PADILE
PADILJ
PADILL
Price
U.S. $
Drawout Cassette
The Drawout Cassette is available for
use with JG, LG and NG, 3- and 4-pole
breakers. Also available are drawout
cassettes for use with the standard
3-pole 65 and 100 kA/480 Vac, 1600
ampere and 2000 ampere RG circuit
breakers. The cassettes consist of two
separate components: the movable
mechanism, which attaches to the
breaker, and the stationary mechanism,
which houses in the cassette. The sta-
tionary mechanism is shipped sepa-
rately for the RG frame breakers. For
the JG, LG and NG drawout cassettes,
all necessary parts for installation are
included in the one catalog number.
Features of the drawout cassettes for
the JG, LG and NG include:
For more information visit: www.eaton.com
Trip on drawout — Breaker will
trip if it is in the ON position when
withdrawn from the cassette.
Secondary Terminal Block —
The drawout cassettes include a
secondary terminal block for easier
access when wiring low voltage
accessories, including shunts and
undervoltage releases.
JG and LG Drawout Cassettes
Drawout Cassette
The drawout mechanism has three
primary positions:
Table 12-120. RG Drawout Cassette
65 kA/480 Vac Version
100 kA/480 Vac Version
Movable mechanism must be ordered
with RG circuit breaker and is shipped
mounted to circuit breaker frame.
Stationary mechanism is ordered
separately.
Table 12-121. JG, LG and NG Drawout
Cassettes
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2
Description
Movable
Mechanism
Stationary
Mechanism
Movable
Mechanism
Stationary
Mechanism
Breaker
Frame
JG
LG
NG
Connected — The breaker is fully
connected to the primary stabs and
secondary contacts.
Disconnected — Both the primary
stabs and the secondary contacts
are disconnected.
Withdraw — The breaker can be
removed from the cassette.
List price included in price of the stationary
mechanism.
Without shutters.
With shutters.
Poles
3
4
3
4
3
4
Catalog
Number
RD20DOM
RD20DOS
RD20DOSS
RDC20DOM
RDC20DOS
RDC20DOSS
Catalog
Number
JG3DOM
JG4DOM
LG3DOM
LG4DOM
NG3DOM
NG4DOM
November 2008
CA08101001E
Price
U.S. $
Price
U.S. $

Related parts for FD3125