Specifications of FN5045-17-33

Voltage Rating
500 VAC
Current Rating
17 A
Mounting Style
Bolts
Termination Style
Cable
Product
Power Line Filters
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Technical specifications
Nominal operating voltage:
Motor frequency:
Switching frequency:
Rated currents:
Motor cable length:
Impedance (uk):
Residual ripple voltage:
High potential test voltage:
Protection category:
Overload capability:
Temperature range (operation and storage):
Acoustic noise level:
Insulation class:
Flammability corresponding to:
Design corresponding to:
Environmental reliability:
MTBF:
Approvals:
Declaration of conformity:
Features and benefits
n
n
LC sine wave filter for motor drives
Converts the rectangular PWM output
voltage of motor drives into a smooth sine
wave with low residual ripple.
Elimination of premature motor damage
caused by high dv/dt, overvoltages, cable
ringing, motor overheating, and eddy
current losses.
n
n
n
n
3x 500VAC ±10%
0 to 70Hz (up to 200Hz with derating (see graph))
See filter selection table
4.5 to 1200A @ 45°C
Up to 2,000m (see graph)
8 to 10% @ 400V, 50Hz and rated current
<5%
P –> E 3000VAC, 1 minute
P –> P 2500VAC, 1 minute
IP00 (FN 5040)
IP20 (FN 5045)
1.5x rated current for 1 minute, once per hour
-25°C to +70°C (25/070/21)
<70dB(A) @ 1m
EIS 200
UL 94V-2 or better
IEC 61558-2-20
IEC 60068-2-1
>100,000 hours
UL 508 pending
CE / LVD
n
n
n
Smooth sine wave without voltage peaks
Motor protection against pulse pattern
stress
Improvement of system reliability
Simple to install
Improves bearing life time because of
bearing currents caused by circulating
currents.
Complies with IEC 60034-17* and NEMA-
MG1 requirements for general purpose
motors.
Optional with NEMA 1 protective cover.
Output filters
FN 5040 / FN 5045
Approvals
(in preparation)
Typical electrical schematic
Typical applications
n
n
n
n
n
n
n
n
n
n
n
HVAC applications
Pumps
Ventilators
Conveyors
Compressors
Elevators
Cranes
Medium voltage applications, deployed
in front of the step-up transformer
Retrofit installations with motor drives
Motor drive with long motor cable
Motor drive with multiple motors in
parallel

Related parts for FN5045-17-33

FN5045-17-33 Summary of contents

Page 1

LC sine wave filter for motor drives Technical specifications Nominal operating voltage: Motor frequency: Switching frequency: Rated currents: Motor cable length: Impedance (uk): Residual ripple voltage: High potential test voltage: Protection category: Overload capability: Temperature range (operation and storage): Acoustic ...

Page 2

Components > FN 5040 / FN 5045 Filter selection table Filter Rated current Rated current @ 45ºC/50Hz @ 45°C/100Hz motor drive inductance capacitance [A] FN 5040-4.5-82 4.5 FN 5040-8- 5040-10- 5040-17- 5040-24-84 24 ...

Page 3

Components > FN 5040 / FN 5045 Installation Filter placement n Lift the filter with appro- priate crane using lifting eye bolts – smaller types may be lifted manually by two persons (no lifting eye bolt applicable). Never attempt ...

Page 4

Components > FN 5040 / FN 5045 Motor frequency derating max. current [%] 110 100 100 120 140 Mechanical data FN 5040 4.5 to 75A types A ...

Page 5

Components > FN 5040 / FN 5045 180 to 1200A types Filters from 180 to 660A have only 1 capacitor module Dimensions FN 5040 4. 126 155 B 77 ...

Page 6

Components > FN 5040 / FN 5045 Mechanical data FN 5045 4.5 to 38A types 180 to 480A types 115A types 660 ...

Page 7

Components > FN 5040 / FN 5045 Dimensions FN 5045 4.5A 8A 10A 17A A 330 330 330 440 B 100 100 100 160 C 165 165 165 245 E 310 310 310 400 110 ...