GA400 Tyco Electronics, GA400 Datasheet

LINE CORD 7.5' W/3CONDUCTORS BLK

GA400

Manufacturer Part Number
GA400
Description
LINE CORD 7.5' W/3CONDUCTORS BLK
Manufacturer
Tyco Electronics
Datasheet

Specifications of GA400

Connector Type
NEMA 5-15P to IEC 320-C13
Cord Type
SVT, 18AWG
Length
7.5' (2.286m)
Conductors
3
Color
Black
Approvals
CSA, UL
Conductor Size Awg
18
Voltage Rating
125V
Current Rating
10A
Jacket Color
Black
Connector Type B
Power Socket
Connector Type A
Power Plug
Cable Assembly Type
Power Cord
Cable Length
7.5ft
Filter Type
Accessories
Product
Accessories
Type Of Inlet
Accessories
Filtered
No
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
6HJ4-2 - INPUT MODULE MED FILTERED 6A6J4-2 - INPUT MODULE FILTERED 6A6VJ1-2 - INPUT MODULE UNFILTERED 6ACCM1202 - MODULE POWER ENT FUSED FILT MEDCCM1201 - MODULE POWER ENT FUSED FILTER GPCCM1200 - MODULE POWER ENT FUSED UNFILTER
Features
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
1609142-1
CCM1819
GA400

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
GA400-3
Manufacturer:
BROADBAND
Quantity:
658
Part Number:
GA400DD120K
Manufacturer:
IR
Quantity:
1 000
Part Number:
GA400DD120K
Quantity:
55
Part Number:
GA400DD60U
Quantity:
55
Part Number:
GA400HD60U
Manufacturer:
Danfuss
Quantity:
1 000
Part Number:
GA400HD60U
Quantity:
55
Part Number:
GA400LD60U
Manufacturer:
IR
Quantity:
1 000
Part Number:
GA400LD60U
Quantity:
55
Part Number:
GA400TD25S
Manufacturer:
SANYO
Quantity:
2 100
Part Number:
GA400TD25S
Quantity:
57
114
J Series
J Series
The most widely accepted of all the power entry modules,
the J series combines an IEC connector, 2-voltage, or 4-
voltage selection, and a North American fuseholder. It
features a compact snap-in design and a unique voltage
selector card.
J4 Models - This general purpose filter provides
susceptibility protection from line-to-ground noise on the
power line and acts as a high frequency “clean-up” filter for
more complex emissions applications.
HJ4 Models - This medical filter provides susceptibility
protection without the leakage current associated with line-
to-ground capacitors. Designed to allow equipment to
meet UL544 medical specifications for patient care and
non-patient care equipment, the HJ filter has a maximum
leakage current of 2µA at 120 VAC 60 Hz. See Appendix
C for more information on medical applications and UL
standards.
Equipment rating labels and mounting clips for thicker
panel widths are available as accessories.
For more information on UL544 specifications, see
Appendix C.
Note: When using the models with an IEC connector,
remember that the leakage current of the companion line
cord, GA400, is more significant than that of the filter -
which may disqualify this line cord from use in patient care
applications.
Catalog 1654001
Revised 04-06
UL Recognized
CSA Certified
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
CORCOM Product Guide
Voltage Selecting and Fused Connector with Optional RFI Power Line Filter for
General Purpose Applications for UL544 Health Care Equipment
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
Voltage Selection
Unfiltered and Filtered Models
Open cover door and rotate fuse-pull lever to left. Select
operating voltage by orienting voltage selection card,
desired voltage on top left side. Push card firmly into
module slot. Rotate fuse-pull lever back into normal
position and re-insert fuse into holders. Use caution in
selecting correct fuse value.
Unfiltered Models
Unfiltered Models
Note 1: General purpose filter for susceptibility applications
Note 2: Medical line filter for very low leakage UL544 health care requirements
Part Number
Part Number
6VJ1-2
6HJ4-4
6HJ4-2
Front View, All Models
6J4-2
6VJ1
6VJ4
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
Germany:
Available Voltage
Positions
Selection
49-89-6089-0
6HJ4-1/6HJ4-2
Terminal View
Available Voltage Selection
4
2
4
2
Positions
4
2
General Purpose
General Purpose
RFI Filter
Medical
Medical
www.corcom.com
www.tycoelectronics.com
Type
Terminal View
6J4/6J4-2
2
2
1
1

Related parts for GA400

GA400 Summary of contents

Page 1

... For more information on UL544 specifications, see Appendix C. Note: When using the models with an IEC connector, remember that the leakage current of the companion line cord, GA400, is more significant than that of the filter - which may disqualify this line cord from use in patient care applications. 114 ...

Page 2

CORCOM Product Guide Voltage Selecting and Fused Connector with Optional RFI Power Line Filter for General Purpose Applications for UL544 Health Care Equipment J Series Electrical Schematics Electrical Schematics Filtered 6J4 & 6J4-2 Power On-Off Off Hot Ground Pilot On ...

Page 3

CORCOM Product Guide Voltage Selecting and Fused Connector with Optional RFI Power Line Filter for General Purpose Applications for UL544 Health Care Equipment J Series Case Styles Unfiltered Models Note 5 A Filtered Models Note 116 Catalog ...

Page 4

... Dimensions are in inches and Revised 04-06 millimeters unless otherwise specified. Values in italics are metric equivalents. Accessories Unfiltered and Filtered Models Line Cord No. GA400: (7 1/2 foot, 3-conductor line cord to mate with J series) JA302, 2 Voltage Selector Card (comes standard with 6VJ1-2, 6J4-2, 6HJ4-2) 120V 220V 240V ...

Related keywords