C25BNB240A Eaton / Control Automation, C25BNB240A Datasheet

no-image

C25BNB240A

Manufacturer Part Number
C25BNB240A
Description
CONTACTOR; DP; 2 POLE; 40A; 120VAC COIL
Manufacturer
Eaton / Control Automation
Datasheet

Specifications of C25BNB240A

Coil Voltage
120
Current, Rating, Inductive
40
Current, Rating, Resistive
50
Horsepower, Motor, Max At 115 V
3
Horsepower, Motor, Max At 230 V
7.5
Number Of Poles
Double-Pole
Temperature, Operating, Maximum
+70 °C
Temperature, Operating, Minimum
–25 °C
Insulation Voltage
690 V
Contacts
Double Break
Magnet Coil
Class F, 155°C
Operating Temperature Range
–13 to 158°F (–25 to +70°C)
Terminal Wire Range — Hex Washer Head Screws
16-10 AWG, 30 Lb.-In. Torque Rating
Mounting Position
Vertical, Horizontal or Tabletop
May 2007
Application Description
These Cutler-Hammer
devices from Eaton’s electrical business are designed for
service in applications such as Refrigeration, Air Conditioning
and Resistance Heating and are manufactured to traditional
Cutler-Hammer standards for quality and reliability. They are
subjected to stringent quality assurance inspections and
Catalog Number Selection
Table 1. Definite Purpose Control Catalog Numbering System
PG03502001E
25 = Non-reversing Contactors & Starters
27 = Non-reversing Starters
29 = Non-reversing Starters
65 = Reversing Contactors
C = Contactor
A = Three-Phase Starter
B = Single-Phase Starter
A = Binding Head Screw
B = Binding Head Screw and Quick Connect
C = Screw/Pressure Plate
D = Screw/Pressure Plate and Quick Connect
E = Box Lugs (Posidrive Setscrew)
F = Box Lugs (Posidrive Setscrew) and Quick
G = Binding Head Screw and Quick Connect
H = Screw/Pressure Plate and Quick Connect
J = Box Lugs (Posidrive Setscrew) and Quick
K = Box Lugs (Hex Socket Allen Head Setscrew)
L = Box Lugs (Hex Socket Allen Head Setscrew) and
M =Box Lugs (Hex Socket Allen Head Setscrew) and
N = Open with Metal Mounting Plate
R = Open with DIN Rail Mounting Adapter
G = NEMA Type 1 Enclosed
Not available on 50A devices.
Terminals (side by side)
Terminals (side by side)
Connect Terminals (side by side)
Terminals (vertical in-line)
Terminals (vertical in-line)
Connect Terminals (vertical in-line)
Quick Connect Terminals (side by side)
Quick Connect Terminals (vertical in-line)
(2- and 3-Pole, 15 – 50A Contactors Only)
A = Compact 1-Pole
B = Compact 2-Pole
C = Compact 1-Pole W/Shunt
D = 15 – 50A, 2- and 3-Pole
E = 25 – 40A, 4-Pole
F = 60 – 75A, 2- and 3-Pole
G = 90A, 2- and 3-Pole
H = 120A, 2- and 3-Pole
K = 200 and 300A, 3-Pole
L = 360A, 3-Pole
C = Common Control Wiring
S = Separate Control Wiring
Model
Contactor Frame Size
Type
For Starters Only
Enclosure Type
®
Power Terminals
ampere and horsepower rated
C 2 5 D N A 2 1 5 A A 1 6 1 - 8 4
For more information visit: www.eaton.com
Definite Purpose Control
Product Family Overview
1 = 1-Pole
2 = 2-Pole
3 = 3-Pole
4 = 4-Pole
No. of Poles
testing procedures. The life expectancy, both electrical and
mechanical, will meet or exceed industry performance
requirements for Definite Purpose devices.
If more detailed technical information is required — specifi-
cations, ratings, etc. — contact your local Eaton distributor
or sales office.
15 = 15A
25 = 25A
30 = 30A
40 = 40A
50 = 50A
60 = 60A
A = 110 – 120V AC, 50/60 Hz
B = 208 – 240V AC, 50/60 Hz
C = 440 – 480V AC, 50/60 Hz
D = 550 – 600V AC, 50/50 Hz
H = 277V AC, 60 Hz
J = 220 – 240 V AC, 50/60 Hz
L = 380 – 415V AC, 50 Hz
A = 1NO Pressure Plate
B = 1NC Pressure Plate
C = 1NO-1NC Pressure Plate
D = 2NO Pressure Plate
E = 2NC Pressure Plate
F = 1NO Pressure Plate and QC
G = 1NC Pressure Plate and QC
H = 1NO-1NC Pressure Plate and QC
J = 2NO Pressure Plate and QC
K = 2NC Pressure Plate and QC
L = 1NO-1NC Snap Switch QC Only
M =2NO-2NC Snap Switch QC Only
Current Rating
Auxiliary Contacts (Side Mount)
161 = Class M, 600V, 30A
237 = Class G, 300V, 15A
238 = Class G, 300V, 20A
231 = Class G, 300V, 30A
232 = Class G, 300V, 60A
361 = Class J, 600V, 30A
362 = Class J, 600V, 60A
431 = Class T, 300V, 30A
432 = Class T, 300V, 60A
461 = Class T, 600V, 30A
462 = Class T, 600V, 60A
521 = Class H, 250V, 30A
522 = Class H, 250V, 60A
621 = Class R, 250V, 30A
622 = Class R, 250V, 60A
120 = 120A
200 = 200A
300 = 300A
360 = 360A
75 = 75A
90 = 90A
Coil Selection
Fuse Blocks
Blank = individual pkg.
-84 = 20 pc./pkg. (C25D_)
-86 = Rotate coil terminals 180°
R =
T =
1R = 12V DC
1T = 24V DC
1W = 48V DC
1A = 120V DC
50 pc./pkg. (C25A_,
C25B_, C25C_)
for 15A – 50A Contactors
Bulk Packaging
12V AC, 50/60 Hz
24V AC, 50/60 Hz
1

Related parts for C25BNB240A

C25BNB240A Summary of contents

Page 1

May 2007 Application Description ® These Cutler-Hammer ampere and horsepower rated devices from Eaton’s electrical business are designed for service in applications such as Refrigeration, Air Conditioning and Resistance Heating and are manufactured to traditional Cutler-Hammer standards for quality and ...

Page 2

Definite Purpose Control 2 Contactors 20 – 40A, Compact 1- and 2-Pole — C25 Contents Description Page Compact 1- and 2-Pole Contactors 20 – 40A Product Description . . . . . . . 2 Standards and Certifications . . ...

Page 3

May 2007 Compact 1-Pole Compact 1-Pole with Shunt Compact 2-Pole Dimensions 0.03 0.21 (0.8) (5.2) 1.50 1.77 2.40 (38) (45) (61) 1.61 (41) 1.97 (50) 1-Pole and 1-Pole +Shunt Ship. Wt.: 0.5 lb. (0.2 kg) Figure 1. Compact Approximate Dimensions ...

Page 4

Definite Purpose Control 4 Contactors 15 – 360A, 2-, 3- and 4-Pole — C25 Contactor Product Description ® Cutler-Hammer Type C25 Definite Purpose Contactors 15A through 360A, from Eaton’s electrical business incor- porate most competitive contactor mounting ...

Page 5

May 2007 Product Selection When Ordering Specify ■ Catalog Number plus Magnet Coil Suffix, below. Table 12. C25 Contactors Product Selection— Open Type Rating, Amperes Maximum Motor Horsepower Inductive Resistive Line Locked 1-Phase Full Load per Pole Voltage Rotor 15 ...

Page 6

Definite Purpose Control 6 Contactors 15 – 360A, Options and Accessories Options — Factory Installed To order C25, C65, A25 and B25 Contactors and Starters with the factory installed options listed below, change the basic Catalog Number listed in the ...

Page 7

May 2007 Magnet Coil Quick Connect Terminal Table 18. Magnet Coil Quick Connect Terminal Description Extra Dual Quick Connect Terminals (U-shaped) for Magnet Coil Terminals To order, add Suffix Number 9 to the complete Catalog Number. Example: C25DND215A9. Auxiliary Contact ...

Page 8

Definite Purpose Control 8 Contactors 15 – 40A, 3-Pole Fuse Block Optional 3-Pole Fuse Block Available only on 3-Pole, 15 – 50A Contactors Designed to save space and reduce installation costs, these 3-pole Fuse Blocks will accommodate a variety of ...