XTMC9A10TD Eaton / Control Automation, XTMC9A10TD Datasheet

no-image

XTMC9A10TD

Manufacturer Part Number
XTMC9A10TD
Description
MINI CONTACTOR; 3 POLE; 9 AMP; FRAME A; 1NO AUX; 24VDC COIL
Manufacturer
Eaton / Control Automation
Datasheet

Specifications of XTMC9A10TD

Coil Voltage
24
Contacts
1 NO
Current, Operational, At 380 To 400 V
8.8
Function
Non-Reversing
Horsepower, Max, 1 Phase, At 115 V
0.5
Horsepower, Max, 1 Phase, At 200 V
1
Horsepower, Max, 1 Phase, At 230 V
1.5
Horsepower, Max, 3 Phase, At 200 V
2
Horsepower, Max, 3 Phase, At 230 V
3
Horsepower, Max, 3 Phase, At 460 V
5
Horsepower, Max, 3 Phase, At 575 V
5
Temperature, Operating, Maximum
+50 (+122) °C (°F)
Temperature, Operating, Minimum
–25 (–13) °C (°F)
Type Of Contactor
Electro Mechanical
Voltage, Input
24 VDC
Lead Free Status / Rohs Status
RoHS Compliant part
14
Contents
Description
Catalog Number
Product Selection . . . . . . . . . .
Accessories . . . . . . . . . . . . . . .
Technical Data and
Dimensions . . . . . . . . . . . . . . .
Reference Data . . . . . . . . . . . . .
Product Description
Eaton’s new line of Cutler-Hammer
XT Miniature Controls includes non-
reversing and reversing mini contactors,
mini overload relays and snap-on
accessories. A wide range of applica-
tions is possible including small
electrical motors from fractional to
5 hp (460V AC) or up to 4 kW
(400V AC).
Selection . . . . . . . . . . . . . . . .
Specifications . . . . . . . . . . . .
Non-reversing
Reversing Mini
Star-Delta (Wye-Delta)
Overload Relays. . . . . . . . . .
XT IEC Power Control
Miniature Controls
Product Family Overview
Mini Contactors . . . . . . . . .
Contactors . . . . . . . . . . . . .
Miniature Contactors . . . .
XTMC Mini Contactor
Page
15
16
16
16
18
19
20
23
28
199
®
Application Description
Due to its compact size, the XT line of
mini controls is best suited to be
applied in light duty loads such as
hoisting, packaging, material handling,
heating, lighting and automation sys-
tems. XT mini contactors are a particu-
larly compact, economic and
environmentally friendly solution
wherever control of small motors or
loads is required.
Features
Mini Contactors — Types XTMC
and XTMF, 6 – 9A
Mini Overload Relays — Bimetallic
Type XTOM
For more information visit: www.eaton.com
AC Control from 12V to 550V 50 Hz,
600V 60 Hz
DC Control from 12V to 220V
Available with screw or spring cage
terminals
Reversing or Non-reversing
3 and 4-Pole Configurations
Panel or DIN rail mounting
IP20 finger and back-of-hand proof
Low noise operation
High degree of climatic proofing
Large ambient temperature range
-25° to 50°C [-13° to 122°F]
Phase failure sensitivity
Direct mount to XTMC and XTMF
Mini Contactors
Trip Class 10
11 settings to cover 0.1 to 12A
Ambient temperature compensated
-5° to 50°C [23° to 122°F]
Manual and automatic reset by
selector switch
1 Make (NO) or 1 Break (NC) auxil-
iary contact as standard
Test/Off Button
Trip-free release
3-Pole XTMC
4-Pole XTMF
Standards and Certifications
Instructional Leaflets
Pub51219
Pub51243
Pub51206
MN03402002E XTOM Mini Overload
IEC EN 60947
CE Approved
UL
CSA
ATEX
CCC
Inside of Packaging
XTMC, XTMF Mini
Contactors, XTRM
Mini Control Relay and
Accessories
Inside of Packaging
XTOM Mini Overload
Relays
Mini Reversing Link
Kits
Relays Installation and
User Manual
CA03407001E
May 2007

Related parts for XTMC9A10TD

XTMC9A10TD Summary of contents

Page 1

XT IEC Power Control 14 Miniature Controls Product Family Overview Contents Description Page Catalog Number Selection . . . . . . . . . . . . . . . . 15 Product Selection . . . . . ...

Page 2

May 2007 Catalog Number Selection Table 22. XT IEC Miniature Contactors — Catalog Numbering System Designation IEC Power Control Type MC = 3-Pole FVNR Mini IEC Contactor ...

Page 3

XT IEC Power Control 16 Miniature Controls Product Selection Product Selection Non-reversing Mini Contactors Table 24. Full Voltage Non-reversing Contactors Opera- Conven- Maximum tional tional kW Ratings AC-3 Current Free Air 3-Phase Motors AC-3 Amp Thermal 50 – ...

Page 4

May 2007 Table 26. Magnet Coil Suffix Coil Voltage Suffix Coil Voltage Code 110V 50 Hz, 120V 415V 50 Hz, 480V 60 Hz 220V 50 Hz, 240V 550V 50 Hz, 600V 60 Hz 230V ...

Page 5

XT IEC Power Control 18 Miniature Controls Product Selection Star-Delta (Wye-Delta) Miniature Contactors Table 27. Star-Delta (Wye-Delta) Miniature Contactor Configuration Maximum kW Ratings AC-3 Maximum 3-Phase Current Motor Rating 3-Phase Motors 50 – 1-Phase hp Ratings 220/230/ 380/400/ ...

Page 6

May 2007 Overload Relays Table 30. Mini Overload Relays Overload Trip Contact Contact Release I Class Sequence Configuration t 0.1 – 0.16A 10A 1NO-1NC 97 95 0.16 – 0.24A 0.24 – 0.4A 0.4 – 0. ...

Page 7

XT IEC Power Control 20 Miniature Controls Accessories Accessories Auxiliary Contacts Front mounted snap-on auxiliary contacts for mini contactors are available with screw or spring cage terminals in a variety of contact configurations. Auxiliary contact modules are standard with interlocked ...

Page 8

May 2007 RC Suppressor Table 32. RC Suppressor Voltage For Use Circuit Package with… Symbol Qty. 24 – 48 XTMC6A… XTMC9A… 48 – 130 XTMC6A…, 10 XTMC9A… A2 110 – 250 XTMC6A…, 10 XTMC9A… 24 – 48 XTMCC6A…, ...

Page 9

XT IEC Power Control 22 Miniature Controls Accessories Star-Delta (Wye-Delta) Bridge Table 37. Star-Delta (Wye-Delta) Bridge Contact Sequence Package Qty. 20 Price listed is for a quantity of one (1). Orders must be placed in multi- ples of package quantity ...

Page 10

May 2007 Technical Data and Specifications Table 41. XT Miniature Controls — General Specifications Description Physical and Electrical (Continued) Standards Weights in kg [lb] Mechanical Life — Operations Mechanical Life — Coil @ 50 Hz Maximum mechanical operating frequency (ops/hr) ...

Page 11

XT IEC Power Control 24 Miniature Controls Technical Data and Specifications Table 42. XT Miniature Controls — Magnet Systems Description Voltage Tolerance Pick- Single-voltage coil 50 Hz and dual-voltage coil 50 Hz Dual frequency ...

Page 12

May 2007 Table 43. XT Miniature Controls Description AC-1 Operation Conventional free air thermal current, 3-pole, 50 – (A) at 40° 50° 55° Conventional free air thermal ...

Page 13

XT IEC Power Control 26 Miniature Controls Technical Data and Specifications Table 45. XT Miniature Controls — Auxiliary Contacts Description Interlocked opposing contacts to ZH1/457, including auxiliary contact module Rated impulse withstand voltage, U imp (VAC) Overvoltage category / pollution ...

Page 14

May 2007 Electrical Switching Operation Charts Squirrel-cage motors Operating characteristics Starting: from rest Stopping: after attaining a full running speed Electrical Characteristics — Make (NO rated motor current Breaking (NC): 1x rated motor current ...

Page 15

XT IEC Power Control 28 Miniature Controls Dimensions Dimensions D 58 [2.28 [1.77] XTMC D 52 [2.05 [3.27] Figure 27. Non-reversing Mini Contactor 61 [2.40] 180 [7.09] 108 [4.25] Figure 28. Star-Delta Starter Combinations 61 [2.40] ...