OUTPUT SPECIFICATIONS 1
Operating Voltage (47-63 Hz) [Vrms]
Load Current Range
Transient Overvoltage [Vpk]
Max. Surge Current, (16.6ms) [Apk]
Max. On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (R θJC ) [°C/W]
Maximum I 2 t for Fusing, (8.3 msec.) [A 2 sec]
Max. Off-State Leakage Current @ Rated Voltage [mArms]
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]
Max. Turn-On Time
Max. Turn-Off Time
Power Factor (Min.) with Max. Load
INPUT SPECIFICATIONS 1
Control Voltage Range
Max. Turn-On Voltage
Min. Turn-Off Voltage
Nominal Input Impedance
Typical Input Current
GENERAL NOTES
1
2
3
4
SERIES 53TP.
Rev. 100107
PAGE 1 OF 3
All parameters at 25ºC and per section unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 2.
Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).
4
3
[Arms]
M O D E L N U M B E R S
2
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Inc., 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 606030 • FAX +44 (0)1202 606035 Crydom SSR Ltd., Arena Business Centre,
Holyrood Close, Poole, Dorset BH17 7FJ, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
• SCR Output
• LED Status Indicator
• Protective Cover Available
• Panel Mount
• Integrated Overvoltage
(Part No. KS300)
Protection by Automatic
Self Turn-On (Suffix P)
D53TP25D
1/2 Cycle
1/2 Cycle
48-530
.05-25
1200
1.02
250
260
500
1.6
0.5
10
DC CONTROL
10mA @ 5 Vdc
450 Ohms
3-32 Vdc
3.0 Vdc
1.0 Vdc
D53TP50D
1/2 Cycle
1/2 Cycle
© 2007 CRYDOM Inc., Specifications subject to change without notice.
48-530
.05-50
1200
1620
625
500
1.6
.63
0.5
10
25-50Amp • 240/480 Vac - 3 PHASE
Three-phase solid state relays switch up
to 530 Vrms directly to loads such as
motors, transformers, heating elements,
etc. Available with either AC or DC
input (coil) control in zero-voltage or
random turn-on switching versions.
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
2.2mA @ 120 Vrms, 4.4mA @ 240 Vrms
Series
A53TP25D
10.0 msec
40.0 msec
48-530
.05-25
1200
1.02
250
260
500
1.6
0.5
10
90-280 Vrms (60Hz)
AC CONTROL
54.8k Ohms
90 Vrms
10 Vrms
53TP
A53TP50D
10.0 msec
40.0 msec
48-530
.05-50
1200
1620
625
500
1.6
.63
0.5
10

Related parts for D53TP50D

D53TP50D Summary of contents

Page 1

... Vrms directly to loads such as motors, transformers, heating elements, etc. Available with either input (coil) control in zero-voltage or random turn-on switching versions. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability. D53TP50D A53TP25D 48-530 48-530 .05-50 .05-25 1200 1200 ...

Page 2

... Screws - 10 in. lbs. (1.1Nm), 8-32 and 10-32 Screws - 20in. lbs. (2.2Nm) (Screws dry without grease.) 100 0.5ºC/W 105 1ºC/W 110 1.5ºC/W 115 120 Max Ambient Temp. [ºC] A53TP50D, D53TP50D 90 .25ºC/W 95 .5ºC/W 100 105 1ºC/W 110 115 1.5ºC/W 120 Max Ambient Temp. [º ...

Page 3

DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / PERIGO HAZARD OF RIESGO DE ELECTRIC DESCARGA SHOCK, ELECTRICA O EXPLOSION, EXPLOSION. OR ARC FLASH. • Desconectar • Disconnect all todos los suministros de power before energia a este installing or ...

Page 4

ANNEX – ENVIRONMENTAL INFORMATION: The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products. ...

Related keywords