MTC600 Emerson Network Power, MTC600 Datasheet - Page 15
MTC600
Manufacturer Part Number
MTC600
Description
Microtca
Manufacturer
Emerson Network Power
Datasheet
1.MTC600.pdf
(19 pages)
Available stocks
Company
Part Number
Manufacturer
Quantity
Price
Electromagnetic Compatibility
All Models
AC Models
-48 Vdc Models
Radiated Emissions
EN55022, Class A
GR-1089-CORE
Conducted Emissions
EN55022, Class A
GR-1089-CORE
ElectroStatic Discharge
EN61000-4-2
Radiated Immunity
EN61000-4-3
Conducted Immunity
EN61000-4-6
Voltage Dips & Interruptions
EN61000-4-11
Fast Transients
EN61000-4-4
Surge
EN61000-4-5
Fast Transients
EN61000-4-4
Surge
EN61000-4-5
Standard
Per Section 6
Per Section 3.2
Per Section 6
Per Section 3.2
8 KV Contact, 15 KV Air discharge
10 V/m (level measure unmodu-
lated) 80% AM, 1 KHZ
3 V (level measured unmodulated)
80% AM, 1HKz
-100% for 10 ms @ 0°;
-100% for 10 ms @ 180°;
-60% for 100 ms;
-30% for 500 ms;
-100% for 5 s
5/50 ns 5 KHz pulse
1 KV direct
1.2/50 μsec pulse
2 KV Line to Earth
1 KV Line to Line
5/50 ns 5 KHz pulse
500 V direct
1.2/50 μsec pulse
500 V Line to Earth
500 V Line to Line
Limits & Test Parameters
150 KHz to 30 MHz
150 KHz to 80 MHz
Frequency Range
10 KHz to 30 MHz
10 KHz to 10 GHz
80 MHz to 1GHz
3 MHz to 1 GHz
Impulsive
Impulsive
Impulsive
Impulsive
Impulsive
Impulsive
Embedded Power for
Business-Critical Continuity
Criteria
N/A
N/A
N/A
N/A
B,C
A
A
B
B
B
B
B
MTC600 Series
Rev. 05.26.08
15 of 19