e5cn-q2tu Omron Corporation, e5cn-q2tu Datasheet
e5cn-q2tu
Related parts for e5cn-q2tu
e5cn-q2tu Summary of contents
Page 1
... This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) ( mm) 48 × ...
Page 2
... Temperature input 1 control output Analog input Option Units E53-CN@@@ Applicable Controller CN: E5CN or E5CN-H 2. Function 1 Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection ...
Page 3
... VAC Silver 24 VAC/VDC Note: Models with analog inputs do not have temperature unit indicators. Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Communications 3-phase heater burnout/SSR failure/ RS-485 Heater overcurrent detection Heater burnout/SSR failure/Heater ...
Page 4
... Current output Relay output Thermocouple or resistance 1 Voltage output (for driving SSR) E5CN-Q1TU thermometer Current output Relay output 2 Voltage output (for driving SSR) E5CN-Q2TU Current output Relay output 1 Voltage output (for driving SSR) E5CN-Q1LU Current output Analog (current/voltage) Relay output 2 Voltage output (for driving SSR) E5CN-Q2LU ...
Page 5
... USB-Serial Conversion Cable Model E58-CIFQ1 Terminal Cover Connectable models Terminal block models Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Model Y92S-29 Note: The Waterproof Packing is included with the Controller only for models with terminal blocks. Current Transformers (CTs) Hole diameter 5 ...
Page 6
... model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) E5CN Power 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) consump- 100 to 240 VAC (max.) ...
Page 7
... JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Voltage E5CN/E5CN-U Infrared temperature sensor 115 140 120 II 70° ...
Page 8
... Set value: 5, Upper- and lower-limit with standby sequence X ON Always OFF when the upper-limit and lower-limit hysteresis OFF overlaps OFF OFF 0 E5CN/E5CN-U Case 2 Case 3 (Always ON) H < < < > > < 0 H ≥ L ...
Page 9
... Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1 Setup Tool port USB-Serial Conversion Cable is required to connect the computer to the E5CN. *6 Approved UL 61010-1, CSA C22 ...
Page 10
... ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 E5CN 250 VAC, 30 VDC 3 (resistive load) cosφ ...
Page 11
... DO NOT USE B Input power supply B • 100 to 240 VAC TC/Pt universal input • 24 VAC/VDC (no polarity) E5CN/E5CN-U A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. E53-CNPHN2 E53-CNP03N2 External Power Communications (RS-485) Supply and CT ...
Page 12
... Nomenclature E5CN E5CN-U The front panel is the same for the E5CN and E5CN-U. Operation indicators Dimensions E5CN Terminal Models 48 × Waterproof Packing (Accessory) E5CN-U Plug-in Models 48 × Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 Temperature unit Level Key Mode Key ...
Page 13
... Two, 3.5 dia. 2.36 dia dia. 9 Two, M3 (depth: 4) Armature Lead E5CN/E5CN-U E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω 100 ∞ 10 Distortion 1 kΩ factor 10% 1 ...
Page 14
... Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets Protective Cover for finger protection (Y92A-48G) is also available. 4.7 69.6 to 77.6 72 × 72 Panel ( mm) 72 × × 48 2.2 4.7 77.3 (to back of E5CN) Terminal Layout/Internal Connections 3 4.5 7.8 (Top View 35.4 Two ...
Page 15
... OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ Read and Understand This Catalog Warranty and Limitations of Liability Application Considerations Disclaimers In the interest of product improvement, specifications are subject to change without notice. (c)Copyright OMRON Corporation 2009 All Right Reserved. 2009.4 ...