TL100048 TDK Corporation, TL100048 Datasheet

PWR SUP FNT END 48V 1000W 20A

TL100048

Manufacturer Part Number
TL100048
Description
PWR SUP FNT END 48V 1000W 20A
Manufacturer
TDK Corporation
Series
TLr
Datasheets

Specifications of TL100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 20A
Size / Dimension
11.12" L x 3.41" W x 3.45" H (282.4mm x 86.6mm x 87.6mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 65°C
Efficiency
92%
Approvals
CE, CSA, EN, UL
Line Regulation
±1%
Load Regulation
±1%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
20A
Power Rating
1000W
Input Voltage
90V AC To 264V AC
Length
282.448mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
285-1646
F e a t u r e s a n d B e n e f i t s
S p e c i f i c a t i o n s
Feature
ITEMS
Output Voltage Range
Total Regulation
Current limit
Short Circuit Current
Output Noise
Output Rise Time
Dynamic Response
Overvoltage Protection
Load sharing
I2C programming
Signals (opto isolated)
Remote On/Off
Auxiliary Output
AC Input
Power Factor
Inrush Current
Leakage Current
Efficiency (typical)
Immunity
EMC (conducted and radiated)
Operating Temperature
Storage Temperature
Humidity
Altitude
Shock
Vibration
Safety Agency
Size (L x W x H)
Weight
Warranty
(1) Contact Factory for application
(2) All three signals share a common return - Logic GND
2U high
Hotswap capable
High efficiency
Full array of signals
MODEL
(1)
(3)
(1)
(2)
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
VDC
VDC
mA
mV
lbs
%
%
%
A
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-40°C to +65°C, short duration at 75°C, no derating (TL250048: -40°C to 65°C)
11.12” x 3.41” x 3.45” (stand alone), 14” x 18.9” (incl. ears) x 3.45" (TLR5 rack)
TL1000: 90~264VAC, 95VAC start up; TL1500-2500: 180~264VAC, 185VAC start up
Converter OK, AC Present, and Over-temperature alarms. Active Low on Fail
Set Output Volt., Monitors AC Present, Converter OK, Thermal profile, Fan fail
1000 to 2500W Front End Power Supplies
UL60950, CSA 22.2 No. 60950-00, EN60950, CE Mark
-200 to 8000 feet, derate max. ambient 2°C/1000 feet
24V Nominal
27 to 30V
(Factory Set)
480mV maximum, peak to peak (10Hz to 20MHz)
21 - 28V
IEC68-2-64 (random) 20 - 200Hz, 30 minutes
3% in 10ms for a 10 - 100% load change
Benefit
Stand alone unit: 5.6lbs, Rack: 9.5lbs
Power for Distributed Power Architecture
Factory Automation
Shuts down output(s) by applying 5V
K e y M a r k e t S e g m e n t s & A p p l i c a t i o n s
Utilizes less cabinet space
Suitable for N+1 redundancy
Higher density
Easier system monitoring
0.99 Typical meets EN61000-3-2
IEC68-2-27, MIL STD 810E, 20G
(3) Factory Programmable
EN61000-4-2, -3, -4, -5, -6, -8
EN55022, level B, FCC Class B
2U high
Up to 12,500W in 19" rack
Hotswap capable
>90% efficiency
Full power at 65°C ambient
5 - 95% RH non condensing
12V 0.1A bias voltage
TL Series
150% maximum
-40 to +85°C
105 to 120%
100 - 400ms
Two Years
<3.2mA
±10%
<40A
92%
±1
48V Nominal
(Factory Set)
54 to 60V
42 - 56V
77